HomeMy WebLinkAboutVERIZON WIRELESS FTC DRAKE CROSSING - PDP/FDP - FDP130032 - CORRESPONDENCE -Comment Numbb Comment Originated: 08/21/2013 08/21/2013: EMERGENCY GENERATOR The storage and use of diesel fuel, in conjunction with the diesel generator, shall comply with any applicable sections of Chapter 34 of the International Fire Code on Flammable and Combustible Liquids. The equipment shelter housing the generator shall be property signed and labeled. Department: Stormwater Engineering Contact: Jesse Schism, 970.218.2932, jschiam(a)fcoov.com Topic: Erosion Control Comment Number: 1 Comment Originated: 08/01/2013 08/01/2013: No Comment from Erosion Control. This site; disturbs less than 10,000 sq-ft, is not in a sensitive area, and is not in a larger development under construction. Therefore, no submittal of erosion control material is needed. However, the site still must still be swept and maintained to prevent dirt and other pollutants from entering the stone sewer or else BMPs will be required of the site. If you need clarification concerning this, or if there are any questions please contact Jesse Schlam 970-218-2932 or email @ jschlam@fcgov.com Contact: Wes Lamarque, 970.416.2418, wlamaraue(a'lfcoov.com Topic: General Comment Number: 2 08/19/2013: No comments. Department: Technical Services Contact: Jeff County, 970.221.6588, icountv(e)fcoov.com Topic: General Comment Originated: 08/19/2013 Comment Number: 1 Comment Originated: 08/07/2013 08/07/2013: Please rotate the text marked on sheet A1.0, 180 degrees so it is read from the right side of the sheet. See redlines. Comment Number: 2 Comment Originated: 08/07/2013 0810712013: There is one line over text issue on sheet A3.0. See redlines. Department: Water -Wastewater Engineering Contact: Roger Buffington, 970.221.6854, rbuffinaton(Mcgov.com Topic: Site Plan Comment Number: 1 Comment Originated: 08/22/2013 08/22/2013: Show existing water service, meter pit and fire line on the site plan. Page 3of3 T— Contact: Andrew Gingerich, 221.6603, aninnerichAfcoov.com Topic: General Comment Number: 1 Comment Originated: 08/20/2013 08/20/2013: From the plat of the Drake Crossing Center 2nd Filing it appears that there is a building envelope surrounded by a blanket access and utility easement. Measuring from the plat and aerials it appears that the new structure may just barely fit within the existing building envelope and potentially encroach into the easement by 1- 2 feet. Please provide information confirming that the structure will fit within the building envelope, otherwise we may need to proceed with vacating a small portion of the blanket easement. Comment Number: 2 Comment Originated: 08/20/2013 08/20/2013: An excavation permit will be required for any work within the right of way for tying in communication lines. Comment Number: 3 Comment Originated: 08/20/2013 08/20/2013: Any damaged curb, gutter and sidewalk existing prior to construction, as well as streets, sidewalks, curbs and gutters, destroyed, damaged or removed due to construction of this project, shall be replaced or restored to City of Fort Collins standards at the Developers expense prior to the acceptance of completed improvements and/or prior to the issuance of the first Certificate of Occupancy. Department: Environmental Planning Contact: Lindsay Ex, 970.224.6143, lex0fcaov.com Topic: General Comment Number: 1 08/1312013: No comments. Department: Light And Power Contact: Rob Irish, 970-224-6167, ridsh(a)fcoov.com Topic: General Comment Originated: 08/13/2013 Comment Number. 1 Comment Originated: 08/14/2013 O8/14/2013: Existing transformer is a 500KVA 120/208v 3-phase. Any relocation or modification to the existing electric facilities will incur system modification charges. Comment Number: 2 Comment Originated: 08/14/2013 08/14/2013: A C-1 form and One -line diagram will need to be submitted to Light & Power Engineering showing power requirements. Comment Number: 3 Comment Originated: 08/14/2013 08/1412013: Owner will be responsible for Electric Capacity Fee and Building Site charges. Contact Light & Power Engineering @ 970-221-6700. Department: PFA Contact: Jim Lynxwiler, 970.416.2869, ilynxwiler0poudre-fire.oro Topic: General Page 2 of 3 Fort Collins August 23, 2013 Irene Cooke Closser Consulting LLC P.O. Box 423 Tabemash, CO 80478 RE: Verizon Wireless FTC Drake Crossing, FDP130032, Round Number 1 Community Development and Neighborhood Services 281 North College Avenue PO eox 580 Fort Collins, CO 80522 970.221.6760 970.224.6134 - fax lcgov. com/developmentreview Please see the following summary of comments from City staff and outside reviewing agencies for your submittal of the above referenced project. If you have questions about any comments, you may contact the individual commenter or direct your questions through the Project Planner, Noah Beals, at 970-416-2313 or nbeals@fcgov.com. Comment Summary: Department: Current Planning Contact: Noah Beals, 970.416•2313, nbealsl�fcaov.com Topic: General Comment Number: 1 Comment Originated: 08/19/2013 08/22/2013: Applicant pointed out where this information has already been provided. No further action is needed for this comment. 08/19/2013: Land Use Code (LUC) 3.8.13(C)(3) Roof monted equipment shall be located as far away as possible for the roofs edge as possible. Please explain the proposed location and why it is as far away from the roof edge as possible. Comment Number: 2 Comment Originated: 08/19/2013 08/19/2013: LUC 3.18.13(C)(4) Along with the relocation of the two shurbs and one tree. Additional landscaping should be added North of the equipment shelter. Comment Number: 3 Comment Originated: 08/19/2013 08/19/2013: LUC 3.18.13(C)(3) What is the cable tray made of? It should resemble a brick column to blend better with the buildng. Comment Number: 4 Comment Originated: 08/19/2013 08/19/2013: LUC 3.18.13(B) The applicant has explained why co -locations was not possible in current near by locations. But please provide information how the current proposal will allow for co -location. Comment Number: 5 08/19/2013: Remove the word future from plans. Department: Engineering Development Review Comment Originated: 08/19/2013 Page 1 of 3