HomeMy WebLinkAbout210-212 W. MAGNOLIA ST., URBAN LIVING LOFTS - PDP - 24-05 - CORRESPONDENCE -Number. 107 Created: 11 /15/2005 [11/15/05] See plans for other comments. Be sure and return all of your redlined plans when you re -submit. You will need to submit just two sets of plans --one for me and one for Roger Buffington. We will review and get back to you individually. Once Roger and I are satisfied that you have addressed our comments, you may proceed to mylars. The mylars won't be signed until the other comments are addressed. If you have any questions regarding these issues or any other issues related to this project, please feel free to call me at (970) 221-6750. Sincerely, Ine H. As n City Planner Page 4 This proposed building shall be fire sprinklered. 1997 UFC 1003.2.9 Number: 43 Created: 6/2/2005 [11/7/05] [7/26/05] [6/2/05] FIRE ALARM REQUIREMENTS: A fire alarm system is required for this proposed project. 1997 UFC 1007.2.9.1.1 Number: 44 Created: 6/2/2005 [11/7/05] [7/26/05] [6/2105] KNOX BOX: Poudre Fire Authority requires a "Knox Box" to be mounted on the front of every new building equipped with a required fire sprinkler system or fire alarm system. 1997 UFC 902.4; PFA POLICY 88-20 Number: 45 Created: 6/2/2005 [11/7/05] [7/26/05] [6/2105] STANDPIPE SYSTEM & FIRE PUMP: A standpipe system with a fire pump shall be required for this project. Department: Stormwater-Water-Wastewater Issue Contact: Wes Lamarque Topic: Drainage Number: 85 Created: 8/26/2005 [11/15/05] Need to receive off -site drainage easement for property to the west. [8/26/05] A letter of intent is required for the off -site work to the west of the property. Topic. ErosionfSediment Control Number: 108 Created: 11 /16/2005 [11/16/05] Please submit an erosion control plan/report per City requirements. Call Bob Zakely at 224-6063 if you have any questions. Department: Stormwater-Water-Wastewater Issue Contact: Roger Buffington Topic: General Number: 106 Created: 11 /15/2005 [11/15/05] Schedule meeting with me ASAP if there is any interest in possible cost participation by City in the 8-inch water main. Topic: Landscape Plan Number: 105 Created: 11 /15/2005 [11/15/05] Show water services in correct locations. Coordinate with utility plans. Topic: Utility Plan Number: 103 Created: 11 /15/2005 [11/15/05] Revise water main note on Sht 2 as shown. Number: 104 Created: 11 /15/2005 [11/15/05] Revise note on water main abandonment at Magnolia and Howes as shown. Page 3 [11/17/05] An "information for development agreements" sheet is attached which should be filled out in order for me to prepare a development agreement draft. Please note that this document and the easement document referenced in item 89 can be sent in electronic format if desired. Department: PFA Issue Contact: Michael Chavez Topic: General Number: 39 Created: 6/2/2005 [11/7/05] [7/26/05] [6/2/05] REQUIRED ACCESS: A fire lane is required. The fire lane shall be visible by painting and signage, and maintained unobstructed. 1997 UFC 901.2.2.1; 901.3; 901.4.2; 902.2.1; FCLUC The criteria for a required fire lane contain several conditions that must be met. 1. The minimum width shall be 20 feet. 2. Inside turning radius shall be 25 feet and outside turning radius shall be 50 feet. 3. Compacted road base shall be used during the construction phase only. The permanent fire lane shall consist of asphalt or concrete and shall be required to support 40 tons 4. The fire lane shall be platted as an "Emergency Access Easement" on the final plat. Buildings three stories or more in height must have access to a 30 foot unobstructed access roadway on at least (1) one side for aerial operations. PFA Policy 85-5 (B) Number: 40 Created: 6/2/2005 [11/7/05] [7/26/05] [6/2/05] PREMISES IDENTIFICATION: Approved numerals or addresses shall be provided for all new and existing building in such a position as to be plainly visible and legible from the street or road fronting the property. 1997 UFC 901.4.4 A. In Multi -story buildings the following requirements shall pertain. 1. The first floor units shall be designated with 100's. 2. The second floor units with 200's 3. The third floor units with 300's, and so forth. B. All brass letters and numerals shall be posted on a black background. C. Some multi -family layouts may require address postings from the back side as well as the front of the buildings. D. A clockwise addressing pattern shall be maintained when ever possible. Number: 41 Created: 6/2/2005 [11/7/05] [7/26/05] [6/2/05] WATER SUPPLY: Commercial No commercial building can be greater then 300 feet from a fire hydrant. Fire hydrants are required with a maximum spacing of 600 feet along an approved roadway. Each hydrant must be capable of delivering 1500 gallons of water per minute at a residual pressure of 20 psi. 1997 UFC 901.2.2.2 Number: 42 Created: 6/2/2005 (11/7/05] [7/26/05] [6/2/05] SPRINKLER REQUIREMENTS: Page 2 STAFF PROJECT REVIEW City of Fort Collins ALAN STROPE Date: 11/22/2005 3201 E MULBERRY ST. SUITE B FORT COLLINS, CO 80524 Staff has reviewed your submittal for 210-212 W. MAGNOLIA ST., URBAN LIVING LOFTS AT MAGNOLIA ST. PDP, TYPE I, and we offer the following comments: ISSUES: Department: Current Planning Issue Contact: Anne Aspen Topic: Cover Sheet Number: 109 Created: 11 /16/2005 [11/16/05] Yet again, the parking numbers do not add up correctly. Also, these numbers need to be exactly what your modification approved. See redlines for detail. You should note the modification. Number: 110 Created: 11 /16/2005 The project address is not legible anywhere on the cover sheet. Please rectify. Topic: Elevations Number. 114 Created: 11/22/2005 [11/22/05] There continue to be scanability issues with the elevations and shadow analysis. If you have questions, please contact J.R. Wilson in the Technical Services Department of Engineering. You can reach him at 221-6605. Topic: General Number: 96 Created: 8/31/2005 [11/22/05] The utilities are now on the cover sheet. They need to be on the LANDSCAPE plan. [8/31/05] Clearly identify water and sewer lines on the landscape plan. Topic: Photometrics Number: 113 Created: 11/22/2005 [11/22/05] 1 did not receive revised photometrics to review. Please submit. Topic: Site Plan Number: 112 Created: 11/22/2005 [11/22/05] See redlines for minor comments. Department: Engineering Issue Contact: Marc Virata Topic: General Number: 89 Created: 8/26/2005 (11/17/05] The actual easement deed of dedication will be required prior to or in conjunction with mylars for signature. Deed of dedication document templates are attached for use. [8/26/05] A letter of intent is required from the Edwards (property owners to the west) for offite work shown on their property. Number: 111 Created: 11 /17/2005 Page 1