HomeMy WebLinkAbout4900 SOUTH COLLEGE AVENUE FDP, CHANGE OF USE - 3-06/A - SUBMITTAL DOCUMENTS - ROUND 1 - REVISIONS[2/28/06] Hydrant spacing and water flow must meet minimum requirements based on type of
occupancy. Spacing and flow requirements for commercial property are 1,500 gpm at 20 psi
residual pressure, spaced not further than 300 feet to the building, on 600-foot centers
thereafter.
Department: Transportation Planning
Topic: General
Number: 51
[4/19/06) No further comments.
Issue Contact: Kurt Ravenschlag
Created: 4/19/2006
Department: Stormwater-Water-Wastewater Issue Contact: Basil Harridan
Topic: Stormwater
Number: 38 Created: 3/1 /2006
[4/17/06] The provided water quality outlet detail needs to be revised.
As currently shown, the water quality pond will hold water up to 2 inches deep before it
releases. Please make sure that the plate has an opening at the invert elevation of the pond.
According to Urban Drainage criteria, rows need to be separated by 4 " in order to use that
manual's charts.
If no utility plans are being submitted, then how will the change to the pond outlet be
documented. Maybe a note on the site plans referencing the drainage design documents would
be appropriate.
Note added to plan referencing the revised drainage design documents prepared by
Terry Everett of Northern Engineering.
[3/1/06] The original detention area did not have a water quality component. Since the pond is
already built and landscaped, no new detention will be required, however, it is requested that
the pond outlet, be modified to include a water quality plate and detention. A variance will be
approved to account for the water quality volume as being part of the quantity volume.
Please provide water quality calculations.
Thank you for you time and consideration during this process.
Sincerely,
Uq �06
Amy Lopp
VF Ripley Associates, Inc.
4
4 Rip11ey.SOC)ATE5 INC
f Lanpsccpc- Arenilcciure Urban Design planning
May 18, 2006
Shelby Sommer
City of Fort Collins
Planning Department
281 North College Avenue
Fort Collins, CO 80522
RE: 4900 South College Round 2 Comments
Dear Shelby:
The following is our response to Round #2 Staff Comments received on April 24,2006.
Department: Current Planning Issue Contact: Shelby Sommer
Topic: General
Number: 49 Created: 4/17/2006
[4/17/06] Is any additional lighting proposed? If so, please indicate where and what type. See
lighting standards in LUC Section 3.2.4. If not, please place a note indicating such on the site
plan.
No additional lighting is proposed and a note has been added to the Land Use Notes
section on the Site/Landscape Plan.
Department: Engineering Issue Contact: Susan Joy
Topic: Easement Dedications
Number: 45 Created: 4/7/2006
[4/7/06] The 20' access easement dedication was incorrectly submitted and needs to be
resubmitted using the UNALTERED City template. The exhibit and legals for this easement
were checked and accepted. OK to submit signed and wetstamped docs from the surveyor
along with a $250 filing fee made out to the City of Fort Collins. Larimer County filing fees also
apply and that amount will be calculated once all the paperwork is received.
Easement Dedication coordinated between Todd Rogers (client's attorney) and City
Attorney. Revised Easement Dedication included with this submittal.
Topic: General
Number: 15 Created: 2/28/2006
[4/5/06] Just keeping this comment in for coordination and papertrail.
[2/28/06] The City will not require any upgrades to the existing sidewalk along either the
frontage road or Fairway. This project will only have to replace and/replace any existing
damaged curb, gutter, ramp and/or sidewalk.
Number: 16 Created: 2/28/2006