agent and shall indicate the number of occupants permitted for each room use. 97UFC
2601.16.1
Number: 46 Created: 10/31 /2006
[12/1 /06]
(10/31/06] COMMERCIAL COOKING FIRE EXTINGUISHING SYSTEM: With the
production of grease -laden vapors, an approved, automatic fire -extinguishing system shall
be provided for the protection of commercial -type cooking equipment. 97UFC 1006.1;
1006.2.1
Number: 47 Created: 11 /1 /2006
[11/29/06] 1 need to see a plat showing.the emergency access easements that we agreed
upon.
[11/1/06] FIRE LANE: PFA requires a fire lane throughout the entire main, U-shaped drive
aisle off Avondale Road, and also the drive on the north side of the school (for buses). This
fire lane shall be visible by painting and signage, and maintained unobstructed at all times.
97UFC 901.2.2.1; 901.3; 901.4.2; 902.2.1
Department: Stormwater-Water-Wastewater Issue Contact: Basil Harridan
Topic: Stormwater- Grading Plans
Number: 12 Created: 10/24/2006
[11/29/06] Please provide spot elevations at the points where the existing grades will tie into
the proposed grades on the north, south and west boundaries of the school.
[10/24/06] The area to the west of the school site will need to 'be regraded in order to
eliminate the low point in the existing overflow swale, please show how that area will be
regraded. If that area is owned by the Ridgewood Hills HOA approval from that HOA will be
required.
The existing storm manhole is located within the new driveway entrance to the north, please
clarify on the plans how the existing manhole will be modified to match the revised grading.
Please add a note to the grading plan indicating that existing grading on the homes to the
south of the school will not be disturbed during construction operations.
Topic: Stormwater- Utility Plans 1
Number: 11 1 . . - Created: 10/24/2006 ,
[11/29/06] Please specify how the inlet in the north drive will be tied into the existing storm
pipe. The pipe should be core drilled and grouted. N Note says that connection will be
made with an ADS saddle Tee, how can this be made on a concrete pipe?
[10/24/06] Please call out all proposed storm sewer sizes and types on the utility plans.
Please provide a detail for the proposed veined grate proposed for the type 13 inlet as well
as a detail for the sidewalk chase with metal grate.
Grading plans and utility plans do not agree. ;Grading plans do not reflect the proposed
inlets and pipes that are tied to the existing lines. Please modify grading plans to match
utility plans.
Please label all existing easements.
Page 5
[10/26/06] Please take a look at the proposed transformer location. The proposed location
looks fine except I see a conflict with the grease interceptor. The line from the building to
the interceptor looks to be in the same location as the transformer pad. This would not be
acceptable. Please take a look at this.
Department: PFA Issue Contact: Carle Dann
Topic: Fire
Number: 39 Created: 10/31/2006
[12/1/06]
[10/31/06] FIXED FIRE PROTECTION: This structure shall be equipped with an approved,
automatic fire -extinguishing system and smoke detectors that tie in to the fire -alarm system,
per 1997 UFC requirements for Group E occupancies.
Number: 40 Created: 10/31/2006
[12/1/06]
[10/31/06] WATER SUPPLY: Fire hydrants, where required, must be the type approved by
the water district having jurisdiction and the Fire Department. Hydrant spacing and water
flow must meet minimum requirements based on type of occupancy. Spacing and flow
requirements include: Commercial, 1,500 gpm at 20 psi residual pressure, spaced not
further than 300 feet to the building, on 600-foot centers thereafter. 97UFC 901.2.2.2
Number: 41 Created: 10/31/2006
[12/1/06]
[10/31/06] ADDRESS NUMERALS: Address numerals shall be visible from the street
fronting the property, and posted with a minimum of six-inch (6) numerals on a contrasting
background. (Bronze numerals on brown brick are not acceptable).97UFC 901.4.4
Number: 42 Created: 10/31/2006
[12/1/06]
[10/31/06] FIRE DEPARTMENT CONNECTION: Fire department connections shall be
installed remote from the buildings, and located on the street or fire lane side of buildings,
fully visible and recognizable from the street or nearest point of fire department vehicle
access or as otherwise approved by the fire code official.
Number: 43 Created: 10/31/2006
[12/1 /06]
[10/31/06] FIRE LINE: The fire line supporting the automatic fire -sprinkler system shall be a
minimum 6-inch line, unless hydraulic calculations can support a reduced -size line.
Number: 44 Created: 10/31/2006
[12/1/06]
[10/31/06] KNOX BOX REQUIRED: Poudre Fire Authority requires a "Knox Box" to be
mounted on the front of every new building equipped with a required fire sprinkler system or
fire alarm system. 97UFC902.4; PFA BUREAU POLICY 88-20
Number: 45
Created: 10/31/2006
[12/1 /06]
[10/31/06] OCCUPANT -LOAD SIGN: Any room having an occupant load of 50 or more
where fixed seats are not installed, and which is used for assembly purposes, shall have the
capacity of the room posted in a conspicuous place on an approved sign near the main exit
from the room. Such sign shall be maintained legible by the owner or the owner's authorized
Page 4
Number: 57 Created: 11 /28/2006
[11/28/06] Still does not meet Appendix E6 scanning requirements.
Topic: Landscape/Site
Number: 58 Created: 11 /28/2006
[11/28/06) Redlines from the previous round and comments under "General" have not been
addressed. The redlines from both rounds of review are being returned. Please address
the comments and return both sets of redlines with the next round of review.
Topic: Site Plan
Number: 29 Created: 10/30/2006
[11/28/06] Repeat.
[10/30/06] Please remove all utilities from the site plan.
Number: 31 Created: 10/30/2006
[11/28/06] [10/30/06] Show and dimension all easements (existing and proposed).
Topic: Utility Plans
Number: 37 Created: 10/30/2006
[11/28/06] Please label all slopes.
[10/30/06] Grading Sheet - label all slopes and tie in all proposed contours to existing.
Grading needs to be flat to nearly flat for a minimum of 2' behind a public sidewalk. Most
spots are eligible. Lots of overlapped labeling. Make sure the roof drains don't discharge
across your sidewalk.
Number: 38 Created: 10/30/2006
[11/28/06] If PFA is requiring emergency access easements, they will need to be shown on
all plan sets/sheets.
[10/30/06] Horizontal Control Plan - please dimension all sidewalks, parking dimensions,
parkways, easements, etc. Label the bus loop radius.
Number: 60 Created: 11 /28/2006
[11/28/06] C2 - The General Notes are "off' in numbering or missing something (they were
correct the first time). Please see Appendix El. Also, the variance listed needs to be more
speck - list the section, standard and what was granted as the variance.
Number: 61 Created: 11 /28/2006
[11/28/06] Remove all bid alternative labeling. Only show what is to be constructed.
Number: 62 Created: 11 /28/2006
[11/28/06] Grading sheet - this sheet won't scan and in some cases, can't be read or
reviewed (spots are overlapped too thickly). Label all slopes. Show grading.for the offsite
sidewalk shown to the north.
Department: Light & Power Issue Contact: Rob Irish
Topic: General
Number: 13 Created: 10/26/2006
[11/28/06] The location of the grease interceptor is fine. The conflict is the sewer line
between the building and the grease interceptor running under a portion of the transformer.
Please re -look at this area.
Page 3
Number: 19 Created: 10/30/2006
[11/28/06) Repeat.
[10/30/06) There is a sidewalk proposed off site to the north. Will need an easement from
the neighboring property owner for access and temp construction easement.
Number: 21 Created: 10/30/2006
[11/28/06] Repeat.
[10/30/06] Is it even possible to construct the driveway/culdesac as shown without entering
the neighboring property? Will need temp construction easement and a 5 or 10'
maintenance easement for any work needing to be done in the future. I suggest moving the
driveway 10' to the south so that you can bring the sidewalk onto your property and avoid
any offsite easements for construction.
Number: 22 Created: 10/30/2006
[11/28/06] Repeat.
[10/30/06] Please see Appendix E6 for all scanning requirements. The plan sets are out of
conformance. Do not overlap labeling. Do not shade (will not scan), use hatching instead,
greyscale too light, etc.
Number: 23 Created: 10/30/2006
[11/28/06] Repeat.
[10/30/06] Please use greyscale for existing improvements and a darker lineweight for
proposed improvements. The greyscale used is too light and will not scan very well (hardly
legible in some areas).
Number: 25 Created: 10/30/2006
[11/28/06] Repeat.
[10/30/06] All driveways must be designed in accordance with 707 (please add to the utility
plan detail sheet and remove the street intersection crosspan detail).
Number: 59 Created: 11 /28/2006
[11/28/06] Please change the title on all plan sets to read "Elementary School at Ridgewood
Hills" and put the tract U, etc, in the legal description.
Number: 63 Created: 11 /28/2006
[11/28/06] All plan sets - See redlines for other comments as well as comments under other
sections.
Topic: Landscape Plan
Number: 33 Created: 10/30/2006
[11/28/061 Lineweight is too faint. Show proposed in dark lineweight, existing in the
minimum grey scale required by Appendix E6.
[10/30/06] Show all utilities.
Number: 34 Created: 10/30/2006
[11/28/06] Repeat.
[10/30/06] Dimension all sidewalks, parkways, etc.
Number: 56 Created: 11 /28/2006
[11/28/06] Show, label, and dimensin all easements and row.
Page 2
000
a STAFF PROJECT REVIEW
Citvof Fort Collins
Benneett Wagner & Grody Architects Date: 12/1/2006
Anne Weber -Williams
1301 Wazee Street
Denver, CO 80204
Staff has reviewed your submittal for ELEMENTARY SCHOOL AT RIDGEWOOD HILLS -
SITE PLAN ADVISORY REVIEW, and we offer the following comments:
ISSUES:
Department: Current Planning Issue Contact: Shelby Sommer
Topic: Landscaping
Number: 20 Created: 10/30/2006
[11/28/06] Thank you for providing the landscaping island, but additional ones are desired
in order to adequately shade and define the parking lot. Also, the parking lot perimeter
landscaping is still deficient and the foundation treatment is lacking interest.
[10/30/06] Parking lot perimeter and interior landscaping is typically required for all projects.
Please refer to Land Use Code Section 3.2.1(E) for landscape standards, and please make
your best effort to satisfy these requirements. As proposed, the parking lot and its perimeter -
are deficient in landscaping. Also, please explore alternatives to the crusher fines around
the foundation of the building (such as xeriscaping) to add visual interest and variety.
Topic: Site Plan
Number: 54 Created: 11/28/2006
[11/28/06] Please label all fences and sidewalks as such. All of the proposed fences and
gates are not drawn on the plans (on the north and west sides of the property especially).
Also, vinyl clad is much nicer than traditional chain link fencing, so please consider using
this for your development.
Number: 55 Created: 11 /28/2006
[11/28/06] Thank you for providing additional bicycle parking, however the bicycle parking
total on the site plan does not match the total on the landscaping plan. Please revise to
show how many spaces will be provided at each location.
Department: Engineering Issue Contact: Susan Joy
Topic: General
Number: 17 Created: 10/30/2006
[11/28/06] Repeat. All easements need to be shown as existing or proposed before going
to hearing.
[10/30/06] Will need to dedicate new drainage easements as well as any emergency
access easement required by PFA. There are existing easements dedicated through the
site. Please show all existing easements, labeled and dimensioned on all plan sets and
label as "existing" or "proposed". Will you be vacating any of these easements?
Number: 18 Created: 10/30/2006
[11/28/06] Repeat.
[10/30/06] Please complete and submit a TDRF application with the next submittal for all
easements you wish to vacate or dedicate. Please provide a legal description and exhibit
for all easements that you wish to vacate or dedicate.
Page 1