95 . Issue Contact: Doug Moore
Relocate Sidewalk Connection -
Remove Sidewalk connection along Countryside Road to natural area trail. River
Bend Ponds Natural Area is a "Trail Only" natural area and limit entrance points to
the area is a key management practice for the natural area.
Sidewalk connection could be relocated to connect to the westbound Countryside
Road and then possibly down to the controlled trail head entrance. Please contact
Doug Moore at 224-6143 to setup a meeting with Natural Resources,
Transportation, Engineering, and Current Planning to discuss these issues.
96 Issue Contact: Doug Moore
Stormwater released on to Natural Area -
No more than two-year historic flow rates will be allowed without easements. All
water released on to Natural Area property must comply with all applicable local,
state and federal water quality standards, including, but not limited to, those
regulating erosion and sedimentation, storm drainage and runoff control, solid
wastes, and hazardous substances. Projects shall be designed so that precipitation
runoff flowing from site is treated in accordance with the criteria set forth in the
Storm Drainage Criteria and Construction Standards. Treatment measures may
include, but shall not be limited to:
Minimization of impervious surfaces
Runoff spreaders
Infiltration devices
Extended detention
Constructed wetlands
Sand filters
Water quality inlets
Section 3.4.3 of the Land Use Code.
97 Issue Contact: Doug Moore
Utility Easement in Natural Area -
Natural Resources has a new easement policy that they are required to follow if any
easement might be needed on Natural Area property the process should be started
immediately. The Natural Resource Advisory Board has full discretion over granting
easement and this process may be time consuming.
Department: PFA
74
Issue Contact: Michael Chavez
Required Access: A fire lane is required. The fire lane shall be visible by painting
and signage, and maintained unobstructed. Surface criteria may be obtained from
Page 13
Project:
Date:
i1 O
Planner:
-9�e£ Ck.T Traffic Operations: IN'�G +3MI�
Engineer:
Items Requested
Redlined Items Being Returned
T
a
?
v
Y
.� 0
0
Other Items Required
a)
U)
J
a
v
y
0
Other Items being
Returned
En ineerin ' -
,r
X
6
Stormwater
n
x
Water/Wastewater
Traffic Operations
�G
_
_
Transportation Planning
)c
Transfort
Natural Resources
_
Park Planning
TOTALS -{rl� 40� Ap,
G�
Other:
Note: All redlined items should be returned with the resubmittal/revisions.
L,
I
REVISION ROUTING 51"T
1 h19 L1nl
ITEM:3�I -� l fZt,tler�P�nr
-- (eta T . LUGS
DATE RECEIVED:
H
�
`n
C
¢
�
�
�
u
z °
Z w
a
z o°
Z U
`n
Z °
C.F.'
F
Z
C E�
h Z
� o
u1 ry
<�
FILE: PROJECT PLANNER
ENGINEERING PAVEMENT
ZONING
BUILDING INSPECTION
LIGHT & POWER,I
TECHNICAL SERVICES
FORESTRY
WATER & WASTEWATER/FCLD
PFA
POLICE -
ADVANCE PLANNING
STREETS
R.O.W. PLANNING
WATER CONSERVATION
POST OFFICE
US WEST
PUBLIC SERVICE
SCHOOLS: POUDRE / THOMPSON
AT & T DIGITAL CABLE
CDOT
DITCH COMPANY
RAILROAD: UP or BNSF
REA/DOE/PRPA
LGD uOa t�isY%
I
`
tZ-
I
2
40
If you have any questions regarding these issues or any other issues related to this
project, please feel free to call me at (970) 221-6341.
Yours Truly,
hljz�
STEVE OLT
City Planner
Page 17
so 40
Straw bales do not work on concrete pans, please utilize the stormwater pond as a
sediment trap with a gravel filter.
Please indicate seeding/mulching/sodding, whatever is to be completed on the
detention pond in the erosion control plan.
Calculations, surety?
87
Issue Contact: Basil Hamdan
Please refer to the redlined plans and report for additional review comments.
Department: Transportation Planning
78
Issue Contact: Kathleen Reavis
Add sidewalks on internal drive. Prefer 6' attached sidewalk, but 5' could work if
there is not rollover curb.
79
Issue Contact: Kathleen Reavis
Redirect the sidewalk connections for units #2 and #3 to the internal drive, not out to
Countryside Drive. This is better for residents and will help minimize illegal parking
on Countryside.
Department: Zoning
2
Issue Contact: Gary Lopez
Indicate building footprint dimensions and relative distance to nearest property line.
Department: Engineering Pavement
Rick Richter indicated that they will need pavement design if Countryside Drive is
new.
This development request is subject to the 90-day revision re -submittal requirement
as set forth in Section 2.2.11(A) of the Land Use Code. The number of each
document to re -submit is on the attached Revision Routing Sheet. Be sure and
return all of your redlined plans when you re -submit.
Page 16
40
M
81
Issue Contact: Basil Hamdan
Water Quality:
Please eliminate the pan at the bottom of the Water Quality pond since it will not
allow the pond to function as a true Water Quality pond.
E-W
Issue Contact: Basil Hamdan
Outfall:
Please show where the drainage coming out of the pond will be routed to, how will it
get into the Poudre. Since the outfall needs to go through Natural resources
property, the Natural Resources Department will need to sign off on the plans.
W
Issue Contact: Basil Hamdan
Sidewalk Culvert:
Please use the concrete sidewalk detail D12 for the proposed inlet on Countryside
Road.
Issue Contact: Basil Hamdan
Utility Plans:
Please call out all drainage facilities, existing and proposed on the overall utility plan.
Call out size, type and class of all storm sewers.
Please make sure that all proposed trees are at 5 feet of storm sewers.
Please show the 500 year floodplain limits on the drainage plan.
85
Issue Contact: Basil Hamdan
Grading:
Please tie in elevations at the property lines. Please label existing contour
elevations. Call out all pipe invert elevations on the grading plan.
Even though the site is outside of the 100-year floodplain, it is suggested that
building Finish Floor elevations be raised above the 500- year base flood elevation
to prevent the potential for flooding.
86 Issue Contact: Basil Hamdan
Erosion Control:
Erosion control notes need to be on the erosion control plan.
Why install silt fence on the top edge of a detention basin?
Page 15
40
40
the City Engineering department. NOTE:. If the turnaround is meant to be a "Fire
Lane" it shall be platted as an "Emergency Access Easement'.
75
Issue Contact: Michael Chavez
Address Numerals: Address numerals shall be visible from the street fronting the
property, and posted with a minimum of 6-inch numerals on a contrasting
background.. 97 UFC 901.4.4 NOTE: Lots 4-8 do not front a street and can not be
addressed.
r1:1
Issue Contact: Michael Chavez
Residential Water Supply: No residential building can be greater then 400 feet from
a fire hydrant. Fire hydrants are required with a maximum spacing of 800 feet along
an approved roadway. Each hydrant must be capable of delivering 1000 gallons of
water per minute at a residual pressure of 20 psi. 97 UFC 901.2.2.2
77
Issue Contact: Michael Chavez
Sprinklers Required: The buildings on Lots 3-8 shall be fire sprinklered. NOTE:
When any portion of a facility or any portion of an exterior wall of the first story of the
building is located more then 150 feet from fire apparatus access as measured by an
approved route around the exterior of the building or facility it shall be fire
sprinklered. 97 UFC 902.2.1
Department: Police
73
Issue Contact: Joseph Gerdom
Landscape/Lighting: The two ponderosa pines in the parking lot island should be
removed. First, they will block visual surveillance between the units and parking
area. Second, the height of these materials will block lighting portions of the drive
area and garage areas.
Department: Stormwater Utility
:1
Issue Contact: Basil Hamdan
Detention:
Water quantity detention might be required on this site based on Natural Resources
requirements. Natural Resources have stated that they will only allow detained —
runoff to enter their property to the south.
Page.l4
so 40
90 Issue Contact: Susan Joy
Technical Services: "Tie" from Section Corner in conflict w/adjoining subdivision
plat.
91 Issue Contact: Susan Joy
Technical Services: How does the RAN easement tie into a dedicated roadway?
92
Issue Contact: Susan Joy
Technical Services: What street will this be addressed off of?
Department: Light & Power
1
Issue Contact: Doug Martine
It will be necessary for Light& Power to use above grade pad type transformers to
be placed between the curb & sidewalk.
Department: Natural Resources
Issue Contact: Doug Moore
Plant material with in Natural Area Buffer -
All plant material within the Natural Area Buffer must be native to the Fort Collins
area. 3.4.1(E)
93 Issue Contact: Doug Moore
Performance Standards are not being meet -
The Natural Areas Team feels that the current Landscape Plan does not meet the
intent of the Performance Standards and that more vegetation is needs to be added
to buffer between the activity proposed for the development and the natural habitat.
Section 3.4.1(E) of the Land Use Code.
94 Issue Contact: Doug Moore
Install a fence along south side of property -
Natural Areas would like to see a fence installed along the south property line
between the development and the River Bend Ponds Natural Area. River Bend
Ponds Natural Area is a "Trail Only" natural area and limit entrance points to the
area is a key management practice for the natural area.
Page 12
64
Issue Contact: Susan Joy
Site Plan: Contact the PFA regarding Note 11 and their addressing requirements.
65
Issue Contact: Susan Joy
Site Plan: Note 13
is not correct. The utility and landscape plans show many
improvements outside
the property boundary.
66
Issue Contact: Susan Joy
Landscape Plan:
Provide a Legend.
67
Issue Contact: Susan Joy
Landscape Plan:
Show ROW, easements, property lines, existing and proposed
utilities, etc.
68
Issue Contact: Susan Joy
Landscape Plan:
Landscaping shown outside the property boundaries. You will
need to work with Doug Moore/Natural Resources for any work done in this area._
69
Issue Contact: Susan Joy
Landscape Plan:
Correct the labeling for the natural area buffers. See comments
from the Site Plan regarding the proposed change to the buffer zone.
70
Issue Contact: Susan Joy
Landscape Plan:
Incorporate comments from the site and utility plans.
71
Issue Contact: Susan Joy
Landscape Plan:
Dimension given in the NE corner for?
72
Issue Contact: Susan Joy
Landscape Plan:
See redlines for other labeling, corrections.
89
Issue Contact: Susan Joy
Technical Services: Boundary and Legal Close
Page 11
56 Issue Contact: Susan Joy
Site Plan: Provide the R for the inside and outside dimensions of the culdesac.
Code requires 20' inside, 40' outside.
57
Issue Contact: Susan Joy
Site Plan: Label the Private Drive and show Emergency Fire Access Easement.
58 Issue Contact: Susan Joy
Site Plan: Label the existing parking lot.
59 Issue Contact: Susan Joy
Site Plan: Redesign the parking lot entrance from Countryside Drive using detail 7-
29A and all other applicable standards. Use C&G one side, none on the other. See
redlines and call me at 221-6605 if you have any questions. Extend the sidewalks
as necessary.
60 Issue Contact: Susan Joy
Site Plan: Bring the sidewalk from the front of the buildings out to the eop.
61
Issue Contact: Susan Joy
Site Plan: See the Land Use Code 3.6.2(L)2 and contact Ron Gonzales, 416-2864,
with the PFA. It appears that buildings 6,7,8 are out of fire access (max 150) from a
public street. Is there a separate "man door" at the rear of the buildings? Fire
access cannot be taken through the garage. If there IS a separate entrance and
PFA can serve off the private drive, then the private drive must be dedicated as an
emergency access easement. Show on Plat.
62
Issue Contact: Susan Joy
Site Plan: What are the rounded areas behind the units? Is this all concrete?
Where is the. pedestrian connection behind the garages? There are no sidewalks on
site in the interior.
63
Issue Contact: Susan Joy
Site Plan: Contact Doug Moore with Natural Resources, 221-6600, regarding the
20' reduction in the natural area buffer zone. He will advise you on the mitigation =
you will be responsible for.
Page 10
• 40
47
Issue Contact: Susan Joy
Drainage/Erosion Control: See Grading Sheet comments regarding contours.
48 Issue Contact: Susan Joy
Drainage/Erosion Control: Reference detail/sheet number for details (typical, all
sheets).
49
Issue Contact: Susan Joy
Detail Sheet: Update all the details to current LCUASS. All the details shown are
the old standard.
50
Issue Contact: Susan Joy
Detail Sheet: Add street cut note to "Replacing Asphalt Paving detail". Update the
detail to current LCUASS.
51
Issue Contact: Susan Joy
Site Plan: Correct the overlapping and duplicated words. See redlines.
52
Issue Contact: Susan Joy
Site Plan: Add a Legend, label all ROW, easements, setbacks, etc. See redlines.
53
Issue Contact: Susan Joy
Site Plan: Countryside improvements should be to 7-81F w/out the sidewalk one
side. -
54
Issue Contact: Susan Joy
Site Plan: Parking depth must be 23'or 21' with overhang.
55
Issue Contact: Susan Joy
Site Plan: Handicapped Parking is 12' wide minimum with ramp access to
sidewalks. Please see the Land Use Code, pg 34, Article 3, section 5, paragraph b
for further requirements.
Page 9
38 • Issue Contact: Susan Joy
Grading/Utility Sheet: Show existing features for a minimum of 150' beyond the
project limits. This sheet should match the site and landscape plan. Show and label
the existing parking lot.
39
Issue Contact: Susan Joy
Grading/Utility Sheet: Provide the statement shown in Appendix E4, Il, E.
40
Issue Contact: Susan Joy
Grading/Utility Sheet/Site: Show general location of signs.
41
Issue Contact: Susan Joy
Grading/Utility Sheet: Something is wrong with the property lines in the NE area.
Overlap shown. Which line is correct? How does this correlate with the plat?
42 Issue Contact: Susan Joy
Grading/Utility Sheet: Provide easements for all the work that is occurring off -site
(culvert, utilities in Natural Areas, construction on neighboring properties, etc.).
Contact Doug Moore with Natural Areas ASAP - any request for easements.from this
department takes quite a long time.
43 Issue Contact: Susan Joy
Grading/Utility Sheet: Give enough information on the sidewalk extension so that
they can lay this out in the field. See redlines.
44 Issue Contact: Susan Joy -
Drainage/Erosion Control: Show revegetation methods and specific notes regarding
the natural area.
45 Issue Contact: Susan Joy
Drainage/Erosion Control: Update the Erosion Control Notes per Appendix E2.
These notes can stay on page 2 of the cover sheet with the rest of the Construction
Notes if you wish. Either sheet is fine.
46 Issue Contact: Susan Joy
Drainage/Erosion Control: Provide drainage arrows and show positive drainage to
streets or to an approved drainage facility.
Page 8
N as
r
29 Issue Contact: Susan Joy
Grading/Utility Sheet: Private Drive entrance does not match the Site and
Landscape Plan. Do not use the high volume drive, design to detail 7-29A instead.
Provide all spot elevations as shown in the detail. Dimension the drive width.
30 Issue Contact: Susan Joy
Grading/Utility Sheet: Dimension sidewalk widths.
31 Issue Contact: Susan Joy
Grading/Utility Sheet: Design the sidewalk culvert in accordance with detail 7-31.
32
Issue Contact: Susan Joy
Grading/Utility Sheet: - Expand your Legend to include Property lines, Easements,
Tracts, Building Envelopes, Buffer Zones, etc, all sheets. Show on plans and label,
all sheets.
33
Issue Contact: Susan Joy
Grading/Utility Sheet: Is there a fire hydrant in the culdesac area? Should there be
one? Please consult with the PFA.
34
Issue Contact: Susan Joy
Grading/Utility Sheet: Show striping in parking area and dimension. See comments
from Site Plan.
35
Issue Contact: Susan Joy
Grading/Utility Sheet: Show Tracts and label, all sheets.
36 Issue Contact: Susan Joy
Grading/Utility Sheet: Existing and proposed contours must be provided at 2' min
intervals and labeled. Please darken up what you have so that one can read it
easier.
37 Issue Contact: Susan Joy
Grading/Utility Sheet: Contours must extend a minimum of 50' offsite and tie into
existing contours. I'll reserve further comments on grading/elevations when I can
see them better on the next submittal.
Page 7
21 Issue Contact: Susan Joy
Cover Sheet: Provide the statement: "I hereby affirm...". See E4, I, J.
22
Issue Contact: Susan Joy
Cover Sheet: Provide the typical street section (Detail 7-8F w/out the sidewalk on
one side) being proposed. Sections include appropriate horizontal and vertical
dimensions and cross slopes.
23
Issue Contact: Susan Joy
Cover Sheet: Provide the names, addresses, and phone numbers of the owner(s),
developer(s).
24
Issue Contact: Susan Joy
Cover Sheet: Add the Indemnification Statement: "These plans have been
reviewed by the Local Entity for...". See LCUASS 3.3.1.F.
25
Issue Contact: Susan Joy
Cover Sheet: Provide a 4"x6" area on each sheet for the local entity's stamp of
approval.
26 Issue Contact: Susan Joy
Cover Sheet: Provide a signature block for the County Engineer.
27 Issue Contact: Susan Joy
Grading/Utility Sheet: Label the "Private Drive". -
28 Issue Contact: Susan Joy
Grading/Utility Sheet: Where ever there is a street cut, add the following note:
Limits of street cut are approximate. Final limits are to be determined in the field by
the City Engineering Inspector. All repairs to be in accordance with the City street
repair standards.
Add this same note to the appropriate current detail on the detail sheet.
Page 6
N do
10 Issue Contact: Susan Joy
Plat: Add a Note that "No Parking allowed on Countryside Drive
11 Issue Contact: Susan Joy
Plat: Dedicate and show all utility easements as required. Obtain and provide all
off -site utility and construction easements.
12
Plat: Label Street.
Issue Contact: Susan Joy
13 Issue Contact: Susan Joy
Cover Sheet: Correct preamble title to read "Utility Plans for...."
14 Issue Contact: Susan Joy
Cover Sheet: Provide the legal description below the project name.
15 Issue Contact: Susan Joy
Cover Sheet: Minimum size for the Vicinity Map is 10" x 10" and to a scale of
1 "=1000-1500'. See LCUASS, 3.3.1.C.1 &2. Correct the Vicinity Map, see redlines.
W
Cover Sheet: Add a Title Block.
17
Cover Sheet: Add Print Date, each sheet.
Issue Contact: Susan Joy
Issue Contact: Susan Joy
18 Issue Contact: Susan Joy
Cover Sheet: Update the signature block, each sheet. See attached.
19 Issue Contact: Susan Joy
Cover Sheet, pg 2: Update the General Notes. See Appendix E1. Complete lines
19 and 40.
20
Issue Contact: Susan Joy
Cover Sheet, pg 2: Add the Construction Notes, see Appendix E2
Page 5
M
2. A better design is needed for the water quality pond. Water quantity is
needed, also.
Transportation Planning
1. There are concerns about the internal pedestrian circulation in this project.
The interior of the site is driveway and garage doors. Where is any good
internal pedestrian access, or emergency access, to the dwelling units?
2. No parking will be allowed on Countryside Drive.
Department: Engineering
3
Issue Contact: Susan Joy
Complete and submit the Checklist in Appendix E-4.
4
Issue Contact: Susan Joy
Coordinate the various sheets so that they present the same information.
5 Issue Contact: Susan Joy
Plat: Update the language in several areas. See attached.
M
Plat: Add current date.
VA
Issue Contact: Susan Joy
Issue Contact: Susan Joy -
Plat: Private Drive must be dedicated on the Plat as an emergency fire access
easement.
Issue Contact: Susan.Joy
Plat: See attached for the following notice that shall be placed on the plat set apart
from the other notes in a box labeled as "NOTICE" when private drives or streets are
utilized on the property.
9
Issue Contact: Susan Joy
Plat: Need to identify who is to own and maintain all of the tracts.
Page 4
104 Issue Contact: Steve Olt
Current Planning Department's comments are on red -lined plans that are being
forwarded to the applicant.
105
Issue Contact: Steve Olt
The following comments were expressed at the staff review meeting on October 17,
2001:
Engineering
There is a property line conflict with the single family development to the east.
2. Please contact Ron Gonzales to discuss the addressing for the 8 dwelling
units in this project. Ron can be reached at 221-6570.
3. No parking will be permitted on Countryside Drive. This must be indicated on
the subdivision plat.
4. There are no walkways from the handicapped parking space to handicapped
accessible doors to the dwelling units. Basically, handicapped accessible
doors do not exist.
5. The entrance to the natural areas parking lot should be redesigned with this
project.
Natural Resources
1. This development may have to eliminate 2 dwelling units to deal with the
possible detention concerns.
2. Stormwater to be released into the natural area needs to be adequately
filtered. It is very possible that the Natural Resources Advisory Board may not
grant an easement on the City -owned natural area, if one is required.
3. The required 100' buffer between development and the ponds in the natural
area should not be reduced.
4. The landscape Plan is not showing the use of native plant materials.
Stormwater Utility
1. The drainage report does not discuss where stormwater goes when it leaves T
this site. The drainage plan does not provide for detention, just water quality.
This must be approved by the Natural Resources Department.
Page 3
4. The Lighting and Landscape Plans show a proposed streetlight on the east
side of Countryside Road (Drive). This location is acceptable to L&P, but the
street trees need to be a minimum of 40' from the light. .
Please contact Doug, at 224-6152, if you have questions about his comments.
101
Issue Contact: Steve Olt
Rick Lee of the Building Inspection Department indicated that he is attaching a
copy of the various codes that the Building Department will enforce. From the brief
information provided it is apparent that this project is going to be a single family (R-
3) attached project with zero lot line construction. This type of construction is going
to require two 1-hour walls back to back. This construction should extend from the
foundation wall to the roof deck above and the restricted openings in the roof
requirements of 709.4.1.
102 Issue Contact: Steve Olt
Dennis Greenwalt of AT&T Broadband (cable TV) indicated that the Riverbend
PDP is too far from their facilities for service at this time and does not meet the
franchise requirements. With this project being in the city limits of Fort Collins and no
one else holding a franchise for Fort Collins, there should not be any cable service
available.
103 Issue Contact: Steve Olt
Len Hilderbrand of Excel Energy (Public Service) offered the following comments:
1. The building envelope for Lots 1 & 2 encroaches into an easement on the
west end of the lots.
2. Meters must be clustered together on the west wall of Lot 3 to serve Lots 3 -
8.
3. The water curb stop must be to the back of the easement. If telephone, cable,
and electric equipment are located within the 9' easement, then the easement
must be expanded to 11' in width.
4. The gas line must be located in the street right-of-way with a minimum 10'
clearance from water and sewer.
5. Any relocation of existing gas lines will be at the developers expense.
Page 2
STAFF PROJECT REVIEW
City of Fort Collins
HOORAZ, LLC _
C/O VIGNETTE STUDIOS
144 N. MASON STREET, SUITE 2
FORT COLLINS, CO 80524
Date: 10/24/01
Staff has reviewed your submittal for RIVERBEND PDP, #39-01, and we offer the
following comments:
ISSUES:
Department: Current Planning
Issue Contact: Steve Olt
Eric Bracke of the Traffic Operations Department offered the following comments:
No Transportation Impact Study is required.
2. The parking on Countryside Drive will be eliminated.
Issue Contact: Steve -Olt
Gary Lopez of the Zoning Department indicated that the building footprint
dimensions and relative distances to property lines must be shown on the Site Plan.
100
Issue Contact: Steve Olt
Doug Martine of Light & Power offered the following comments:
1. Off -site easements along the north side of Countryside Road (Drive) will be
necessary.
2. Electric meters will need to be "gated" at the west end of Buildings 3 - 8, and
on the south or west end of Buildings 1 & 2.
3. Light & Power will need to cross Countryside Road (Drive) and the developer
will need to provide a street cut permit, pay the permit and impact fees, and
repair asphalt as necessary.
Page 1