HomeMy WebLinkAboutHELLENIC PLAZA (635 S. SHIELDS ST.) - PDP - 30-05A - CORRESPONDENCE - (8)[5/2/07] Repeat Comment -The comment below can be addressed with an informal
meeting at City Utilities.
[3/16/07] After the amount of detention volume is agreed upon, the grading plan
reviewed to show this volume is achievable, offsite flows shown to safely pass
through the site, PDP can go to a hearing.
Number: 88 Created: 5/2/2007
[5/2/07] The detention pond needs to have some freeboard. This can be discussed
at Final Compliance.
Department: Stormwater-Water-Wastewaterlssue Contact: Roger Buffington
Topic: WaterMastewater
Number: 58 Created: 3/13/2007
[5/2/07]
[3/13/07] Provide water service sizing calc's for the residential service for review.
Number: 87 Created: 5/2/2007
[5/2/07] Add to the note on the 1.5" water service on Shields indicating that that it is
for commercial water service.
Department: Zoning Issue Contact: Gary Lopez
Topic: Zoning
Number: 91 Created: 5/2/2007
[5/2/07] Issues resolved ok
Be sure and return all of your redlined plans when you re -submit
If you have any questions regarding these issues or any other issues related to this
project, please feel free to call me at (970) 221-6750.
Sincerely,
O t & w'*e
Shelby Sommer
Associate City Planner
Page 5
Number: 85 Created: 4/26/2007
-[4/26/07]—Please submit a revised plan for any scheduled hearings. Thank you.
Topic: Tech. Services
Number: 89 Created: 5/2/2007
[5/2/07] Many line over text conflicts on the Site and Landscape Plans. Please see
redlines for clarification and correct with final plan submittal.
Department: Light & Power Issue Contact: Doug Martine
Topic: Electric Utility
Number: 73 Created: 4/24/2007
[4/24/07] The developer will need to coordinate power requirements by providing a
completed Commercial Service (C-1) form to Light & Power Engineering. The reply
comments to the previous round of City staff comments indicated that the form was
— --attached=to=the=resubmittal. The -form was not included in the Light & Power packet
for the resubmittal.
Department: PFA Issue Contact: Carle Dann
Topic: Fire
Number: 90 Created: 5/2/2007
[5/2/07] STREET ADDRESSING: Please note that PFA is emphasizing consistency
in addressing. Future projects shall comply with International Fire Code and PFA
policy, which require that buildings be addressed off the street that provides access
to the site. In the future, a project such as this will receive a Birch Street address,
which is the actual, accurate street that provides access onto the site. The two lots in
this project at one time had Shields Street access; however, the development is
starting from scratch, the property is being redeveloped, and access is not off
Shields Street. PFA's emphasis on consistent addressing requirements ensures
accurate, clear addressing, which enables PFA to provide emergency services as
expeditiously as possible.
Department: Transportation Planning Issue Contact: David Averill
Topic: Engineering
Number: 56 Created: 3/13/2007
[5/4/07] 1 think the crossing of the drive aisle/exit might need to be slightly
reconfigured for pedestrian safety. We will need to discuss this at final compliance.
Department: Stormwater-Water-Wastewaterlssue Contact: Wes Lamarque
Topic: Stormwater
Number: 69 Created: 3/15/2007
[5/2/07] Reminder Comment
[3/15/07] A drainage easement is required for the limits of the detention area.
Number: 71
Created: 3/16/2007
Page 4
[3/13/07] You will need to submit a construction cost estimate for the Coy Street
ultimate design for the frontage obligation. This cost will be collected as a cash in
- ---- lieu payment -and -provided -in -the -development -agreement..------ -
Number: 54 Created: 3/13/2007
[4/26/07] Please pay with final plan review $1,081.75. Thank you.
[3/13/07] The PDP submittal review fee was not calculated correctly. An additional
$81.75 is due. Please submit this payment prior going to hearing.
Number: 64 Created: 3/13/2007
[4/26/07] Field meeting resulted in approval of 6 foot wide attached walk along Birch
... matches sidewalk on south side of street.
[3/13/07] The sidewalk on Birch does not meet LCUASS standards for local
residential streets. Minimum 6 foot parkway and 4.5 foot detached sidewalk.
_— .Number:_65 __- - -- - ---C-reated:3/_13/2007-
[4/26/07] Please show cross slope at cross walk on Shields Street access and
provide a cross section or adequate elevation data on the plan to verify that a
monolithic pan will be poured to carry flows south along Shields with a minimum of
0.5 percent fall.
[3/13/07] Please calculate and show the cross slope on the access to Shields at the
cross walk. 2% is the maximum cross slope allowed under ADA guidelines.
Number: 81 Created: 4/26/2007
[4/26/07] The Plat is showing an existing 10 foot wide ditch easement running east -
west from Shields Street. If you wish to vacate this easement by the Plat, the ditch
owner will need to sign the final plat and a standard vacation note must be added to
the plat. You may also record a termination of easement by separate document
signed by the ditch owner. Either way, the City will need at a minimum, a letter of
intent from the ditch owner stating that the ditch easement is no longer needed or
desired. This must be resolved prior to scheduling a hearing for the project.
Number: 82 Created: 4/26/2007
[4/26/07] Please provide addition spot - flowline elevation data at the Shields access
to show drainage being conveyed at 0.5 percent min. in a monolithically poured pan.
You can also provide a simple cross section at this location to show how this is to be
constructed.
Number: 83 Created: 4/26/2007
[4/26/07] Please extend arrows from standard street cut note to all areas in the
ROW with proposed street cuts (access points)
Number: 84 Created: 4/26/2007
[4/26/07] The north and south flow line sag curves for the Coy Street design do not
meet LCUASS standards. Minimum K values must be 30 or greater. Lengthening the
vertical curve should solve the problem. See LCUASS Table 7-3.
Page 3
in the same locations as the lights, and when those trees mature they will most likely
impact the lighting levels. This is not a requirement, but definitely something to
consider. --
Topic: Shadow Analysis
Number: 72 Created: 4/20/2007
[4/20/07] The shadow analysis is incorrectly labeled as the landscape plan.
Number: 86 Created: 4/30/2007
[4/30/07] (Please address before hearing) The shadow analysis looks good - thanks
for providing this. The visual analysis is on the right track but still needs some work
before the hearing ... the photos are great, but please refer to Section 3.5.1(G)(1)(b)
for specific information to include in the visual analysis. At a minimum you- need a
visual analysis that:
_a. identifies the -extent to. which existing views_ may be-blocked;--
b. depicts in graphic form views before and after the project, utilizing
photographs of the area and neutral drawings derived from at least two (2)
points from which the proposal will be commonly viewed, one (1) of which
should be a vista towards the foothills; and
c. indicates these points of observation on an inset map or plan of the area; and
d. a summary of the key conclusions of the shadow and visual analysis, and
steps to be taken to comply with the review standards set forth above.
Topic: Site Plan
Number: 78 Created: 4/25/2007
[4/25/07] The small text for the legal description probably won't scan well. You'll
also need a vicinity map on the site plan. You may want to consider doing a
separate cover page for the site plan and include all of the signature blocks, land
use statistics, vicinity map and legal description on it, and it might give the site plan a
little room to "breathe." A total of the land use statistics (NCB and MMN) would be
helpful as well.
Number: 79 Created: 4/25/2007
[4/25/07] Please see redlines for additional comments/typos on the site plan.
Department: Engineering Issue Contact: Randy Maizland
Topic: Engineering
Number: 35 Created: 3/13/2007
[4/26/07] Carry over comment. Design looks good, please prepare and submit local
portion cost estimate for review.
Page 2
r
f�
�i STAFF PROJECT REVIEW
City of Fort Collins
Don Brookshire Date: 05/04/2007
Eastpoint Studio, LLC
552 Kinnikinnik Ct.
Windsor, CO 80550
Staff has reviewed your submittal for HELLENIC PLAZA PDP (635 S. SHIELDS ST.)
- TYPE I, and we offer the following comments:
ISSUES:
Department: Current Planning Issue Contact: Shelby Sommer
Topic: Building Elevations
Number: 80 Created: 4/25/2007
[_4/25/07]_Please-use_a.different-font-or-font size -for the dimensions -on -the -building - -
elevations. It's a bit difficult to read now and I don't think it will scan clearly later.
Topic: Landscape plan
Number: 27 Created: 3/8/2007
[4/25/07] (Please Address Before Hearing) It is still unclear on the plans what
landscaping is existing (if any) on the neighboring property's landscape setback
area. Will you maintain this with this project?
[3/8/07] Minimum width of any landscape setback area along a lot line is 5 feet.
Please address this issue along the western property line by providing more
information about what is existing on the adjacent property and/or a modification of
standards request.
Number: 74 Created: 4/25/2007
[4/25/07] (Please address before Hearing) Per LUC section 3.2.1(E)(5) landscape
islands with a tree must be 8 feet in its smallest dimension. This is a problem for the
landscape island area highlighted on the landscape plan. Can you shift that entire
row of parking to the west 3 feet to satisfy this standard?
Number: 75 Created: 4/25/2007
[4/25/07] (Please address before Hearing) The comment response letter states that
11 of the trees will be up -sized to mitigate the loss of existing trees. It is unclear on
the landscape plan which 11 trees are specified for up -sizing.
Number: 76 Created: 4/25/2007
[4/25/07] Since many of the existing trees will be preserved, please add tree
protection notes (LUC Section 3.2.1(G) to the Landscape Plan).
Number: 77 Created: 4/25/2007
[4/25/07] (Please address before Hearing) You may want to show the proposed
lighting fixtures on the site and/or landscape plan. Several of the proposed trees are
Page 1