HomeMy WebLinkAboutCOLUMBINE EAST LONG TERM CARE - FDP - 11-05A - CORRESPONDENCE - REVISIONSPlease let us know if you have any other issues.
Sincerely:
Sandy McReron
Project Manager
V.F. Ripley Associates, Inc.
Fraser Walsh
Project Manager
TST, Inc. Consulting Engineers
Topic: Utility Plans
Number. 77 Created. 1012712005
[10127105] Please specify the riprap proposed to be buried.
Acknowledged.
Please add note to the storm sewer profiles indicating that the system is privately
owned and will be maintained by the property owner.
Acknowledged.
Detail D-10 was modified to include holes drilled into the plate. Please clarify why
was the detail modified, has the owner experienced icing problems with the
typical detail before ?
Yes, the client has had some problems with sidewalk chases icing up, particularly in
shady areas.
Department: Water Utilities Issue Contact: Roger Buffington
Topic: Utility Plans
Number. 70 Created. 1012612005
[10126105] There is an updated detail for 3- and 4-inch meter vaults. Please
provide an email address and we will forward it to you.
Acknowledged.
Number. 71 Created. 1012612005
[10126105] Correct the labeling of sizes and fittings on the water main as noted on
the plans.
Acknowledged.
Number: 72 Created: 1012612005
[10126105] Provide calculations for the restrained length each direction from the
3-inch 90-degree bend on the domestic water service and label on the plans.
Calculations were faxed to Roger Buffington, and callouts were added to util. plans.
Comments from Current Planning:
On the Lighting Plan, please specify that the wall -mounted fixtures labeled as
"CC" are "Full" cutoff. Also, please specify that the under -canopy fixtures
labeled as VD" are to be mounted with "Flush Mount and Flat Lens." Finally,
please add the quantity of each fixture.
The Lighting Plan has been updated.
Department: Transportation Planning Issue Contact: Kurt Ravenschlag
Topic: Transportation
Number. 53 Created. 511012005
[5110105] The intersection at Lemay Avenue and Rule Drive along the front of
your site indicates directional ramps, which are to standard, that align with radial
ramps to the south and west. This creates an awkward maneuver and could be
mitigated by moving the directional ramps closer together to reduce the offset
currently created.
Acknowledged. This was previously addressed.
Department: Water Utilities Issue Contact: Basil Hamdan
Topic: Detention Ponds
Number. 52 Created. 511012005
[101271051
[5110105] Please provide an overflow spillway detail and location for all proposed
detention ponds.
Details have been created.
Topic: Off -site easements
Number. 37 Created: 3/29/2005
[10125105] Please provide a copy of the separate document that would allow the
off -site construction of line ST-1.
[3129105] The construction of ST-1 will involve acquiring an off --site easement
from the owners of Tract A of Oakridge, if the area within Tract A where the work
is proposed is already a drainage easement, then approval from the owner of that
property should be secured.
Acknowledged.
Topic: Retaining Wall
Number., 38 Created. 312912005
[10125105] The provided details on the grading plan show top and bottom of wall
elevation, please specify material.
[5110105]
[3129105] At final, please provide a detail of the retaining wall being proposed in
the detention pond.
TOP and TOE elevations have been provided. A note on the grading plan specifies the
type of wall to be built and there is a cross-section detail in the detail sheets.
Topic: Sheet 2
Number. 67 Created. 1012512005
[10125105] Correct the spelling mistake in line 48 and add the other variance
requests (total of 4 were approved).
Spelling corrected and additional variances listed.
Topic: Sheet 6
Number: 62 Created: 1012512005
[10125105] Please add the street cut note:
Limits of street cut are approximate. Final limits are to be determined in the field
by the City Engineering Inspector. All repairs to be in accordance with City street
repair standards.
Note has been added.
Number. 63 Created: 1012512005
[10125105] Please label sections A -A and B-B as "Onsite'.
Sections are labeled.
Topic: Utility Plans
Number. 60 Created: 1012512005
[10125105] Please see JR in Technical Services regarding scanning requirements
and bring your plans with you so that you can go over them with him.
Acknowledged.
Number. 61 Created. 1012512005
[10125105] Construct the drive entrance off Rule Drive in accordance with detail
707.
Access has been shown concrete to the back of walk.
Number: 73 Created: 1012712005
[10127105] Please provide a legal and exhibit for the offsite 30' drainage easement
to be dedicated to the city. Once reviewed and approved, the actual dedication
statement will need to be completed prior to plan approval. The offsite temp
construction easement needs to be recorded at the county and a copy of the
recorded document has to be submitted to the city UNLESS stormwater is ok with
just a letter from the property owner stating that you have permission to
construct the drainage improvements. If Basil is ok with this, then I am too. Just
provide me a copy of the letter and get the original to Basil in Stormwater.
Acknowledged.
Topic: Landscape Plans
Number: 57 Created: 1012512005
[10125105] Please see JR in Technical Services regarding scannability
requirements.
TST met with JR and looked through plan set. Changes have been made where we
could to help with scanability. VF Ripley has made adjustments so that the scannibility
requirements are met.
Number. 58 Created. 1012512005
[10125105] Please show, label, and dimension all easements.
Labels and dimensions for the easements have been added to the landscape plan.
Topic: Plat
Number: 65 Created. 1012512005
[10125105] From Technical Services: Boundary and Legal close.
Acknowledged.
Number. 66 1Created. 1012512005
[10125105] From Technical Services: The NW corner of Section 6 exists. Need to
tie the survey to it.
Acknowledged.
Number. 68 Created. 1012512005
[10125105] Please spell out all abbreviations (esmt = easement).
Acknowledged.
Number. 75 Created. 1012712005
[10127105] From Technical Services: The boundary and legal close.
Acknowledged.
Number: 76 Created. 1012712005
[10127105] From Technical Services: The NW corner of Section 6 exists. You
need to tie/survey to it.
Acknowledged.
V F9RiPI4ey.sCCIATEs INC
Landscape Architecture Urban Design Planning
December 02, 2005
Mr. Ted Shepard
Fort Collins Planning Department
281 North College Avenue
Fort Collins, CO 80524
Columbine East Long Term Care - TYPE II
Response to staff Project Review comments
Dear Mr. Shepard,
We have reviewed the staff letter dated November 02, 2005 and have the following
comments. -
ITEM: 131-Bed Nursing Home at 4824 South Lemay Avenue (Rule Property —
northeast corner of Lemay Avenue and Rule Drive)
COMMENTS:
Department: Engineering Issue Contact: Susan Joy
Topic: Detail Sheets
Number: 64 Created: 1012512005
[10125105] Please remove the revised detail D10 and replace it with the City's
approved detail D10.
The City's approved detail DI was added to detail sheet. Sidewalk chases on private
property will utilize a modified D10, while chases in the public ROW will use the
standard D10. The plans note where each type of chase is to be used.
Topic: Elevations
Number. 59 Created: 1012512005
[10125105] Cool! l really like the 3D effect - it makes it easy to visualize the
project. Thanks.
Acknowledged.