Loading...
HomeMy WebLinkAboutUS FOREST SERVICE, SITE EXPANSION - SITE PLAN ADVISORY REVIEW - 30-01 - CORRESPONDENCE - (3)r Department: Zoning Issue Contact: Peter Barnes Plans should be on 24 x 36 size sheets, but since this is an advisory review, well... 3 Issue Contact: Peter Barnes Should provide a landscape plan. 4 Pedestrian connection to Hemlock? Issue Contact: Peter Barnes 5 Issue Contact: Peter Barnes need interior parking lot landscape islands per 3.2.1(E)(5) Department: Park Planning The site plan indicates there will be off -site grading within the property to the south. An off - site easement will be necessary for the installation and placement of any storm drainage facilities which extend off of the property. Since the property to the south is City parkland, an easement may only be granted by the Fort Collins City Council. An easement dedication will need to be coordinated through the City of Fort Collins Parks and Recreation Department. If a connection to the City trail south of this site, coordination will need to occur with the Parks and Recreation Department. Outside Review Agency: Excel Energy Any new facilities will need Public Service Company to install gas main and service lines to each individual building. Contact Rick Traynor @ 970-225-7827 to schedule installation. If you have any questions regarding these issues or any other issues related to this project, please feel free to call me at (970) 221-6750. SinC�� Bob Barkeen City Planner Page 1 13 Issue Contact: Michael Chavez Required Access: A fire lane is required. The fire lane shall be visible by painting and signage, and maintained unobstructed. Minimum turning radius of access roadways must be 20 feet inside and 40 feet outside. All access roadways must be an all weather driving surface capable of supporting fire apparatus. Surface shall be asphalt, concrete, or compact road base. Surface criteria may be obtained from City or County engineering departments. 97 UFC 901.3; 901.4.2; 902.2.1 14 Issue Contact: Michael Chavez Water Supply: No commercial building can be greater then 300 feet from a fire hydrant'. Fire hydrants are required with a maximum spacing of 600 feet along an approved roadway. Each hydrant must be capable of delivering 1500 gallons of water per minute at a residual pressure of 20psi. 97 UFC 901.2.2.2 15 Issue Contact: Michael Chavez Hazardous Materials: Corrosive, flammable liquids, reactive, or toxic materials (As defined in the Uniform Fire Code) if used, stored or handled on site must have a Hazardous Materials Impact Analysis (HMIA) completed and supplied to the Planning Department and the Fire Department. NOTE: This pertains to the Flammable Storage Unit. FCLUC 3.4.5(C) Department: Police C Issue Contact: Joseph Gerdom Lighting and Landscape: security lighting type and location not on plans. Department: Transportation Planning 7 Issue Contact: Tom Reiff Explore a connection to the existing bike trail to the west. This will provide personnel training or staying at the facility direct access to the downtown area. 8 Issue Contact: Tom Reiff Identify and label all handicap parking stalls. 9 Issue Contact: Tom Reiff Consider providing bikes for personnel training or staying at the facility for mobility around town. 16 Issue Contact: Tom Reiff A sidewalk minimum of 6 feet is necessary where vehicles can over hang into the sidewalk. All other locations a 4.5 foot sidewalk is required. Page 2 STAFF PROJECT REVIEW September 27, 2001 Dana Bardsley USDA Forest Service 240 W. Prospect Ave. Fort Collins, CO 80526 Re; US Forest Service Site Expansion Dear Dana, Staff has reviewed your submittal for US FOREST SERVICE SITE EXPANSION, SITE PLAN ADVISORY REVIEW - #30-01, and we offer the following comments: ISSUES: Department: Engineering 10 Issue Contact: Dave Stringer No issues at this time. If Forest service acquires the 20 foot strip of land between their north property line and 4th Street right of way then they will be required to make improvements to 4th Street or enter into an agreement with the City to pay for their portion of improvements at such time as the street is improved 11 Issue Contact: Dave Stringer The city would like to have a current metes and bounds description mylar copy of this site for our records Department: Natural Resources 17 Issue Contact: Doug Moore Need Proof of Compliance - Provide the City of Fort Collins Natural Resource Department with proof of compliance. Copies of any federal permits that may have been required or any written statements identifying compliance with any federal environmental regulations. 3.4.1(0)(1-2) Department: PFA 12 Issue Contact: Michael Chavez Address Numerals: Address numerals shall be visible from the street fronting the property, and posted with a minimum of 10-inch numerals on a contrasting background. 97 UFC 901.4.4 Page t To: I) � I ) . 5 l 7 Citv of Fort Collins CURRENT PLANNING FACSIMILE Re: l� 5 �'cv.a.SC? sa-.4'c t cc' .� psi c�.. 'S . Date: --A - Z F, . l Fax: Pages: (including this coversheet) -.4'1 ct e, v d c S C%-c �.o\n , �� a.. Q.$ '�o..4\f ICC. Sf k c.. ' %.3 CS (1` o..S c-- Fj V. c( \ lac % \\ V C. From the desk of... Bob Barkeen City Planner City of Fort Collins - Current Planning 281 North College Avenue Fort Collins, CO 80524 Email: bbarkeen@fcgov.com 970.416.2138 Fax: 970.416.2020