HomeMy WebLinkAboutFORT COLLINS COLORADOAN - FDP - 41-03A - CORRESPONDENCE -Topic: Erosion/Sediment Control
Number: 87 Created: 2/27/2004
[6/24/04] Repeat Comment
[3/30/04] Repeat Comment
1. Previous note #2 has not been addressed. Also include a note stating that all
disturbed areas are to be seeded and mulched.
Department: Water Wastewater Issue Contact: Jeff Hill
Topic: Utility
Number: 104 Created: 6/21 /2004
(6/21/04] Maintain 10 feet of separation between thrust blocks and all other
underground utilities. Provide copies of the utility easement documents for the water
main and fire hydrant for our review.
Number: 105 Created: 6/21 /2004
[6/21/04] Clearly define that the water service is to be 1 1/2" from the main to a point
5 feet downstream of the meter pit.
Number: 106 Created: 6/21 /2004
[6/21/04] Reconfigure the alignment of the fire line and fire hydrant to avoid multiply
fittings and thrust blocks.
See site, landscape and utility plans for other comments.
Be sure and return all of your redlined plans when you re -submit.
If you have any questions regarding these issues or any other issues related to this
project, please feel free to call me at (970) 221-6750.
Yours Truly,
/�
Ted Shepard
City Planner
Page 5
Number: 99 Created: 3/31/2004
[6/22/04] Sheet 6 now sheet 7 - A new manhole has been added in the middle of a
ramp. Please relocate. See redlines for approximate limits of the street cut per
Lance Newlin, Chief Inspector. Show phase line.
[3/31/04] Sheet 6 - Remove note to vacate existing utility easement along Riverside
as it is not necessary (see earlier comment). Correct the asphalt patch note to
reference note 10, sheet 6. This sheet will not scan for same reasons mentioned
earlier.
Number: 100
[6/22/04] Sheet 7 now sheet 8 - repeat.
corners. Need to show phasing.
Created: 3/31 /2004
Please provide spot elevations for all lot
[3/31/04] Sheet 7 - Please provide the note shown in the checklist, Appendix E4,
section II, paragraph E. Correct all scanning issues. Please provide spot elevations
for ALL lot corners.
Number: 109 Created: 6/22/2004
[6/22/04] Sheet 4, 5, 7, 8, 9 and 11 - show phasing line.
Number: 110
[6/22/04] See redlines for other comments.
Department: Stormwater Utility
Topic: Drainage
Number: 49
[6/22/04]
[3/30/04]
[2/27/041 Reminder Comment
Created: 6/22/2004
Issue Contact: Wes Lamarque
Created: 1 /7/2004
Drainage easements are required for the water quality pond and storm sewers.
Number: 88
(6/22/04]
Created: 2/27/2004
[3/30/04] Please also include a detail for the attachment of the orifice plate and well
screen to the retaining wall. Currently, the orifice and well sreen details are
only included.
At final review, please include a site specific water quality outlet structure detail on
the plans.
Page 4
[2/23/04] [1/6/04] Please provide spot elevations along Riverside's flowline and at
the PCs of the driveways so that we can verify whether or not minimum
grades are being met.
Number: 66 Created: 2/23/2004
[6/22/04] Any retaining wall over 30" requires handrails. Please provide finish
information (class 5?).
[3/30/04] You've added a retaining wall detail to sheet 11 with the latest round.
Please revise the note requested below to include sheet 11 as well or put all
the retaining wall details together so that you only have to reference one
sheet.
[2/23/04] Sheet 6: Label the retaining wall and reference the details on sheet 8 and
9.
Number: 70 Created: 2/23/2004
[6/22/04] Repeat comment.
[3/30/04] Repeat comment. Missing two lot corners and missing the spots around
the curb return in the eastern corner. The curb return is not even shown in its
entirety, please provide.
[2/23/04] Sheet 7: Incomplete spot elevations provided.
Number: 96 Created: 3/31/2004
[6/22/04] Repeat. Please see E6 for minimum font size and greyscale. Please
show the existing concrete structure that's to be removed.
[3/31/04] Sheet 3 - Remove all shading and replace with building outlines. The
shaded areas will not scan. Correct all overlapped labeling and please see
Appendix E6 for other scanning requirements regarding minimum grey scales and
pen weights.
Number: 98 Created: 3/31 /2004
[6/22/04] Sheet 5 now sheet 6 - repeat comment. Remove shading for scanability.
Spell out "drainage easement" or "drainage and utility easement". See redlines.
[3/31/04] Sheet 5 - Will not scan for same reasons mentioned before. Label
drainage easement, label existing easements as "existing'%see redlines, and correct
retaining wall note.
Page 3
[2/23/04] Repeat comment, applies to all plan sets, all sheets. None of the plan
sets/sheets are scannable.
[1/6/04] See Appendix E-6 for scanability requirements. The current font size is too
small in some cases and in others, overlapped and illegible.
Number: 28 Created: 1 /6/2004
[6/22/04] Repeat. The utility plans need to show a Phase line, see comments under
"Utility".
[3/30/04] [1/6/04] There is phasing for this project and the plans do not show it.
Please show phasing (parking lot, erosion control, etc) on the appropriate
sheets as well as the Site and Landscape plans. All plan sets need to
present the same information.
Number: 108 Created: 6/22/2004
[6/22/04] The ramps at the driveways are not drawn correctly and do not meet the
standard as shown. Please correct all plans (site, land, utility).
Topic: Landscaping
Number: 81 Created: 2/23/2004
[6/22/04] [3/31/04] Repeat comment. Please label the easements correctly. See
redlines.
[2/23/04] Show and dimension all easements.
Topic: Site
Number: 92
[6/22/04] Repeat comment.
Created: 3/31 /2004
[3/31/04] All existing easements need to be labeled as "existing", all proposed
easements to be dedicated by separate document need to be labeled as "to be
dedicated by separate document'.
Number: 107 Created: 6/22/2004
[6%22/04] See Appendix E6 for scanning requirements (ie: minimum greyscale).
Remove all shading as it will not scan. See redlines.
Topic: Utility
Number: 32 Created: 1 /6/2004
[6/22/04] Sheet 7 now sheet 8 - Repeat. Please show all 4 lots corners with spot
elevations. Also please provide the flowline along Riverside - the spot elevationsare
there but the flowline itself is not.
[3/30/04] Repeat comment. Sheet 7 is still missing the corner of this project.
Please provide this information.
Page 2
6aSTAFF PROJECT REVIEW
City of Fort Collins
BHA DESIGN Date: 06/28/2004
JENNY TORREY
4803 INNOVATION DR
FT. COLLINS, CO 80525
Staff has reviewed your submittal for FORT COLLINS COLORADOAN PDP - TYPE
I (LUC) AND FINAL PLAN, and we offer the following comments:
ISSUES:
Department: Engineering Issue Contact: Susan Joy
Topic: General
Number: 15 Created: 1 /6/2004
[6/22/04] [3/30/04] Any easement being dedicated by separate document needs to
be labeled as being "dedicated by separate document" on the various plan sets.
Any existing easement needs to be labeled as "existing".
[2/23/04] Sheet 5 of the Utility Plans show a 6' easement, not 15'. The site and
landscape plans do not show or dimension the easement, please provide.
[1/6/04] A 15' utility easement is required along Riverside and must be dedicated by
separate document if not platting. Only 6' is currently shown.
Number: 17 Created: 1 /6/2004
[6/22/04]
[3/30/04] Any easement being dedicated by separate document needs to be labeled
as being "dedicated by separate document" on the various plan sets. Any existing
easement needs to be labeled as "existing".
[2/23/04] Sheet 5 of the Utility Plans show a 6' easement, not 15'. The site and
landscape plans do not show or dimension the easement, please provide.
[1/6/04] A 15' utility easement is required along Riverside and must be dedicated by
separate document if not platting. Only 6' is currently shown.
Number: 21 Created: 1 /6/2004
[6/22/04] There are still scanning issues. See comments under Site and
Landscape.
[3/30/04] Repeat comment. The utility and landscape plans are not scannable and
we will not approve them until they are. I would be happy to meet with you to
discuss appendix E6 or any other questions you have about scannability.
Page 1