HomeMy WebLinkAboutCINGULAR, TAFT HILL & ELIZABETH (CEDARWOOD PLAZA) WTF - PDP - 31-03A - CORRESPONDENCE - (5)Department: Stormwater-Water-Wastewater Issue Contact: Roger Buffington
Topic. General
Number: 15 Created: 9/21/2005
[1/19/06],There is a sanitary sewer line in the vicinity of the south property line. It may be in
the north edge of the residential lots. Provide 10 feet of separation between the sewer and
any new underground utility lines. The new underground utility lines must also be 10 feet
from the existing water line.
[11/21/05]
[11/15105] (Repeat comment) Sewer is not•shown.
(9/21/05] There is a water main and a sanitary sewer that extend west from Taft on the
south side of the Farmers Table and behind the buildings to the northwest. Field locate
these lines and show on the site plan so that potential conflicts (if any) can be identified.
If you have any questions regarding these issues or any other issues related to this project,
please feel free to call me at (970) 221-6750.:
Sincerely,
P���pen O9
H. As
City Planner
Page 2
F'a
Cityof Fort Collins
STAFF PROJECT REVIEW
MATZKO CONSULTING Date: 01/20/2006
MICHAEL MATZKO
PO BOX 3600 c e&1 * Mdke 1/2,Io(o
AVON, CO 81620
Staff has reviewed your submittal for CINGULAR, TAFT AND ELIZABETH (CEDARWOOD
PLAZA) WTF - TYPE I, and we offer the following comments:
ISSUES:
Department: Current Planning
Topic: General
Number: 14
Issue Contact: Anne Aspen
Created: 9/21 /2005
[1/20/06] There is still concern from a number of City Staff on the location of this WTE.
Staff has already indicated that stealth technology may be a sufficient alternative to co -
location since you have made a good faith effort in that direction. But in fairness to the
neighborhood, staff requests a neighborhood meeting so that the affected property owners
have a chance to voice any concerns prior to the hearing. Please contact me to schedule
this meeting.
[9/21/05] Staff is concerned about the visibility of this tower from Taft Hill Road and the
neighborhood to the south of the shopping mall. Please show other possible locations and
tower configurations that will reduce the visibility of this equipment: can you locate on top of
the existing roof? Can you use equipment that is less visually intrusive? Can you locate
somewhere else on the site that would have fewer impacts to the surroundings? We have
several good examples here in Fort Collins that better achieve compatibility. Please let me
know if you would like pictures of these.
Number: 10 Created: 9/20/2005
[1/17/06] Since the project has been relocated, the setback has changed. The pole is now
47 feet from the property line so the height cannot exceed 47 feet. Please revise.
[9/20/05] Per the Land Use Code, you must provide a foot of setback from the nearest
property line for every foot of height for a monopole assembly unless you demonstrate to the
Director of Current Planning that the structure would collapse not topple. It appears that you
may have already met the setback requirement. This will be confirmed once you have
labeled the property line.
Number: 8 Created: 9/20/2005
[1 /17/06]
(9/20/05] The Building Inspection Department requires a pre -submittal Code Review
Meeting for all projects. This project must meet the UBC and the2005 National Electrical
Code. Plans Analyst Rick Lee advises you to be aware that Fort Collins is a high wind
location (100 mph) so the mounting devices need to be designed to satisfy this requirement.
A scan of their comments will be emailed along with your staff review comment letter.