HomeMy WebLinkAboutSANCTUARY WEST - FDP - 30-07A - CORRESPONDENCE - (3)If you have any questions regarding these issues or any other issues related to this project,
please feel free to call me at (970)221-6341.
Yo rs Truly,
*Steve Olt
City Planner
cc: Susan Joy
Bill Veio
Planning file #30-07/A
Page 14
Number: 338 Created: 10/6/2009
[10/6/09] Add to the Waterline Notes on Sht 2 that the water mains shall be DIP with
polywrap or PVC with tracer wire.
Number: 339 Created: 10/6/2009
[10/6/09] Add the lengths of water main between valves, fittings, etc., etc.
Number: 340 Created: 10/6/2009
[10/6/09] Add steel casings whenever water or sewer mains cross under a storm drain that
is greater than or equal to 24-inch.
Number: 341 Created: 10/612009
[10/6/091 Specify diameter and thickness of each steel casing.
Number: 355 Created: 10/8/2009
[10/8/091 Label size of all storm sewer crossings on water and sanitary profiles.
Number: 356 Created: 10/8/2009
[10/8/09] Correct the references to 16-inch water main and list the correct sizes.
Number: 357 Created: 10/8/2009
[10/8/09] Revise the location of the point of connection to the existing 27-inch water main at
Laporte and Briarwood as noted on the red -lined plans.
Number: 358 Created: 10/8/2009
[10/8/09] Show ALL pipe crossings in the water and sewer profiles. Check elevations.
Some do not agree between water and sewer profile sheets.
Number: 359 Created: 10/9/2009
[10/9/09] Add water main and sanitary sewer stubs in Webb Avenue.
Number: 360 Created: 10/9/2009
[10/9/09] See red -lined plans for other comments.
Number: 361 Created: 10/9/2009
[10/9/09] Prior to the re -submittal of this project, more effort is needed on checking, cross
checking and quality control.
Department: Zoning Issue Contact: Gary Lopez
Topic: zoning
Number: 362 Created: 10/9/2009
[10/9/09] no issues
Be sure and return all red -lined plans if/when you re -submit for Final Plan review
Page 13
Number: 269 Created: 9/29/2008
[10/13/09] Contours are not reflective of spot elevations shown.
[9/29/08] Please revise contours and spot elevations on sheet 22 per redlines. Drainage
can not flow as arrows indicate.
Number: 272 Created: 9/29/2008
[10/13/09] Please see redlines for storm sewers that should be private, but were labeled as
public.
[9/29/08] Please label all storm sewers public or private on the Utility Plan sheets. Also,
please add a note on the storm sewer plan and profile sheets that all public storm sewers
are to be inspected by the City.
Number: 273 Created: 9/29/2008
[10/13/09]
[9/29/08] Pease differentiate between outfall, infall, vertical, and flush curb and gutter on the
grading plans and provide a legend.
Number: 277 Created: 9/30/2008
[10/13/09] Please see redlines for one additional separation issue.
[9/30/08] Please provide 10 feet of separation between storm sewers, inlets and canopy
trees. See redlines for specific locations.
Number: 364 Created: 10/16/2009
[10/16/09] Master Planning Comments:
1. (Repeat Comment #4) On the Utility Plans, the ultimate drainage channel is shown to
terminate at the northern property boundary. Please show this swale with a bend to the east
to match the hydraulic modeling submitted by URS so the location and size of the ultimate
water quality pond can be verified.
2. (Repeat Comment #5) Please revise the Ultimate Conditions hydraulic model to
incorporate the bend between Section 0 and Section 100. Also, please define the channel
bends and culvert skew at the Barton Street crossing in the model. This will be necessary to
determine if super elevation and/or bank stabilization will be required when the channel is
constructed.
3. (Repeat Comment #7) With this submittal, there is a pipe shown under Briarwood Road
in the Utility Plans. This pipe is not incorporated into the hydraulic modeling. If the pipe is
needed, please revise the hydraulic model to incorporate the standard bridge and weir
approach.
Number: 365 Created: 10/16/2009
(10/16/09] Please see redlined plans for other detailed comments and revisions.
Department: Stormwater-Water-Wastewater Issue Contact: Roger Buffington
Topic: Water/Wastewater
Number: 228 Created: 6/6/2008
[10/6/09] Will the water main in Briarwood be completed and accepted by the City prior to
the timing of the abandonment of the 27-inch steel main crossing the site?
[9/26/08]
[6/6/08] The water service for 2216 Laporte (actually fronts on Briarwood) currently
connects to the 27-inch main to the west which will be abandoned. This service will need to
be reconnected to the new main in Briarwood. How will service to this property be provided
throughout constructions?
Page 12
i
7. If XSs 830.35, 830.25, and 830.15 must be extracted for Proposed Conditions, then
they should not be in the Existing Conditions models.
a. These sections are skewed to the alignment of the road, and are too long to represent
accurate hydraulics. Removing the XSs from the Existing model will remove errors
associated with section alignments.
8. The proposed roadway should be modeled as an inline weir, not as a conveyance
element. The current representation of this roadway crossing skews the results to mask the
rise created by the construction of the new roadway.
a. A road embankment may only be simulated in RAS when the weir function of the
roadway is 90% submerged, or more. Submergence on this crossing will not be achieved,
and the road must be represented as a broad crested weir.
b. Since a broad crested weir is a rapidly -varied flow structure, hydraulics at the weir will
be governed by the weir equation, which does not factor Manning's roughness. Therefore,
the assertion in Section 3-4 of the Floodplain Modeling Report (Page 3-4, last paragraph,
last sentence) that fill will not cause a rise is false. This conclusion is not substantiated with
the current modeling.
9. Please correct rounding errors in Tables 3-9 and 3-11.
10. Please revise the Pond 903 hex. outlet pipe calculations to reflect the tailwater rating
curve from the downstream cross section. The max WSEL for max discharge was utilized
for most of the pipe analysis. HEC-RAS can compute a rating curve for this cross section,
which may assist with data input for the culvert analysis.
11. Please label all BFEs on all work maps attached to the Floodplain Modeling Report.
12. Please refer to attached comments from the City of Fort Collins Floodplain. Review
Checklist (50% Development Review Submittals) for additional comments.
Topic: Stormwater
Number:135 _ Created:3/19/2008
[10/9/09] We have standard details that include more information. Please replace with our
standard details.
[5/7/08] At final compliance.
(3/19/08] Please provide design and details for the ultimate condition water quality ponds
and outlet structures.
Number: 264 Created: 9/26/2008
(10/13/09] On the overlot grading plan, notes and some spot grading needs to be included
to show how the low flows entering the property from the private pond to the west will not
flow into this proposed water quality detention pond. A constant low flow will cause
problems to the proposed detention ponds.
[9/26/08] The south water quality pond is proposed within a wetland and will have problems
with ground water. The pond will fill full of water and flow down to the retention pond where
there is no outfall. This will cause both the water quality pond and the north -south retention
pond to fill with 3 feet or more of water. The pond can not hold water for more than 72
hours, so this is a problem and needs to be resolved.
Number: 266 Created: 9/26/2008
[10/13/09] The final grading contours are still hard to read. There are also errors with the
final contours inn several locations.
[9126/08] Please revise the final grading plans by removing the overlot grading contours that
will be changed with the final grading. Please darken the overlot grading contours that will
remain unchanged. This will make these plans easier to read. Also please lighten the
existing contour labeling, they are black when the contours are grey.
Page 11
Number: 351 Created: 10/7/2009
[10/7/09] Several sheets have the "Matchline - See Sheet X" text labeled incorrectly.
Number: 352 Created: 10/7/2009
[10/7/09] The utility plans have line over text, text over text & text over symbol issues.
Number: 353 Created: 10/7/2009
[10/7/09] Several sheets of the overlot grading plans have line work missing near text.
Department: Stormwater-Water-Wastewater Issue Contact: Wes Lamarque
Topic: Floodplain
Number: 363 Created: 10/16/2009
[10/16/09]
1. The Floodplain Modeling Report prepared on September 10, 2009 and stamped by
John S. Griffith, P.E. #16030, is not complete as submitted and cannot be fully reviewed at
this time. The necessary revisions and corrections identified during this review process will
modify the results of the report, and those results must be reviewed before the report can be
approved.
2. Repeat comment from 09-2008; please combine all simulations into 1 single Project file
in HEC-RAS. This will allow all simulations to be compared against each other within the
same project.
a. The following note provided in the response to comments is not be acceptable; All
simulations are provided in the reports as they have been in previous submittals.
b. The Proposed Conditions model contains plan, geometry, and flow files labeled as
Existing. Please correct this error in all Proposed Conditions simulations.
3. Repeat comment from 09-2008; please add the off-line calculations for the discharge
from the existing hexagonal culvert to the Floodplain Modeling Report.
a. The analysis was included in the CD attached to the report, but the report must be
maintained as a stand-alone document. All supporting analyses, maps, technical
documentation, and text must be included in print, and bound in the text or Appendix of the
report.
4. The current No -Rise Certification does not explicitly identify which features must be
certified against no -rise. Furthermore, the report conclusions determine there is no rise
created by the project — this is not true, but if it were, the report would be internally
inconsistent. Please remove the current No -Rise Certification from the report.
a. All proposed modifications within the floodway must be accompanied by a No -Rise
Certification that is signed, stamped, and dated by a registered P.E. licensed to practice in
the State of Colorado.
b. Any No -Rise Certification must be accompanied by a floodplain use permit, and
submitted to Stormwater for approval prior construction mobilization.
5. A corrected effective condition must be prepared for this suite of models. The report
identifies changes to cross section location, and updates to cross section station/elevation
pairs with 2007 topo. The effects of these combined changes must be individually broken
out so the impacts from DE to CE, from DE to Existing, and from CE to Existing can be duly
investigated and justified.
6. Revise all references to interim conditions to read proposed conditions for clarity. You
may still reference the ultimate condition when referring to the residual floodplain anticipated
after the fully constructed Master Plan improvements are in place.
Page 10
Department: PFA Issue Contact: Carle Dann
Topic: Fire
Number: 330 Created: 10/6/2009
Good general notes regarding the Emergency Access Easements. Let's get together soon to
hammer out a Fire Lane Plan for signs and/or red curb paint.
Department: Traffic Operations Issue Contact: Ward Stanford
Topic: Traffic
Number: 114 Created: 11 /15/2007
[10/12/09] Have not received the formal variance request for excluding the left turn lanes.
[10/21 /08]
[5/12/08] The East bound left turn lane on Laporte is a LCUASS policy that'all arterials will
provide left turn pockets at accesses. You will need to request a variance to this standard
with justification as to why this development should not need to meet this policy.
[11/15/07] Per Figure 8-1 of the LCUASS, this project will need to provide an east bound
left turn lane at its west access. It may be negotiable to forego the left turn lane in favor of a
reversible lane east of your west access to provide a 2 stage left turn capability from the
west access for your residents trying to turn onto east bound Laporte during the AM rush
hour.
Department: Technical Services Issue Contact: Jeff County
Topic: Architectural Elevations
Number: 348 Created: 10/7/2009
[10/7/09] Sheet #11 is mis-labeled as a landscape plan.
Topic: Landscape Plans
Number: 347 Created: 10/7/2009
[10/7/09] The landscape plans have line over text issues.
Topic: Plat
Number: 344 Created: 10/7/2009
[10/7/09] The boundary and legal close.
Number: 345 Created: 10/7/2009
[10/7/09] The right of way & easements along Barton Drive and Brairwood Road that are to
being dedicated by separate document, must have reception numbers shown on the plat
prior to filing.
Topic: Site Plans
Number: 346 Created: 10/7/2009
[10/7/09] The site plans have line over text & text over text issues.
Topic: Structural Plans
Number: 349 Created: 10/7/2009
[10/7/09] Sheet S1.1 of the structural plans, has line over text issues.
Topic: Utility Plans
Number: 350 Created: 10/7/2009
[10/7/09] The benchmark descriptions & the "City's benchmark system name" are incorrect.
See sheet 3.
Page 9
[10/10/08] Station all driveway intersections in both plan and profile views. If you don't want
to station both sides of the driveways, you station one side only and put a typical driveway
intersection detail on each sheet of the P&Ps showing the one side stationed and dimension
out the typical width of the driveway. That way you would only have to station both sides of
atypical driveways.
Number: 309 Created: 10/10/2008
[10/15/09] The ultimate section of the roadway must be carried through, both sides of the
street to the PL. Only the extra half circle within the temp turnaround can be constructed in
the interim.
[10/10/08] Please provide an ultimate design for Kruse Drive to the end of the property line.
Please provide an estimate for the removal of the temporary turnaround and landscaping
and construction of the ultimate Kruse Drive to the property line for our review and approval.
See comment 51 for the history of this comment.
Number: 320 Created: 10/10/2008
[10/16/09] Repeat. Please see comment 309 on the minimum limits of the ultimate street
pavement section.
[10/10/08] Kruse Drive interim temp turnaround - please station/define the limits of the full
street improvements and where the limits of the temp turnaround construction are.
Number: 380 Created: 10/21 /2009
[10/21/09] Please add "and sidewalks" to the label stationing the end of temp asphalt
roadways on the profiles, each street this comment applies.
Topic: Utility Plans - Utility Sheet
Number: 285 Created: 10/8/2008
[10/15/09] Repeat.
[10/8/08] Please provide utilities from Barton Drive through Webb Ave to the property line or
at least past the ultimate road improvements so that the property to the south can tie in
without cutting into the street. If the utilities are not provided to the property line, an
estimate for their construction is required for our review and approval.
Number: 303 Created: 10/8/2008
[10/15/09] Repeat -the utilities must be constructed to the eastern PL.
[10/8/08] Sheet 34 - Kruse Drive utilities (sanitary, water, electric, gas, etc) needs to be
stubbed to the property line.
Topic: Utility Plans - Water Profiles
Number: 312 Created: 10/10/2008
[10/15/09] Still need note on Sheet 56A.
[10/10/08] Please provide a detail (label if where it's shown if on another sheet) for all
encasements, lowerings, etc on the water and sewer plan and profile sheets.
Department: Light & Power Issue Contact: Alan Rutz
Topic: Light and Power
Number: 354 Created: 10/8/2009
[10/8/09] No issues
Page 8
Number: 300 Created: 10/8/2008
[10/15/09] Some still "off', others missing. Other grading sheets have the same issue.
[10/8/08] Sheet 23 - spot elevations for the lot corners are "off' just a little bit... not on the
corner itself.
Number: 315 Created: 10/10/2008
[10/15/09] Please label the concrete drainage pan on the Final Grading Sheets (can show
as "typical") or add it to the Legend. Please provide a drainage easement on each lot that is
showing one of the pans located on it otherwise people may try to remove the pans in the
future.
[10/10/08] Sheet 63 - Please add a label that the concrete trickle pan detail is to be "For
private'improvements only. This detail is not to be used in public right-of-way."
Number: 376 Created: 10/21 /2009
[10/21/09] Need to provide min -max heights on the retaining walls and a min -max on the
slope sections.
Number: 378 Created: 10/21 /2009
[10/21/09] There appears to be another retaining wall(s) in Outlot C? If so, please label and
provide the bow, tow information. If over 3, then we'll need a typical section on the utility
plans with the final structural design provided to Building and Zoning at permit. Please
coordinate the Site and Landscape plans as well.
Number: 379 Created: 10/21 /2009
[10/21/09] The proposed grading needs to tie into the existing grades (in both overlot and
final). The grading shown is incomplete, missing or does not tie in.
Topic: Utility Plans - Plan & Profiles
Number: 248 Created: 6/6/2008
[10/15/09] Repeat.
[10/8108] Please add in the future 9' LIE and show, label in both the plan view and the typical
section.
[9/25/08] [6/6/08] This development is responsible for designing the full street section for
Briarwood. Please show sidewalks on the east side but label as "future".
Number: 287 Created: 10/8/2008
[10/15/09] We still need the intersection spot details.
[10/8/08] Please provide intersection spot details in accordance with Figure 7-27 and 7-28.
Number: 305 Created: 10/10/2008
[10/15/09] Repeat - the curb can not change type in the middle of the block. Barton Drive,
south flowline, must stay the same from PC to PC.
[10/10108] All concrete sections of the street must be constructed by block, from PC to PC.
In other words, all of Briarwood must be constructed in concrete and Barton from Tavelli to
the east side of Briarwood must be constructed in concrete (to the PC, see redlines).
Number: 306 Created: 10/10/2008
[10115/09] Repeat. These are narrow lots and the driveways must be placed exactly where
they are shown to make sure they aren't placed over the water line. Can do either a typical
lot detail with dimensioning for the rollovers and place a note on the plans that states that all
driveways must be constructed per the detail OR you can individually station them.
Page 7
improvements. Please provide all of the necessary design details as discussed in comment
72. This addition to the plans will trigger the need for another offsite drainage easement.
Number: 292 1 Created: 10/8/2008
[10/15/09] Please see the comments from Tech Services.
[10/8/08] The match lines do not match up, each sheet. There is a space missing between
the two from sheet to sheet.
Topic: Utility Plans - Grading
Number: 243 Created: 6/6/2008
[10/15/09] Repeat. I see that you submitted separate structural plans but those aren't
review or approved until you pull a permit for those with the Building Department. If you
could put the typical sections into the utility plans with a note stating that the final design will
be submitted prior to construction, that would be good enough for us. :) Please see Peter
Barnes in Building and Zoning if you have any questions about the permit you will need for
them.
[9/25/08] Please provide a detail for all walls greater than T from the bottom of the footer.
[6/6/08] Label all retaining walls with tow, bow.
Number: 244 Created: 6/6/2008
[10/15/09] Your response letter stated that the retaining wall has been removed but the
plans still indicate "something" is happening there. Also, the portion of the sidewalk that was
removed has to be approved by Transportation Planning.
[10/8/08] The horizontal control sheet shows what appears to be a retaining wall in the
southeast corner of Briarwood and Barton Drive but it doesn't show up on the Final Grading
Sheet. It's hard to tell because the match lines are off and there is missing information.
This area is a little convoluted... not sure what information is being shown here. There
seems to be a section of sidewalk proposed with this project extending to the south - please
remove.
[6/6/08] The retaining wall needs to be a minimum of 2' behind the sidewalk and cannot be
in public row. This will push the wall on the neighboring property and requires a letter of
intent prior to scheduling the public hearing.
Number: 295 Created: 10/8/2008
[10/15/09] Still missing some.
[10/8/08] Please provide finish grade elevations for all lot corners. I marked a few but did
not get them all.
Number: 297 Created: 10/8/2008
[10/15/09] Information was provided for two out of four sidewalks.
[10/8/08] Please provide spot elevations and slope info on the sidewalk connecting to Webb
Avenue.
Number: 299 Created: 10/8/2008
[10/15/09] Repeat. This duplication shows up on other sheets as well.
[10/8/08] Sheet 23 is showing a duplicated line for the property that juts into the detention
pond. See redlines.
Page 6
Topic: Utility Plans - Cover Sheet
Number: 162 Created: 3/20/2008
[10/15/09] The typical street sections have been corrected, however, the changes were not
carried throughout the rest of the sheets and curb types can not change in the middle of the
block as shown on the south side of Barton. Please cant' the curb type all the way to the
PC at Briarwood.
[10/8/08] Please list the names of the streets under each typical section on the cover sheet.
Please remove "and drainage" in the easement labels so that it matches the plat. Please
correct this throughout the plan set.
[5/5/08] [3120/08] Typical street sections need to be identified by street name as the
sections are not typical and change from street to street with the different curb types. Curb
types can change at the end of blocks but may not occur in the middle of a block. Missing a
typical section for Webb Avenue.
Number: 294 Created: 10/8/2008
[10/15/09] Please provide the name and date for each of the reports.
[10/8/08] Please reference the updated or current soils investigation report and the
subsurface report.
Topic: Utility Plans - Detail Sheets
Number: 375 Created: 10/21 /2009
[10/21/09] Please label all details for private improvements as "private" or "on -site".
Number: 377 Created: 10/21/2009
[10/21/09] Please replace detail 709 with detail D10, 11, 12 or 13 which ever applies and
correct the labeling on the various grading sheets.
Topic: Utility Plans -General
Number: 56 Created: 10/30/2007
[10/15/09] The line weights continue to be a problem as most of the line weights used are
the same. It's very hard to tell which is which, as they are almost all identical. Please
choose different line weights for each feature, use darker for proposed and greyscale for
existing. There is also a faint line shown around the east side of the project that varies in
distance from the property boundaries and I do not know what it is supposed to represent.
I'm a little concerned as to what other comments may turn up with the next round of review
once things are presented more clearly.
[10/8/08] The existing ditch line weight needs to be added to the Legend.
[5/5/08] [3/19/08] Please label existing ditches as "to be removed" where ever applicable.
[10/30/07] There are a couple of small existing irrigation ditches shown but what are you
doing with them? Are you removing? Relocating? Something needs to be done as they
cross individual lots. Each and every affected ditch owner will require a signature block on
each sheet where their ditch is shown to be impacted.
Number: 93 Created: 11 /2/2007
[10/15/09] (9/25/08] [6/6/08] [5/5/08] [3/19/08] [11/2/07] See redlines for other comments.
Number: 286 Created: 10/8/2008
[10/15/09] [10/8/08] The newly added culvert in Briarwood Drive needs to be extended to
the east so that it works for the ultimate. The flared end section needs to be placed outside
of the future 9' LIE. Also, if the minimum 2' of cover over the pipe to subgrade is not met,
that section of the street will need to be in concrete, from PC to the end of the ultimate
Page 5
Number: 321 Created: 10/10/2008
[10/16/09] Repeat comment. Please resubmit the corrected documents on the city's
standard dedication template.
[10/10/08] Easements 1, 2 and 3 were received (those surrounding Briarwood), however
there are some outstanding issues.
The exhibit for Vattano is missing the Book and Page.
The exhibit for Phillips is missing the Book and Page.
The exhibit for Alumbaugh is missing the Book and Page.
The dedication statement for Alumbaugh was not submitted with the City's standard
dedication language. Also, there are two properties on the west side of Briarwood. This
easement does not make it clear that both properties are dedicating this easement.
Perhaps a legal description is in order?
Topic: Site and Landscape Plans
Number: 366 Created: 10/16/2009
[10/16/09] Please label either the tow, bow on all retaining walls OR label with the walls with
their height. This is the only way that the Building Department will know whether or not you
need a permit or a structural design for them at the time of construction.
Number: 367 Created: 10/16/2009
[10/16/09] Please define all abbreviations in a legend or you can spell everything out on the
plan sheets. Either way works for me. :)
Number: 368 Created: 10/16/2009
[10/16/09] The easements shown on Lot 1 at the end of Kruse street need to match the
plat.
Number: 369 Created: 10/16/2009
[10/16/09] Please add a ramp on the north side of Barton at Webb Street.
Number: 370 Created: 10/16/2009
[10/16/09] A portion of the sidewalk along Laporte does not match what is shown on the
utility plans. Please coordinate with Loonan and correct whichever one is wrong. Thanks
Terence!
Number: 371 Created: 10/16/2009
[10/16/09] There are a few line weights running around the east side of the property and I'm
not exactly sure what they are. Some sheets have labels and leaders pointing to them and
on others, the labels point to something else. Perhaps the leaders are just a little off?
Topic: Site Plan
Number: 318 Created: 10/10/2008
[10/16/09] [10/10/08] See redlines and coordinate with comments under other topics.
Number: 324 Created: 10/10/2008
[10/16/09] [10/10/08] Please clearly label and identify concrete & interim asphalt
improvements (sidewalk, street) and all type III barricades.
Page 4
Number: 326 Created: 10/16/2008
[10/16/09] Under review. Will finalize as we get closer to mylars.
[10/16/08] Please provide an estimate for the design and construction of the future Laporte
Street improvements along your frontage for our review and approval.
Number: 372 Created: 10/21 /2009
[10/21/09] All Plan Sets will need to be adjusted if the school's property is being transferred
to this Development instead of remaining the school's property with them signing the plat
and plan sets.
Number: 373 Created: 10/21 /2009
(10/21/09] Easements shown on the plat do not match what's shown on the utility plans.
Additional drainage easements are needed where lots share a concrete drainage pan and
some areas are calling for drainage easements where none are required.
Number: 374 Created: 10/21 /2009
[10/21/09] Ownership of the lots east of Outlot C has changed. Please change the plan
sets accordingly.
Topic: Landscape Plans
Number: 317 Created: 10/10/2008
[10/16/09] [10/10/08] See redlines and coordinate with comments under other topics.
Number: 323 Created: 10/10/2008
[10/16/09] [10/10/08] Please clearly label and identify concrete & interim asphalt (sidewalk,
street) and all type III barricades.
Topic: Mite Easements
Number: 160 Created: 3/20/2008
[10/15/09] [9/25/08] Keeping this open until the property is transferred from the school.
[6/6/08] This is still an issue and needs to be resolved prior to hearing.
[5/5/08] Barton row needs to be dedicated all the way to the existing property line so that a
separate tract of land isn't dividing the row and Sanctuary West. Conversations with
Vignette indicated that the school district was going to dedicate this area to the development
to be owned and maintained by this development. Either solution is fine, the plans just need
to reflect the option you are going with and all appropriate letters of intent received prior to
scheduling the hearing.
[3/20/08] Offsite row, slope & utility easements are required for Barton through the school
property. Offsite slope easements may be required for the Webb Ave street stub depending
on where the 4:1 slope ends. Offsite slope and utility easements are required to complete
the Briarwood connection to Laporte. An offsite access easement will be required for the
sidewalk through the small lot on the north side of the large detention pond. In order to go
to hearing, only letters of intent from the affected property owner is required. The actual
easement itself will be required during FC and prior to plan approval.
Number: 308 Created: 10/10/2008
[10/15/09] [10/10/08] The necessity for anew off -site easement has been generated by the
addition of a culvert in Briarwood Drive.
Page 3
Number: 343 Created: 10/7/2009
[10/7/09] Don Kapperman of Comcast Cable indicated that they have no problems or
concerns with the current Final Plans.
Department: Engineering Issue Contact: Susan Joy
Topic: General
Number: 43 Created: 10/30/2007
[10/15/09] Thank you for the estimates however they are a little early. There will be the
need to update them with the next round of review. Hang on to them for now until we're
ready for mylars and then we can review them once we're sure nothing is changing.
[10/8/08] Please provide an estimate for the design and construction of Webb Avenue to
the property line for our review and approval. I will email you a template to use.
[10/30/07] This project is responsible for the design and construction of Webb Ave to the
property line plus 500' of offsite preliminary design. At minimum, Webb Ave must be
constructed to the PC's (including the pedestrian ramps) and type III barricades must be
provided. If any portion of the road is not constructed (from the PCs 'to the PL), then this
development is required to escrow the cash necessary to complete the street. An estimate
for our review and approval will be required in FC and that number will go into the
development agreement to be paid prior to the first building permit. Also, need to watch
whether the street is tipping up or down because the drainage has to either stay on site or a
drainage easement from the offsite property owner will be required.
Number: 213 Created: 5/14/2008
[10/15/09] Still do not match (example, see utility plans, sheet 10 and 17). Please make
sure that all plans, all sheets are showing the same thing. See the comment below
regarding the configuration and construction of the sidewalk.
[9/25/08] The utility plans do not match the site and landscape plans for this comment.
Please terminate the sidewalk perpendicular to the property line (you can't construct a
diagonal piece and add on to it successfully later).
[6/6/08] Just carrying this through until FC.
[5/14/08] The sidewalk in Outlot E is terminated prior to the property line. This development
will be responsible for escrowing the remaining dollars needed to complete the sidewalk to
the property line so that when the neighboring property develops, they will have the money
to tie into it. An estimate will be required in Final Compliance for our review and approval.
The agreed upon figure will be put into the DA and paid prior to the issuance of the first
building permit.
Number: 291 Created: 10/8/2008
[10/15/09] [10/8/08] The future sidewalk connection from Tavelli to the west into the
detention area is in conflict with proposed culvert. Please design the placement of the
culvert so that it accommodates the future sidewalk connection.
Number: 316 Created: 10/10/2008
[10/16/09] Thank you for submitting the estimates. I will hang on to them until the plans are
ready for mylars and review them at that time. Please adjust your estimates as we continue
to adjust the plans but don't submit the updated estimates until we call for mylars.
[10/10/08] Please provide an estimate for the design and construction of Barton and
Briarwood to Laporte from the point you are ending the ultimate improvements to the new
row for our review and approval.
Page 2
STAFF PROJECT REVIEW
'City of Fort Collins
Vignette Studios Date: 10/26/2009
c/o Terence Hoaglund
Staff has reviewed your submittal for SANCTUARY WEST, FINAL PLANS - Revisions, and
we offer the following comments:
ISSUES:
Department: Current Planning Issue Contact: Steve Olt
Topic: Architectural Elevations
Number: 337 Created: 10/6/2009
[10/6/09] Front Elevation for Plan B, sheet 10, appears to be incorrect. It is the Front
Elevation for Plan A on the same sheet and does not fit with the other 3 elevations for Plan
B.
Department: Current Planning Issue Contact: Dana Leavitt
Topic: General
Number: 381 Created: 10/23/2009
[10/23/09] Coordinate adding Limits of Development (LOD) line on all drawings, per
conversation w/ T. Hoagland on 10/22/09.
Department: Current Planning Issue Contact: Steve Olt
Topic: Landscape Plans
Number: 333 Created: 10/6/2009
[10/6/09] Sheet 8 of the Landscape Plan, ditto question in Site Plan comment #332.
Number: 334 Created: 10/6/2009
[10/6/09] The 2 (?) Sight Distance Easements are, for the most part, lost on Sheets 6 & 8 of
the Landscape Plans.
Number: 335 Created: 10/6/2009
[10/6/09] On the Landscape Plans, ditto Site Plan comment #331.
Number: 336 Created: 10/6/2009
[10/6/09] A number of apparent storm sewer lines are not labeled on the Landscape Plans.
Topic: Site Plan
Number: 331 Created: 10/6/2009
[10/6/09] There are lots of undefined lines on the Site Plans. Please see the red -lined plans
being forwarded to the applicant.
Number: 332 Created: 10/6/2009
[10/6/09] On Sheet 5 of the Site Plan there is a parallelogram shaped parcel between Outlot
O and Lot 13, Block 2 that is not defined. What is it?
Topic: Utilities
Number: 342 Created: 10/7/2009
[10/7/09] Richard Stiverson of QWEST indicated that they have no problems or concerns
with the current Final Plans.