HomeMy WebLinkAboutHOWES/CANYON MIXED-USE (CORTINA) - PDP - 45-02 - CORRESPONDENCE - (6)Number: 118 Created: 5/7/2003 Per City Water/Sewer Utilities, the cleaning of the underground parking garage can drain into the sanitary sewer with some restriction. Please coordinate these efforts with Roger Buffington or Jeff Hill. The drainage that enters the garage needs to still drain into the storm sewer via a pump. This drainage should pass through the stormceptor as well. Number: 119 Created: 5/7/2003 The variance for the stormceptor has been accepted. Topic: Erosion/Sediment Control Number: 65 Created: 12/23/2002 Repeat Comment 3/11 /03 1. What is going to happen to protect the area from sediment during construction of the pipelines on the northwest corner of the site? Please call Bob Zakely at 221-6700 for any questions. Repeat 5/7/03 Department: Water Wastewater Issue Contact: Jeff Hill Topic: General Number: 115 Created: 5/1 /2003 Correct water main lowering detail to reflect the current conditions. See site, landscape and utility plans for other comments. Department: Zoning Issue Contact: Jenny Nuckols Topic: Zoning Number: 7 Created: 12/2/2002 Will the trash/recycle area be large enough to accommodate all of the uses/units in this building 4-16-03 - General Note #10 refers to trash enclosures - plural - I only see 1 and I have concerns that this is going to be adequate for 20 units. Will there be enclosures in the underground level that I am not seeing?? Number: 8 Created: 12/2/2002 Will there be any street lights along Canyon or Howes? Be sure and return all of your redlined plans when you re -submit. If you have any questions regarding these issues or any other issues related to this project, please feel free to call me at (970) 221-6750. Yours Truly, Bob Barkeen City Planner Page 3 Number: 113 Created: 4/15/2003 Is section A -A drawn to scale? Number: 114 Created: 4/15/2003 It looks like there will be a problem with cars bottoming out when coming out of the parking garage. Changing the grades isn`t required, but please know that the property owner/developer will be responsible for the maintenance of that driveway. Topic: Overall Utility Plan Number: 83 Created: 3/3/2003 Please show where the drain that collects the water from the driveway down to the underground parking will drain to. Repeat 4.15.03 Topic: Site Plan Number: 13 Created: 12/11 /2002 Encroachment permits are required for seat walls/columns/steps/etc. in the ROW. Also, an agreement with the DDA must be provided for the maintenance of these items, and for special paving. 3.3.03 - Please provide a letter of intent from the DDA prior to hearing, the encroachment permits are not required after all. Number: 16 Created: 12/11 /2002 Please see redlines and landscape plan for further comments. Repeat 3.3.03 Topic: Storm Drain Profile Number: 98 Created: 3/6/2003 There has been a change in policy regarding the use of geotextiles when less than 2' of cover is provided: only concrete pavement will be allowed in these locations, and textiles are no longer allowed. 4.15.03 - A variance will be required to allow less than minimum cover over the stormpipe. Please submit a variance in accordance with the requirements in LCUASS. If the variance is approved, notes will be required on the utility plans (on the plan and profile sheet) and the Development Construction permit referencing the variance. To gain cover over the pipe, consider using D.I.P. or C900. Department: Stormwater Utility Issue Contact: Wes Lamarque Topic: Drainage Number: 103 Created: 3/7/2003 There is concern that water will flow into the underground parking during the minor and major storms at the driveway entrance. There is no curb that can handle any amount of volume down the street. The building needs to be protected for storms up to the 100-year. For storms greater than the 100-year, no hydraulic sizing is required, but the flow needs to have an outfall other than the driveway, similar to detention ponds with the emergency overflow weir. The entrance to the driveway needs to be at a higher elevation than another point along that stretch of road. Please call Glen Schlueter or Wes Lamarque at 221-6700 to set up a meeting to discuss. Repeat Comment 5/6/03 - The new ramp is acceptable and does meet the requirements for the 7.2 cfs, however looking at the new Old Town Drainage Master Plan it was discovered that 49 cfs travels down Canyon Avenue from upstream basins during the 100-year storm. The new building needs to be protected from this flow. Please call Wes Lamorque at 416-2418 to discuss options. Number: 105 Created: 3/7/2003 A street capacity analysis needs to be included to prove that the building will be protected in the 100-year storm. This may include an analysis of the entire basin that contributes flow to Canyon and Howes Street. Repeat Comment 5/6/03 - The street capacity calcs need to show the flow that enters this sub -basin (49 cfs, 24.5 cfs each side of street) from the upstream basins as per the new Old Town Drainage Master Plan. Page 2 STAFF PROJECT REVIEW City of Fort Collins VF RIPLEY ASSOC CATHY MATHIS 401 W. MOUNTAIN AVE. #201 FT. COLLINS, CO 80521 Date: 5/16/2003 Staff has reviewed your submittal for HOWES/CANYON MIXED -USE PDP - TYPE II (LUC) - #45-02, and we offer the following comments: ISSUES: Department: Current Planning Issue Contact: Bob Barkeen Topic: Site Plan Number: 125 Created: 5/16/2003 The lease agreement for the underground storage units encroaching within the adjacent ROW will need to be adopted by City Council prior to approval of the final compliance and utility plans. Department: Engineering Issue Contact: Katie Moore Topic: General Number: 36 Created: 12/11 /2002 Please see redlines and utility plan checklist for any additional comments. 3.3.03 - repeat 4.15.03 - repeat Number: 99 Created: 3/6/2003 Where will the roof drains outlet? Please note that they will not be allowed to outlet over a public sidewalk - under -walk drains would be required. 4.15.03 - repeat Number: 100 Created: 3/6/2003 If under -ROW storage is approved, please provide detailed plans for it. 4.15.03 - A detailed structural design will be required prior to plan approval. Number: 109 Created: 4/15/2003 The sidewalk width along Howes needs to maintain at least 8' of clear walk along the steps at the corner. (6' for the walk plus 2'shy distance from the steps) Number: 110 Created: 4/15/2003 Please show outlines of underground structures on the site/landscape plans. Number: 111 Created: 4/15/2003 Please use the mid -block location detail from Drawing 1603 (LCUASS) for the handicap parking stall ramp. Number: 116 Created: 5/1 /2003 Where the storm sewer runs under the sidewalk, thicker concrete for the walk will be required (8'D. Number: 117 Created: 5/1 /2003 Please show where the perimeter drainage system/sump pit will outlet, and show the location of the sump pit. Topic: Grading plan Number: 112 Created: 4/15/2003 It appears that the layer with the spot elevations got turned off; please turn it back on. Page 1