Please add a note to the grading plan indicating that existing grading on the homes
to the south of the school will not be disturbed during construction operations.
Topic: Stormwater- Offsite flows
Number: 9 Created: 10/24/2006
[10/24/06] Please show that the overflows from the inlets located to the west of this
development will be safely routed around the proposed building without causing any
damages.
An analysis section should be added to the; drainage report discussing how any
potential overflows will be handled:by the proposed:swale around the buildings.
Topic: Stormwater- Plat
Number: 10 Created: 10/24/2006
[10/24/06] Are the existing overflow easements being vacated? If not than dedicate
a new drainage easement for the new overflow path.
Topic: Stormwater- Utility Plans
Number: 11 Created: 10/24/2006
[10/24/06] Please call out all proposed storm sewer sizes and types on the utility
plans.
Please provide a detail for the proposed veined grate proposed for the type 13 inlet
as well as a detail for the sidewalk chase with metal grate.
Grading plans and utility plans do not agree. Grading plans do not reflect the
proposed inlets and pipes that are tied to the existing lines. Please modify grading
plans to match utility plans.
Please label all existing easements.
Topic: Stormwater- Water Quality
Number: 7 Created: 10/24/2006
[10/24/06] Please discuss how water quality is handled on this site. Discuss in the
report how the 3rd filing of Ridgewood Hills.has accounted for this development area
in their water quality detention.
Department: Zoning Issue Contact: Gary Lopez
Topic: Zoning
Number: 5 Created: 10/23/2006
[10/23/061 No Comment
Be sure and return all of your redlined plans when you re -submit.
If you have any questions regarding these issues,or any other issues related to this
project, please feel free to call me at (970) 221-6750.
Page 8
[10/31/06] OCCUPANT -LOAD SIGN: Any room having an occupant load of 50 or
more where fixed seats are not installed, and which is used for assembly purposes,
shall have the capacity of the room posted in a conspicuous place on an approved
sign near the main exit from the room. Such sign shall be maintained legible by the
owner or the owners authorized agent and shall indicate the number of occupants
permitted for each room use. 97UFC 2601.16.1
Number: 46 Created: 10/31 /2006
[10/31/06] COMMERCIAL COOKING FIRE EXTINGUISHING SYSTEM: With the
production of grease -laden vapors, an approved, automatic fire -extinguishing system
shall be provided for the protection of commercial -type cooking equipment. 97UFC
1006.1; 1006.2.1
Number: 47 Created: 11 /1 /2006
[11/1/06] FIRE LANE: PFA requires a fire lane throughout the entire main, U-
shaped drive aisle off Avondale Road, and also the drive on the north side of the
school (for buses). This fire lane shall be visible by painting and signage, and
maintained unobstructed at all times. 97UFC.901.2.2.1; 901.3; 901.4.2-1 902.2.1
Department: Traffic Operations Issue Contact: Eric.Bracke
Topic: Traffic - 1
11
Number: 15 Created: 10/27/2006
[10/27/06) The drop off and pick up area seems a bit short albeit typical for most
schools. I would like to see a "safe route to school plan" in place prior to
construction. It would also be helpful to sit down with the school district and come
to consensus on how the circulation is going to work and what type of signing and
striping will be required and who is going to pay.
Department: Stormwater-Water-Wastewaterlssue Contact: Basil Hamdan
Topic: Stormwater- Drainage Flows
Number: 8 Created: 10/24/2006
[10/24/06] Please discuss in the report what the assumed flows from this site were
in the Ridgewood Hills 3rd Filing drainage study and compare to flows that were
calculated based on proposed impervious areas in this drainage report.
Topic: Stormwater- Grading Plans
Number: 12 Created: 10/24/2006
[10/24/06] The area to the west of the school site will need to be regraded in order
to eliminate the low point in the existing overflow swale, please show how that area
will be regraded. If that area is owned by the Ridgewood Hills HOA approval from
that HOA will be required.
The existing storm manhole is located within the new driveway entrance to the north,
please clarify on the plans how the existing manhole will be modified to match the
revised grading.
Page 7
the building to the interceptor looks to be in the same location as the transformer
pad. This would not be acceptable. Please take a look at this.
Number: 14 Created: 10/26/2006
[10/26/06] The square footage & front footage charge for this site have already been
paid. Developer will be responsible for paying KVA charges and Building Site
charges.
Department: PFA Issue Contact: Carle Dann
Topic: Fire
Number: 39 Created: 10/31/2006
[10/31/06] FIXED FIRE PROTECTION: This structure shall be equipped with an
approved, automatic fire -extinguishing system and smoke detectors that tie in to the
fire -alarm system, per 1997 UFC requirements for Group E occupancies.
Number: 40 Created: 10/31/2006
[10/31/06] WATER SUPPLY: Fire hydrants, where required, must be the type
approved by the water district having jurisdiction and the Fire Department. Hydrant
spacing and water flow must meet minimum requirements based on type of
occupancy. Spacing and flow requirements include: Commercial, 1,500 gpm at 20
psi residual pressure, spaced not further than 300 feet to the building, on 600-foot
centers thereafter. 97UFC 901.2.2.2
Number: 41 Created: 10/31/2006
[10/31/06] ADDRESS NUMERALS: Address numerals shall be visible from the
street fronting the property, and posted with a minimum of six-inch (6) numerals on a
contrasting background. (Bronze numerals on.brown brick are not
acceptable).97UFC 901.4.4
Number:42 Created: 10/31/2006 '
[10/31/06] FIRE DEPARTMENT CONNECTION: Fire department connections shall
be installed remote from the buildings, and located on the street or fire lane side of
buildings, fully visible and recognizable from the street or nearest point of fire
department vehicle access or as otherwise approved by the fire code official.
Number: 43 Created: 10/31/2006
[10/31/06] FIRE LINE: The fire line supporting the automatic fire -sprinkler system
shall be a minimum 6-inch line, unless hydraulic calculations can support a reduced -
size line.
Number: 44 Created: 10/31/2006
[10/31/06] KNOX BOX REQUIRED: Poudre Fire Authority requires a "Knox Box" to
be mounted on the front of every new building equipped with a required fire sprinkler
system or fire alarm system. 97UFC902.4; PFA BUREAU POLICY 88-20
Number: 45
Created: 10/31/2006
Page 6
[10/30/06] Show and dimension all easements (existing and proposed).
Number: 32 Created: 10/30/2006
[10/30/06] Dimension all sidewalks, drive aisles, parking stalls (width and length),
parkways, etc.
Topic: Transportation Planning
Number: 53 Created: 11/3/2006
[11/3/06] From David Averill:
1. Proposed bike parking location doesn't make a whole lot of sense and it's not
clear how it is accessed.
2. Can we fill the "sidewalk gap" from the north edge of the basketball court to the
existing trail (just offsite)?
3. Dimension new walks.
4. What is western boundary of thisrschool enrollment area?
5. Is all control in parking lot achieved by striping?
Topic: Utility Plans
Number: 36 Created: 10/30/2006
[10/30/06] Please email me at sjoy@fcgov.com and I will email you the checklist
(Appendix E4). It will help you get all the required information on your plan sets.
There is a lot of information missing on the plans - more detailed comments to follow
once detailed plans are received. Please see redlines for general comments until
the next round of review.
Number: 37 Created: 10/30/2006
[10/30/06] Grading Sheet - label all slopes and tie in all proposed contours to
existing. Grading needs to be flat to nearly flat for a minimum of 2' behind a public
sidewalk. Most spots are eligible. Lots of overlapped labeling. Make sure the roof
drains don't discharge across your sidewalk.
Number: 38 Created: 10/30/2006
[10/30/06] Horizontal Control Plan - please dimension all sidewalks, parking
dimensions, parkways, easements, etc. Label the bus loop radius.
Department: Light & Power Issue Contact: Rob Irish
Topic: General
Number: 13 Created: 10/26/2006
[10/26/06] Please take a look at the proposed transformer location. The proposed
location looks fine except I see a conflict with the grease interceptor. The line from
Page 5
[10/30/06] There is a sidewalk proposed off site to the north. Will need an
easement from the neighboring property owner for access and temp construction
easement.
Number: 21 Created: 10/30/2006
[10/30/06] Is it even possible to construct the driveway/culdesac as shown without
entering the neighboring property? Will need temp construction easement and a 5
or 10' maintenance easement for any work needing to be done in the future. I
suggest moving the driveway 10' to the south so that you can bring the sidewalk
onto your property and avoid any offsite easements for construction.
Number: 22 1. . Created: 10/30/2006
[10/30/06] Please see Appendix E6 for all scanning requirements. The plan sets
are out of conformance. Do not overlap. labeling. Do not shade (will not scan), use
hatching instead, greyscale too light, etc.
Number: 23 Created: 10/30/2006
[10/30/06] Please use greyscale for existing improvements and a darker lineweight
for proposed improvements. The greyscale used is too light and will not scan very
well (hardly legible in some areas).
Number: 25 Created: 10/30/2006
[10/30/06] All driveways must be designed in accordance with 707 (please add to
the utility plan detail sheet and remove the street intersection crosspan detail).
Number: 27 Created: 10/30/2006
[10/30/06] Is the Context Diagram sheet necessary?
Topic: Landscape Plan
Number: 33 Created: 10/30/2006
[10/30/06] Show all utilities.
Number:34 . Created:10130/2006
[10/30/06] Dimension all sidewalks, parkways, etc.
Topic: Site Plan
Number: 28 Created: 10/30/2006
[10/30/06] Remove all building dimensioning - this sheet is not for construction.
Number: 29 Created: 10/30/2006
[10/30/06] Please remove all utilities from the site plan.
Number: 30 Created: 10/30/2006
[10/30/06] Please remove all contouring from the site plan.
Number: 31
Created: 10/30/2006
Page 4
4. The following notes are to be included in the general notes.
- All water line construction shall conform to the Fort Collins - Loveland Water
District Standards and specifications current to the date of construction.
- All sanitary sewer line construction shall conform to the South Fort Collins
Sanitation District standards and specifications current to the date of construction.
5. A note indicating that the District requires a Back -Flow -Prevention -Device with
flow detection on the riser of the fire line needs to be added.
6. 1 have attached the Districts commercial project review packet and guidelines for
your use.
7. 1 have attached the Districts commercial project review packet and guidelines for
your use.
8. The District requires meter pits, located in non traffic areas, for non-residential
projects.
9. All existing taps that are not activated are to be abandoned, in accordance with
District requirements and standards. All costs associated with the abandonment are
the responsibility of the owner.
10. The District did not complete the review due to the number and nature of the
above comments. The District will require another review. Please do not hesitate to
contact me at 226-3104 ext. 104, if you have any questions or require additional
information.
Department: Engineering Issue Contact: Susan Joy
Topic: General
Number: 17 Created: 10/30/2006
[10/30/06] Will need to dedicate new drainage easements as well as any
emergency access easement required by PFA. There are existing easements
dedicated through the site. Please show all existing easements, labeled and
dimensioned on all plan sets and label as "existing" or "proposed". Will you be
vacating any of these easements?
Number: 18 Created: 10/30/2006
[10/30/06] Please complete and submit a TDRF application with the next submittal
for all easements you wish to vacate or dedicate. Please provide a legal description
and exhibit for all easements that you wish to vacate or dedicate.
Number: 19
Created: 10/30/2006
Page 3
Number: 35 Created: 10/30/2006
[10/30/06] The trash enclosure should be large enough to accommodate recycling
services.
Number: 50 Created: 11/2/2006
[11/2/06] Len Hilderbrand (Xcel Energy): No problems at this time.
Topic: Landscaping
Number: 20 Created: 10/30/2006
[10/30/06] Parking lot perimeter and interior landscaping is typically required for all
projects. Please refer to Land Use Code Section 3.2.1(E) for landscape standards,
and please make your best effort to satisfy these requirements. As proposed, the
parking lot and its perimeter are deficient in landscaping. Also, please explore
alternatives to the crusher fines around the foundation of the building (such as
xeriscaping) to add visual interest and variety.
Topic: Public Hearing
Number: 52 Created: 11 /3/2006
[11/3/06] Another round of review is requested before the Public Hearing. In order
to meet the deadlines for the December 7 Planning and Zoning Board meeting, it
would be best to receive revisions no later than Tuesday, November 14.
Topic: Site Plan
Number: 51 Created: 11 /3/2006
[11/3/06] Please show all proposed fences and gates with the next submittal.
Topic: Technical Services
Number: 48 Created: 11 /1 /2006
[11/1/06] Technical Services Comments (JR Wilson/Wally Muscott): These plans
leave a lot to be desired as far as line quality, value of symbols and masked text.
Topic: WaterMastewater
Number: 49 Created: 11 /2/2006
[11/2/06] Terry Farrill (Fort Collins Loveland Water District/South Fort Collins
Sanitation District):
1. Trees that are placed on the easement lines may be lost due to the removal of
50% of the canopy during maintenance operations. The District will not be
responsible for lost trees.
2. The District requires water lines to be buried a minimum of 5 feet and a maximum
of 6 feet. All notes on the drawings are to be corrected to indicate the correct bury
depth.
3. Note #2 on sheet C2 is to be deleted.
Page 2
STAFF PROJECT REVIEW
Citv of Fort Collins
Benneett Wagner & Grody Architects Date: 11 /03/2006
Anne Weber -Williams
1301 Wazee Street
Denver, CO 80204
Staff has reviewed your submittal for Elementary School at Ridgewood Hills, and we
offer the following comments:
ISSUES:
Department: Advance Planning
Topic: General
Number: 6
[10/24/06] No Comment.
Issue Contact: Pete Wray
Created: 10/24/2006
Department: Current Planning Issue Contact: Shelby Sommer
Topic: General
Number: 1 Created: 10/19/2006
[10/19/06] Rick Lee (Building Inspection): Public Schools are exempt from needing
a building permit. Typically they are self -regulated.
Number: 2 Created: 10/20/2006
[10/20/06] Craig Foreman (Park Planning): No comments.
Number: 3 Created: 10/20/2006
[10/20/06] Laurie D'Audney (Water Conservation): No concerns.
Number: 4 Created: 10/20/2006
[10/20/06] Katy Carpenter (GIS): No comments.
Number: 16 Created: 10/30/2006
[10/30/06] Tim Buchanan (Forestry): The City Forestry Department recommends
that Swamp White Oak be changed to Burr Oak. Swamp White Oak does, not live or
thrive in the type of soils we have in this region.
Number: 24 Created: 10/30/2006
[10/30/06] Are bicycle racks proposed on the "front" side (east) of the school in
addition to the west side? If they are only proposed on the west side, there does not
seem to be a convenient route for students coming from the east to access the
racks.
Number: 26 Created: 10/30/2006
[10/30/06] The number of bicycle parking spaces proposed (16) does not seem
adequate for a school of this size, especially since the majority of students attending
the school live within this neighborhood.