The fire hydrant detail shown does not meet the City Standard nor the PFA standard. If this is for "blow off'
purposes only, then another appurtenance shall be utilized to prevent any confusion as to the purpose of the
hydrant. See Utility Plans C6 for hydrant detail
Department: Stormwater Utility
Topic: General
93
No More Comments.
Department: Transportation Planning
Topic: General
103
No Comments (11-3-02)
Issue Contact: Wes Lamarque
Issue Contact: Tom Reiff
Department: Water Wastewater Issue Contact: Roger Buffington
Topic: Utility Plans
104
Provide 8" x 6" reducer where fire hydrant connects to 8" water main. Revise utility plan and detail drawing..
Department: Water Wastewater Issue Contact: Jeff Hill
Topic: Utility Plans
102
Include the 3/4 and 1-inch interior meter setter detail on the detail sheet.
Be sure and return all of your redlined plans when you re -submit.
If you have any questions regarding these issues or any other issues related to this project,
please feel free to call me at (970) 221-6750.
Yours Truly,
BOB BARKEEN
City Planner
Page 3
10/29/02: Repeat. Correct the street cut note - see redlines.
105
This submittal was received between the monthly meetings scheduled with CDOT. Our next meeting is the
21st of November. The utility drawings will be submitted for CDOTs review at that time and the resulting
redlines and comments will be returned on the 22nd. All remaining comments can be addressed with the
mylar submittal. A CDOT permit, excavation permit, and DA will be required.
Department: Light & Power
Topic: General
1
NO COMMENTS
Issue Contact: Bruce Vogel
Department: Natural Resources Issue Contact: Doug Moore
Topic: Construction Drawings
81
The Tree Protection Specifications can be found under 3.2.1(G) of the Land Use Code. These Specifications
will need to be communicated on Construction Drawings and Landscape Plans as notes, drawings, detail
and possibly elevations to clearly communicate how the existing trees will be preserved.
Department: PFA Issue Contact: Ron Gonzales
Topic: General
24
WATER SUPPLY
A fire hydrant is required to be within 300 ft. of the building, and shall deliver 1500 gpm @ 20 psi,
25
ADDRESS
The building address is required to be visible from the street on which the property fronts, minimum 8 inch
numerals to be posted on a contrasting background
26
FIRE SPRINKLERS
This facility is required to be fire sprinklered (due to # of units).
27
VENTILATION SYSTEM
A ventilation and smoke removal system shall be installed for the underground parking lot in accordance
with 97UBC.
Department: PFA Issue Contact: Michael Chavez
Topic: Utility Plans
89
A 6-inch fire main is required.
Department: PFA Issue Contact: Ron Gonzales
Topic: Utility Plans/fire
107
The 6" fire sprinkler line shall not be installed under the parking lot or under the building. See Utility Plans sheet
C5.
If this sprinkler supply goes through a structure, it shall be properly protected from freezing and any other
damage in accordance with the appropriate NFPA standard for the installation of underground fire service
mains.
Page 2
.11. STAFF PROJECT REVIEW
City of Fort Collins
I
HILLHOUSE ARCHITECTS, INC. Date: 11/15/2002
JIM HILLHOUSE
8897 GANDER VALLEY LN.
WINDSOR, CO 80550
Staff has reviewed your submittal for VIALE COLEGIO PDP - TYPE I (LUC) & FINAL
COMPLIANCE, and we offer the following comments:
ISSUES:
Department: Advance Planning Issue Contact: Pete Wray
Topic: General
94
Coordinate removal of existing trees along College Avenue with City Forester.
Department: Current Planning Issue Contact: Bob Barkeen
Topic: Site Plan
100
The cover sheet of the site plan was not included with the latest submittal. This will need to be included. The
aerial photo may be omitted from this page. A signature block for the Current Planning Director and property
owner will need to be included on this page. The site data, title, and narrative are included as well.
The final mylar set will need to include the cover page, site plan. landscape plan and building elevations.
106
The bike rack shown in front of the building has been removed from this latest submittal. This will need to be
included on the site plan.
Department: Engineering Issue Contact: Susan Joy
Topic: Utility Plans
64
5/21/02: Show how much of the existing driveway cut is being removed and replaced and add the Street
Cut Note:
Limits of street cut are approximate. Final limits are to be determined in the field by the City Engineering
Inspector. All repairs to be in accordance with City street repair standards.
Show how the proposed curb and gutter ties into the existing and what exactly you are removing/replacing.
Define the limits of construction by shading or hatching in the approximate area of removals.
10/29/02: Please add the street cut note shown above to sheet C3 as note #8
65
5/21 /02: Provide a signature block for CDOT.
8/14/02: Repeat comment. Provide signature block on the cover sheet and the grading sheet.
10/29/02: Repeat comment. Provide signature block on the grading sheet.
98
8/14/02: The alley must be patched/repaired to city standards and will require a 2" mill and overlay at
minimum. Please contact Dave Stringer in Development Review if you have any questions.
Correct the street cut note to read as shown in comment #64.
Page 1