HomeMy WebLinkAboutRAM'S CROSSING - PDP - 22-03 - CORRESPONDENCE - FIRE AUTHORITY REQUIREMENTS1997 UFC 901.2.2.2
Number: 29 Created: 9/25/2003
SPRINKLER REQUIREMENTS:
This proposed building shall be fire sprinklered.
Poudre Fire Authority requires a "Knox Box" to be mounted on the front of every new
building equipped with a required fire sprinkler system or fire alarm system
1997 UFC 902.4; PFA POLICY 88-20
Number: 30 Created: 9/25/2003
ADDRESS NUMERALS:
A. In Multi -family buildings more then one floor shall abide by the following
requirements.
1. The first floor units shall be designated with 100's.
2. The second floor units with 200's
3. The third floor units with 300's, and so forth.
B. All brass letters and numerals shall be posted on a black background.
C. Some multi -family layouts may require address postings from the back side as well as
the front of the buildings.
D. An addressing scheme shall be submitted to the fire department for approval prior to
being posted on the building.
E. A counter clock addressing pattern shall be maintained when ever possible.
Page 2
Project Comments Sheet
City of Fort Collins Selected Departments
Department: PFA
Date: September 25, 2003
Project: RAM'S CROSSING PDP - TYPE 1(LUC) #22-03
All comments must be received by Bob Barkeen in Current Planning, no later than
the staff review meeting:
No Review Date
Note - Please identify your redlines for future reference
Issue Contact: Michael Chavez
Topic: General
Number: 27 Created: 9/25/2003
REQUIRED ACCESS:
A fire lane is required. The fire lane shall be visible by painting and signage, and maintained
unobstructed. Buildings three stories or more in height must have access to a 30 foot
unobstructed access roadway on at least (1) one side for aerial operations.
The criteria for a required fire lane contain several conditions that must be met.
1. The minimum width shall be 20 feet.
2. Inside turning radius shall be 25 feet and outside turning radius shall be 50 feet.
3. Compacted road base shall be used during the construction phase only. The
permanent fire lane shall consist of asphalt or concrete and shall be required to
support 40 tons
4. The fire lane shall be platted as an "Emergency Access Easement" on the final plat.
1997 UFC 9012.2.1; 901.3; 901.4.21 902.2.11 FCLUC; PFA Policy 85-5 (B)
Contact Michael A. Chavez with PFA at 416-2869 for location of Fire Lane.
Number: 28 Created: 9/25/2003
WATER SUPPLY: Commercial
No commercial building can be greater then 300 feet from a fire hydrant.
Fire hydrants are required with a maximum spacing of 600 feet along an approved roadway.
Each hydrant must be capable of delivering 1500 gallons of water per minute at a residual
pressure of 20 si. _ '
/(p C D
ignature Date
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
Plat Site Drainage Report Other_
Utility Redline Utility Landscape
Page I
To: C -A
Re: 2 a\"s C� ss.
Date: 6 2 c1 . �� 3
Fax: S `{ S o
Pages:
(including this cover sheet)
5
City of Fort Collins
CURRENT
PLANNING
FACSIMILE
From the desk of...
Bob Barkeen
City Planner
City of Fort Collins - Current Planning
281 North College Avenue
P.O. Box 580
Fort Collins, CO 80522-0580
Email: bbarkeen@fcgov.com
970.221.6750
Fax: 970.416.2020