If you have any questions regarding these issues or any other issues related to this project,
please feel free to call me at (970) 221-6341.
Yours �Truly,
Steve Olt
City Planner
cc: Susan Joy
Current Planning file #35-01C/D
Page 5
Department: Stormwater-Water-Wastewater Issue Contact: Roger Buffington
Topic: Water/Wastewater
Number: 70 Created: 1 /6/2009
[1/6/09] Curb stop on the 1" water service must be minimum of F inside easement, which is
in direct conflict with the UG electric. Meter pit must be within T of curb stop.
Number: 71 Created: 1 /6/2009
[ 1/6/09] Move the fire line and the 1" water service so not in vicinity of the end of the storm
drain.
Number: 72 Created: 1 /6/2009
[1/6/09] Add 6" gate valve where the fire hydrant connects to the N/S water line.
Number: 73 Created: 1 /6/2009
[1/6/09] Show the fire line and I" water service in the storm profile. Any conflict?
Lowering needed?
Number: 74 Created: 1 /6/2009
[1/6/09] Show the north FES in the storm profile.
Number: 75 Created: 1 /6/2009
[1/6/09] Add the Locator Station detail (Std detail 25).
Department: Zoning Issue Contact: Gary Lopez
Topic: Zoning
Number: 69 Created: 12/ 19/2008
[12/19/08] No issues.
This just came in from Tom McCormick of Platte River Power Authority:
Mike Dahl, who you will be meeting with tomorrow on another issue, is waiting on
our general manager to get back from a business trip this week. Mike most likely
will be the one to sign the easement declaration assuming our attorney approves of
the wording. The other issues have been addressed to our satisfaction with regards
to tress, street lights, etc. and do not represent any problems based on the drawings
re -submitted.
You and Mike can discuss this tomorrow on timing and whatever else is needed. Let
me know if you have any questions.
Tom McCormick
Platte River Power Authority
Phone - 970-229-5311
mccormickt@prpa.org
Page 4
Number: 85 Created: 1 /8/2009
[1/8/09] From Technical Services:
1. Boundary and legal close.
2. Line over text (scanning) on site, lighting and utility plans.
3. Could text in hatching be blocked out?
Topic: Site Plan
Number: 81 Created: 1 /8/2009
[1/8/09] Please show and dimension all of the existing and proposed easements.
Topic: Utility Plans
Number: 65 Created: 12/1/2008
[1/8/09] Please place the PRPA signature block on the cover sheet and any other sheet they
need to sign.
[12/1/08] Improvements are proposed within the PRPA No Build Easement. Will this be an
issue? Please place a PRPA signature block on the plan sheets for their signature. Thank
you.
Number: 76 Created: 1/8/2 009
[1/8/09] Scanning issues, please see tech services if you have any questions.
Number: 78 Created: 1 /8/2009
[ 1/8/09] Sheet 10 - Please add the words "on -site only" to all of the on -site only details along
the bottom of the sheet.
Number: 79 Created: l /8/2009
[1/8/09] Sheet 4 -Please dimension all of the existing and proposed easements.
Number: 82 Created: l /8/2009
[1/8/09] Sheet 5 - Lots of missing information (M) and scanning issues.
Department: Stormwater-Water-Wastewater Issue Contact: Wes Lamarque
Topic: Stormwater
Number: 60 Created: 11 / 19/2008
[ 1/9%09] Please provide a manufacturer's design and/or recommendation for the scour stop.
The manufacturer offers this service for free and we want to make sure this is built correctly
during the trial period for this product.
[11/19/081 Please provide a design & detail for the scourstop pad per manufacturer's
recommendation. Also, please use the scourstop all the way to the drainage pan and remove
the rip -rap at the bottom. This area will not withstand the velocity proposed and the 6-inches
of topsoil over the rip -rap will likely wash away.
Page 3
Department: Engineering Issue Contact: Sheri Langenberger
Topic: General
Number: 9 Created: 6/5/2007
[1/8/09] [6/5/07] This development is responsible for a repay for a Special Improvement
District (SID) assessment. This assessment will be due at the time of building permit. Please
contact Matt Baker of Engineering at 224-6108 for information on the SID.
Department: Engineering Issue Contact: Susan Joy
Topic: General
Number: 77 Created: 1 /8/2009
[1/8/09] Please add a note with the PRPA easement restrictions to all of the plan sets.
Number: 83 Created: 1 /8/2009
[1/8/09] I e-mailed the development agreement information sheet to Vignette Studios.
Please have someone fill out and return by fax or PDF to me so we can start the DA. Thank
you.
Number: 84 Created: 1 /8/2009
[1/8/09] I would like an informal round of review before the mylars are submitted to make
sure the remaining items have been addressed sufficiently. You can e-mail me PDF's of the
documents at sloy(CMcgov.com.
Topic: Landscape Plan
Number: 80 Created: 1 /8/2009
[1/8/09] Please show and dimension all of the existing and proposed easements.
Department: Engineering Issue Contact: Sheri Langenberger
Topic: Plat
Number: 34 Created: 6/7/2007
[1/8/09] Need to dimension the offsite easements too.
[6/7/07] Need to show the adjacent off -site easements that need to be dedicated by separate
document for this project.
Department: Engineering Issue Contact: Susan Joy
Topic: Plat
Number: 67 Created: 12/ 1 /2008
[1/8/09] No note has been added, please add.
[ 12/1/08] Should there not be a note or explanation of what the PRPA easements are for -
like, for example, what is the height restriction or what does no -build really mean?
Page 2
STAFF PROJECT REVIEW
City of Fort Collins
Don Tiller Date: 1/15/2009
2121 Midpoint Drive, Suite 302
Fort Collins, CO 80525
Staff has reviewed your submittal for CENTERPOINT PLAZA, REPLAT - FINAL
PLANS (REVISIONS), and we offer the following comments:
ISSUES:
Department: Current Planning Issue Contact: Steve Olt
Topic: General
Number: 86 Created: 1/15/2009
[1/15/09] No further comments from Current Planning.
Number: 87 Created: 1/15/2009
[1/15/09] Comments from Platte River Power Authority have not yet been received. A
message has been sent to Tom McCormick inquiring as to when we can expect comments.
Number: 88 Created: 1/15/2009
[1/15/09] Technical Services offered the following comments:
a. The outside boundary and legal description do close.
b. There are line over text (scanning) issues on the Site, Landscape, and Utility Plans.
C. Could text in hatching be blocked out?
Number: 89 Created: 1/15/2009
[1/15/09] The following department comments were offered at Staff Review on January 7,
2009:
Stormwater/Wes
a. Some rip -rap can be eliminated.
b. Stormwater has no other comments.
Engineering/Susan
a. Platte River Power Authority signature blocks must be added to the appropriate plans.
b. The filing fees for Larimer County must be provided to Engineering.
C. The additional review by Engineering can be dealt with by sending PDF's to Susan.
Page 1