HomeMy WebLinkAboutGARTH COMMERCIAL PLAZA - PDP - 20-02B - SUBMITTAL DOCUMENTS - ROUND 1 - MAPS/GRAPHICSSERVICE: WORST CASE Isc AT A SERMC 7 VOLT, BRANCH CIRCUIT PANELBOARD 3-PHASE, 4-WIRE, WYE = 8,240A RMS SYMM. 10,000 AIC PANEL ACCEPTABLE (4p1 THHN CU & 1 p8 GRD)1.5"c 100/3 r 150/3 d 150/3 -2150/3 �150/3 NEMA 3R ENCL LET THROUGH Isc = 9,430A RMS, SYMM Isc = 15,430A, RMS SYMM PAD MOUNT TRANSFORMER Isc = 22,030A, RMS SYMM SERVICE LENGTH: APPROX. 60' UG PRIMARY TWO PARALLEL (4-250 kcmil XHHW AL)3.0"c BY PVREA ............. _..... FUTURE: TENANT PANEL CALCULATED DEMAND LOAD ON THE MAIN SERVICE: TENANT PANEL LOADS: 10.OVA/SF ASSUMED TENANT FINISH AND HVAC LOAD ALLOWANCE LOAD FOR WORST CASE SPACE = 34.7 KVA (96.4 A) - USE 150A PANEL TOTAL SERVICE DEMAND AFTER TENANT FINISH: 137.0 KVA (380 6A) •.... EMPTY 2.5"C TO EACH TENANT SPACE AND CAPPED FOR FUTURE BRANCH CIRCUIT PANELS, TYP. MODULAR METER CENTER, MMC WITH 22,000 AMPERE BUS BRACING. MINIMUM FEEDER 150/3 —BREAKER AIC RATING: 10.000 AMPERES. `UTILITY REVENUE MAIN SERVICE DISCONNECT: METER IN MMC, TYP. 400A, 4PSN WITH 400A LPN-RK FUSES IN REJECTION CLIPS. PROVIDE NEMA 3R ENCL. Ne, (A. BF)�?n s EXTEND (1 #2 cu GRD)1 "c TO METALLIC WATER SERVICE LINE ATt THE STREET SIDE OF THE MAIN SHUTOFFfl'2 PER NEC 250.52 AND BOND TO A DRIVEN3/4"x10' COPPERCLAD GROUND ROD.Q����+� ONE -LINE DIAGRAM CORE AND SHELL FOR LOTS 3 & 4 AT GARTH COMMERCIAL PLAZA - FORT COLLINS, CO ELECTRICAL SYSTEMS CONSULTANTS ELECTRICAL CONSULTING ENGINEERS FORT COLLINS COLORADO (070) 224-9100 SERVICE CALCULATIONS AND ONE -LINE DIAGRAM PREPARED BY: JOHN M. BENSON, PE