HomeMy WebLinkAboutPLANK ANNEXATION PLD/PD (FOSSIL LAKE RANCH PUD, 6TH FILING) - 33-01N - CORRESPONDENCE -Number: 55 Created: 9/29/2006
[9/29/06] Please insert new WQ outlet structure detail. There has been a couple minor
revisions. I will email it to you.
If you have any questions regarding these issues or any other issues related to this
project, please feel free to call me at (970) 221-6750.
Sincerely,
Shelby Sommer
Associate City Planner
CC: Stan Everitt (Applicant)
3
Department: Engineering Issue Contact: Randy Maizland
Topic: Stormwater
Number: 56 Created: 10/2/2006
[10/2/06] Refer to sheet G1, Grading Plan. The area behind lots 20-27 on the southerly
boundary is shown as being graded to slope and drain into the adjacent lots to the south
creating a cross lot drainage condition. Please revise the grading in this area to slope
towards an acceptable location such as the street or a detention pond or provide area
inlets to collect this drainage to be conveyed to a storm drain system.
Number: 57 Created: 10/2/2006
[10/2/06] Where any storm drain pipe cover is less than 4 feet, please provide a
dimension on the profile from top of pipe to top of soil subgrade at the shallowest point.
Pipe cover shall not include any base or pavement section. Minimum pipe cover is 3 feet
where located below street pavement.
Department: Natural Resources Issue Contact: Doug Moore
Topic: General
Number: 58 Created: 10/2/2006
[10/2/06] No issues.
Department: Stormwater-Water-Wastewater Issue Contact: Wes Lamarque
Topic: Stormwater
Number: 33 Created: 3/5/2006
[9/29/06] Repeat Comment.
[8/9/06] Reminder Comment. No landscape plan submitted to Stormwater.
[3/5/06] This comment is for the landscape plan that was submitted February 27th,
2006. Please provide 10 feet of separation between all trees and storm sewers.
Number: 48 Created: 8/9/2006
[9129/06] No drainage report received.
[8/9/06] The off -site outfall swale needs to have a longitudinal slope of 2% or a drainage
pan is required. The swale was designed with a 2% slope, but needs to be field verified.
Also, please be advised that the off -site swale could have water running in it the majority
of the time which may be undesirable.
Number: 49 Created: 8/9/2006
[9/29/06] Repeat Comment
[8/9/06] Please provide a riprap detail with the 6-inch topsoil cover.
Number: 51 Created: 9/29/2006
[9/29106) The 100-year WSEL for Pond 2 needs to be lower than the flowline elevation
at the inlets along Muskrat Creek Drive.
Number: 52 Created: 9/29/2006
[9/29/06] Can lots 24-27 be Type "A"? Minimizing the drainage to DP 9 is important due
to lack of good outfall. Also, where does drainage from DP 9 go?
Number: 53 Created: 9/29/2006
[9/29/06] Storm sewer on southeast edge of property needs to be more centrally located
within the track for easier maintenance. See redlines.
Number: 54 Created: 9/29/2006
[9/29/06] Please add a detention pond summary table to sheets G2 and DR1. This
should include pond invert, WQ elev, 10-year elev, 100-yr WSEL, and release rates.
1
Comm_,lity Planning and Environmt._.cal Services
Current Planning
City of Fort Collins
October 3, 2006
Matt Lafferty
Larimer County Planning Division
P.O. Box 1190
Fort Collins, CO 80522-1190
Re: Plank PLD/PD Final Plat
Dear Matt,
Thank you for the opportunity to review the Plank PLD/PD Final Plat request. The
request has been forwarded to the City of Fort Collins for review and comment pursuant
to the intergovernmental agreement with Larimer County and the City of Fort Collins.
Upon review of the application, the City offers the following comments:
Department: Current Planning Issue Contact: Pete Wray
Topic: General
Number: 16 Created: 9/26/2005
[10/3/06]
[8/1/06] No problems.
(9/26/05] The Plank PLD/PD is within the Fossil Creek Reservoir Area Plan and
designated TDU Receiving Area. The City has agreed to defer annexation until such
time as the TDU transactions have been finalized in the County along with Final Plan
review. The PD meets the minimum density of 3 Du's per acre.
Number: 50
[9/19/061 No comment.
Created: 9/19/2006
Department: Engineering Issue Contact: Sheri Wamhoff
Topic: General
Number: 6 Created: 9/23/2005
[10/2/06]
[7/25/06] Same comment
[3/13/06] [1/16/06] [9/23/05] If the construction timing of this project and the
Roundabout project correspond this project could save some money on overlay of
Kechter. This project will need to overlay Kecther where the new roadway and utility
connections tie into Kechter. If this is done at the same time that the City is doing the
roundabout work, coordination could be done to add the overlay work the development
will need to the City project at a cost that would probably be better than having to do the
work separately.
Number: 15 Created: 9/23/2005
[9/29/06]
[7/25/06] Same comment
[3/13/06] [1/16/06] [9/23/05] A repay for the Kechter Road improvements is due from
this property at the time of development.