HomeMy WebLinkAboutEASTGATE PDP - 10-04 - CORRESPONDENCE -[3/18/04] The offsite utility easement on the property to the south is for a private sanitary sewer SERVICE. This
easement should be granted to the Home Owners Associated for this 4-plex and NOT to the City. Please redraft the
utility easement to reflect this and provide a copy for our review. Proposed curb stop must be with in a UTILITY
easement. Please label the proposed drainage easement as a utility/drainage easement or move the curb stop and
meter pit toward the street in order to place the curb stop in the existing utility easement.
See site, landscape and utility plans for other comments.
Department: Zoning Issue Contact: Peter Barnes
Topic: Zoning
Number: 3 Created: 3/12/2004
[5/5/04] Zoning can't support the parking modification request. Their Plan B option shows one way to provide the
required parking without the need for a modification. There are other ways to configure the driveways that
wouldn't result in a continuous paved frontage. I believe it would be a bad precedent to grant this
modification.
[3/12/04] Seven parking spaces are required. The Land Use table on the site plan indicates that 8 parking spaces are
provided. However, I count only 4 legal spaces. I assume they are counting the driveway behind the garage as a
parking space. However, Section 3.2.2(13)(2), each parking space has to have unobstructed access to the street. In
other words, tandem parking (one space behind another) is not allowed. Therefore, they only have 4 parking spaces.
Redline drawings are available at the Current Planning front desk. Be sure and return all of
your redlined plans when you re -submit.
If you have any questions regarding these issues or any other issues related to this project,
please feel free to call me at (970) 221-6750.
Yours Truly,
Bob Barkeen
City Planner
Page 3
1997 UFC 901.4.4 NOTE: There shall be one(1) address for this building with individual unit numbers (1-4). The units
shall be identified on two sides - the street side and open space side.
Number: 6 Created: 3/15/2004
[5/13/041
[3/15/041 WATER SUPPLY: No commercial building can be greater then 300 feet from a fire hydrant. Fire
hydrants are required with a maximum spacing of 600 feet along an approved roadway. Each hydrant must be
capable of delivering 1500 gallons of water per minute at a residual pressure of 20 psi. 1997 UFC 901.2.2.2
Department: Police Issue Contact: Joseph Gerdom
Topic: Landscape Plan
Number: 39 Created: 5/11 /2004
[5/11/04] Given there is no auxiliary lighting, the choice of plant materials will have an impact on safety and security.
The walkways into the 4du are planted with CE, VT, and JP that will over grow the walk and create a very isolated path
- suggest smaller and fewer plants. Also, the spacing of some materials like the spruce and maple, don't meet
recommended spacing (scales 10' - center to center)
Department: Stormwater Utility
Topic: Drainage
Number: 35
[5/13/04] Repeat Comment
Issue Contact: Wes Lamarque
Created: 3/19/2004
A drainage easement is required for the existing outfall pipe from the detention pond to the right-of-way
Number: 36
[5/13/04] Repeat Comment
Created: 3/19/2004
A spillway needs to be designated and shown on the drainage plan, along with calculations in the report showing that
no buildings will be inundated in the 100-year storm if the inlet plugs. If an existing low area serves as a spillway
currently, than please designate this area on the plan and provide the calculations in the report.
Topic: Erosion/Sediment Control
Number: 42 Created: 5/13/2004
1. The plan still shows wattles on the concrete pans. I don't know what "use rock to secure wattle where wood
stakes cannot be driven" means.
2. Your project schedule is out of date. Instead of using specific months and a year dated across the top, simply
use Month 1, Month 2, Month 3, etc. That way, if the schedule gets moved back, the schedule will still apply
because it uses construction phases and estimated times, not specific dates.
Number: 53 Created: 5/13/2004
Please revise and update the drainage report. The detention volume provided is inconsistent between the two stage -
storage tables. The volume provided is not known for sure and can not be checked. The first table shows that there is
not enough volume in the pond.
Number: 54 Created: 5/13/2004
[5/13/04] The drainage report is inconsistent with the drainage plan. Please revise and make all data match.
Number: 55 Created: 5/13/2004
The detention requirement for quantity detention is around 16,300 CF, which was calculated in our office. The
intensities used to calculate the required detention in the report were not correct. Please revise.
Department: Water Wastewater Issue Contact: Jeff Hill
Topic: General
Number: 31 Created: 3/18/2004
[5/11 /04]
Page 2
'[J
STAFF PROJECT REVIEW
Citvof Fort Collins
HATTMAN ASSOC. Date: 05/14/2004
RIC HATTMAN
145 W. SWALLOW RD.
FT. COLLINS, CO 80525
Staff has reviewed your submittal for EASTGATE PDP - TYPE I (LUC), and we offer the
following comments:
ISSUES:
Department: Current Planning Issue Contact: Bob Barkeen
Topic: Site Plan
Number: 56 Created: 5/14/2004
[5/14/04] Please provide the alternative parking plan and site plan as discussed at the Wednesday morning staff
meeting.
Architectural details on the side of the building will need to be included as well.
Department: Engineering Issue Contact: Katie Moore
Topic: General
Number: 14 Created: 3/16/2004
[4/30/04] The letter of intent from the property owner to the south was received. Thank you. Please submit a copy of
the completed easement to the City when it is completed. This is required prior to mylars.
Original comment:
[3/16/04) Is the easement shown for the sewer line offsite an existing easement? If not, a letter of intent from the
adjacent property owner will be required prior to hearing, stating that they intend to grant an easement for this line after
the hearing. And prior to mylars being signed by the City, this easement will have to be complete.
Topic: Plat
Number: 8 Created: 3/16/2004
[4/30/04] There are still several typos that need to be corrected in the plat language.
Original comment:
[3/16/04] Please see redlined plat for changes needed to the plat language. Also, please see attached plat language.
Department: Light & Power
Topic: Electric
Number: 1
[4/30/041
Issue Contact: Doug Martine
Created: 3/5/2004
[3/5/04] Developer will need to coordinate electric development charges, and power and meter locations with Light &
Power (221-6700).
Department: Natural Resources
Topic: General
Number: 41
(5/12/04] No issues.
Department: PFA
Topic: General
Number: 5
[5/13/04]
Issue Contact: Doug Moore
Created: 5/12/2004
Issue Contact: Michael Chavez
Created: 3/15/2004
[3/15/04] ADDRESS NUMERALS: Address numerals shall be visible from the street fronting the property, and posted
with a minimum of 6 inch numerals on a contrasting background. (Bronze numerals on brown brick are not acceptable)