HomeMy WebLinkAboutFIRST COMMUNITY BANK PLAZA - FDP - 49-05/A - CORRESPONDENCE -Number: 65 Created: 3/8/2006
[3/8/06] Will a separate irrigation tap be needed?
Comment from Current Planning:
1. The spacing of street trees along J.F.K. now accounts for the two existing street
lights. Please investigate adding ornamental trees in the 80-foot gap between
street trees at the southern street light and to the north of the northern street
light. Keep in mind that ornamental trees are allowed to be setback from street
lights by only 15 feet.
2. Please indicate in the General Notes or on the Site Plan exactly where the
walk-up A.T.M. is located.
3. Is there any shade structure, trellis, canopy, etc. for the benefit of the drive -
through facilities? If so, please provide a character sketch or illustrative
depiction of what this looks like. The materials and color should neutral in tone
so as to not detract from the building. The Lighting Plan indicates that there are
to be recessed fixtures illuminating this area. What are these fixtures recessed
into?
4. Please indicate that any lighting associated with such structure shall be fully
shielded so the light source is not visible by expanding General Note Number 5.
Be sure and return all of your redlined plans when you re -submit.
If you have any questions regarding these issues or any other issues related to this
project, please feel free to call me at (970) 221-6750.
Sincerely:
Ted Shepard
Chief Planner
Page 4
[2/16/06] KNOX BOX: Poudre Fire Authority requires a Knox Box to be mounted on
the front of every new building equipped with a required, automatic fire -sprinkler
system.
Number: 60 Created: 3/8/2006
[3/8/06] This building must be equipped with a fire -alarm system.
Number: 61 Created: 3/8/2006
[3/8/06] The Emergency Access Easement shall continue north and east until it
intersects with the public street, or provide a turn -around on your property. Minimum
width of the EAE for this section is 20 feet.
Number: 62 Created: 3/8/2006
[3/8/06] Fire Department Connection shall be on the north side of the bank building.
Department: Transportation Planning Issue Contact: Kurt Ravenschlag
Topic: Stormwater
Number: 59 Created: 3/7/2006
[3/7/06] Please dedicate trail connection to the west in a Public Access Easement.
Department: Stormwater-Water-Wastewaterissue Contact: Roger Buffington
Topic: Landscape Plan
Number: 19 Created: 12/13/2005
[3/8/06]
[12/13/05] Maintain separation distances between trees and water/sewer lines.
Department: Stormwater-Water-Wastewaterissue Contact: Wes Lamarque
Topic: Stormwater
Number: 56 Created: 3/6/2006
[3/6/06] Please provide drainage easements for the main storm sewers that carry
the 100-year flows to the detention ponds. Roof drain pipes do not need easements.
Number: 57 Created: 3/6/2006
[3/6/06] Please provide 10-feet of clearance between storm sewers and large trees.
Ornamentals can be closer.
Department: Stormwater-Water-Wastewaterissue Contact: Roger Buffington
Topic: Water/WW
Number: 63 Created: 3/8/2006
[3/8/06] Meter pit detail has been updated. Include new detail.
Number: 64 Created: 3/8/2006
[3/8/06] Provide note on removal of 4-inch service from manhole and replacement
with the 6-inch sewer service. ( ...something like " Remove 4-inch sewer service
from manhole, and grout 6-inch service in opening with non -shrink grout. Re -shape
MH bench/invert as needed to direct flow.")
Page 3
1. Legal closes, Boundary closes using measured info, record doesn't close. Record
info doesn't match the legal.
2. Basis of bearing note doesn't match the legal.
3. Subtitle needs to include "being a replat of a portion of Lot 2 Observatory Heights.
Department: Natural Resources Issue Contact: Doug Moore
Topic: Zoning
Number: 40 Created: 2/13/2006
[2/13/06] No remaining issues. Nice job of the landscape plan!
Department: PFA
Topic: fire
Number: 41
[2/16/06] AUTOMATIC SPRINKLERS:
automatic fire sprinklers.
Issue Contact: Carie Dann
Created: 2/16/2006
This building shall be equipped with
Number: 42 Created: 2/16/2006
[2/16/06] STANDPIPE/FIRE PUMP: This building is required to be equipped with an
approved standpipe system and fire pump, capable of providing a minimum of 100
psi at the highest level of the building.
Number: 43 Created: 2/16/2006
[2/16/06) WATER SUPPLY: Minimum water supply shall be 1,500 gallons per
minute at 20 psi residual pressure, spaced not farther than 300 feet from the
building, on 600-foot centers thereafter.
Number: 44 Created: 2/16/2006
[2/16/06] EMERGENCY ACCESS: A fire lane is required. It shall be visible by
painting and signage, and maintained unobstructed. Minimum width is 30 feet on at
least one of the long sides of the building, and 20 feet on the shorter sides.
Number: 45 Created: 2/16/2006
[2/16/06] SMOKE -REMOVAL: The atrium shall have an approved smoke -removal
system.
Number: 46 Created: 2/16/2006
[2/16/06] TURNING RADII: Minimum turning radii in the parking lot is 25 feet inside,
50 feet outside. '
Number: 47 Created: 2/16/2006
[2/16/06] ADDRESS: Address numerals shall be visible from the street fronting the
property, and posted with a minimum six-inch numerals on a contrasting
background.
Number: 48 Created: 2/16/2006
Page 2
STAFF PROJECT REVIEW
City of Fart Collins
VF RIPLEY ASSOCIATES Date: 03/10/2006
SANDY MCFERON
401 WEST MOUNTAIN AVENUE, SUITE 201
FORT COLLINS, CO 80521
Staff has reviewed your submittal for FIRST COMMUNITY BANK PLAZA PDP AND
FINAL PLANS, and we offer the following comments:
ISSUES:
Department: Engineering Issue Contact: Dan DeLaughter
Topic: General
Number: 49 Created: 3/2/2006
[3/2/06] Change the approved variance note on Sheet 2. The approved variance
was for a 70' setback, down from 100', not 50' down from 75'.
Number: 51 Created: 3/2/2006
[3/2/06] The proposed street cut on JFK will need to include the gas service
connection. Please revise the limits of construction.
Number: 52 1Created: 3/2/2006
[3/2/06] Provide text boxes where hatching obscures text.
Number: 53 Created: 3/2/2006
[3/2/06] Signature boxes are missing on several detail sheets.
Number: 54 Created: 3/2/2006
[3/2/06] There is no detail for the retaining walls other than what is shown with the
outlet structure details.
Number: 55 Created: 3/2/2006
[312/06] Change the scales and dimensions on detail sheets to engineering style.
Number: 58 Created: 3/7/2006
[3/7/06] Show dimensions of cover over rebar for bridge sections.
Topic: Plat
Number: 67 Created: 3/8/2006
[3/8/06] Put the full company name on the plat. When will the transfer of the
property occur? Owner/developer must be current at the time the DA and plat are
signed.
Topic: Technical Services
Number: 66 Created: 3/8/2006
[3/8/06] Tech. Services Comments:
Page 1