HomeMy WebLinkAboutVIALE COLLEGIO - FDP - 1-02A - CORRESPONDENCE -108 The fire hydrant detail shown does not meet the City Standard nor the PFA standard. If this is for "blow off' purposes only, then another appurtenance shall be utilized to prevent any confusion as to the purpose of the hydrant. See Utility Plans C6 for hydrant detail Department: Stormwater Utility Topic: General 93 No More Comments. Department: Transportation Planning Topic: General 103 No Comments (11-3-02) Issue Contact: Wes Lamarque Issue Contact: Tom Reiff Department: Water Wastewater Issue Contact: Roger Buffington Topic: Utility Plans 104 Provide 8" x 6" reducer where fire hydrant connects to 8" water main. Revise utility plan and detail drawing.. Department: Water Wastewater Issue Contact: Jeff Hill Topic: Utility Plans 102 Include the 3/4 and 1-inch interior meter setter detail on the detail sheet. Be sure and return all of your redlined plans when you re -submit. If you have any questions regarding these issues or any other issues related to this project, please feel free to call me at (970) 221-6750. Yours Truly, BOB BARKEEN City Planner Page 3 10/29/02: Repeat. Correct the street cut note - see redlines. 105 This submittal was received between the monthly meetings scheduled with CDOT. Our next meeting is the 21st of November. The utility drawings will be submitted for CDOTs review at that time and the resulting redlines and comments will be returned on the 22nd. All remaining comments can be addressed with the mylar submittal. A CDOT permit, excavation permit, and DA will be required. Department: Light & Power Topic: General 1 NO COMMENTS Issue Contact: Bruce Vogel Department: Natural Resources Issue Contact: Doug Moore Topic: Construction Drawings 81 The Tree Protection Specifications can be found under 3.2.1(G) of the Land Use Code. These Specifications will need to be communicated on Construction Drawings and Landscape Plans as notes, drawings, detail and possibly elevations to clearly communicate how the existing trees will be preserved. Department: PFA Issue Contact: Ron Gonzales Topic: General 24 WATER SUPPLY A fire hydrant is required to be within 300 ft. of the building, and shall deliver 1500 gpm @ 20 psi, 25 ADDRESS The building address is required to be visible from the street on which the property fronts, minimum 8 inch numerals to be posted on a contrasting background 26 FIRE SPRINKLERS This facility is required to be fire sprinklered (due to # of units). 27 VENTILATION SYSTEM A ventilation and smoke removal system shall be installed for the underground parking lot in accordance with 97UBC. Department: PFA Issue Contact: Michael Chavez Topic: Utility Plans 89 A 6-inch fire main is required. Department: PFA Issue Contact: Ron Gonzales Topic: Utility Plans/fire 107 The 6" fire sprinkler line shall not be installed under the parking lot or under the building. See Utility Plans sheet C5. If this sprinkler supply goes through a structure, it shall be properly protected from freezing and any other damage in accordance with the appropriate NFPA standard for the installation of underground fire service mains. Page 2 .11. STAFF PROJECT REVIEW City of Fort Collins I HILLHOUSE ARCHITECTS, INC. Date: 11/15/2002 JIM HILLHOUSE 8897 GANDER VALLEY LN. WINDSOR, CO 80550 Staff has reviewed your submittal for VIALE COLEGIO PDP - TYPE I (LUC) & FINAL COMPLIANCE, and we offer the following comments: ISSUES: Department: Advance Planning Issue Contact: Pete Wray Topic: General 94 Coordinate removal of existing trees along College Avenue with City Forester. Department: Current Planning Issue Contact: Bob Barkeen Topic: Site Plan 100 The cover sheet of the site plan was not included with the latest submittal. This will need to be included. The aerial photo may be omitted from this page. A signature block for the Current Planning Director and property owner will need to be included on this page. The site data, title, and narrative are included as well. The final mylar set will need to include the cover page, site plan. landscape plan and building elevations. 106 The bike rack shown in front of the building has been removed from this latest submittal. This will need to be included on the site plan. Department: Engineering Issue Contact: Susan Joy Topic: Utility Plans 64 5/21/02: Show how much of the existing driveway cut is being removed and replaced and add the Street Cut Note: Limits of street cut are approximate. Final limits are to be determined in the field by the City Engineering Inspector. All repairs to be in accordance with City street repair standards. Show how the proposed curb and gutter ties into the existing and what exactly you are removing/replacing. Define the limits of construction by shading or hatching in the approximate area of removals. 10/29/02: Please add the street cut note shown above to sheet C3 as note #8 65 5/21 /02: Provide a signature block for CDOT. 8/14/02: Repeat comment. Provide signature block on the cover sheet and the grading sheet. 10/29/02: Repeat comment. Provide signature block on the grading sheet. 98 8/14/02: The alley must be patched/repaired to city standards and will require a 2" mill and overlay at minimum. Please contact Dave Stringer in Development Review if you have any questions. Correct the street cut note to read as shown in comment #64. Page 1