HomeMy WebLinkAboutUNITED WAY HOUSING SERVICES DAY CENTER - FDP - 30-06/A - CORRESPONDENCE -Department: Stormwater-Water-Wastewater Issue
Contact: Roger Buffington
Topic: Water/Wastewater
Number: 105 Created: 4 / 3 / 2007
[4/3/07] See red -lined utility plans for remaining minor comments.
A copy of a comment letter from Lisa Thieme of the Larimer County
Assessor's office is attached to this letter. She is requesting that the legal
description, title for the subdivision plat be "Lots 2 and 3, A Minor
Subdivision Plat of Conifer Industrial Park". Please check with J.R. Wilson
in the City's Technical Services Department (221-6588) for a title
acceptable to the City. We do not have "minor" plats.
Be sure and return all red -lined plans when you re -submit. Please see
attached REVISIONS ROUTING SHEET for the number of paper copies of
each document to re -submit.
If you have any questions regarding these issues or any other issues related
to this project, please feel free to call me at 221-6341.
Yours Truly,
teve Ol
City Planner
cc: Susan Joy
Current Planning file #30-06
Page 5
Number: 88 Created: 3 / 21 / 2007
[3/21/071 The Landscape Plan shows the planned streetlight on Conifer
Street as previously requested. However, the two adjacent street trees also
need to be relocated or deleted to provide a minimum of 40 ft. clearance
between the light and the trees. This can be reduced to 15 ft. if the trees
are changed to an ornamental type.
Topic: Utility Plans
Number: 74 Created: 12 / 11 / 2006
[3/21/07]
[12/ 11/06] The developer will need to coordinate the power requirements
for both buildings with Light & Power Engineering (221-6700).
Department: PFA Issue Contact: Carie Dann
Topic: Fire
Number: 47 Created: 11 / 21 / 2006
[4/4/07] Plans show the FDC on the building, instead of remote. Since the
project was underway prior to PFA's practice of requiring remote FDCs, the
building -mounted sprinkler connection is acceptable. Please ensure that
access to the sprinkler connection (Fire Department Connection) on the
building is not obstructed, particularly by any type of fence.
[11/21/06] FIRE DEPARTMENT CONNECTION: Fire department
connections shall be installed remote from the buildings, and located on the
street or fire lane side of buildings, fully visible and recognizable from the
street or nearest point of fire department vehicle access or as otherwise
approved by the fire code official. 2006 International Fire Code 912.2.1 and
PFA Bureau Policy
Department: Stormwater-Water-Wastewater Issue
Contact: Wes Lamarque
Topic: Stormwater
Number: 106 Created: 4 / 4 / 2007
[4/4/07] Please replace 24" sidewalk culvert with a concrete sidewalk
culvert, detail D-12.
Number: 108 Created: 4/ 6/ 2007
[4/6/07] Please include a Type R inlet detail in the plan set.
Number: 109 Created: 4/ 6/ 2007
[4/6/07] A modified version of the City's standard WQ Outlet Structure
Detail is needed instead of the detail currently being shown in the plan set.
Please call for further details.
Number: 110 Created: 4 / 6 / 2007
[4/6/07] Please see other minor comments on the red -lined plan set.
Page 4
Topic: Utility Plans - Grading Plan
Number: 96 Created: 3 / 30 / 2007
[3/30/07] Will need a specific design for the portion of the retaining wall
highlighted in yellow (see redlines, sheet 5). The generic details shown on
sheet 12 specify geogrid which would present a problem as the geogrid
would then extend into the utility easement. The first time someone
trenched through there, the grid would be cut and the wall would lose its
structural integrity so no geogrid would be allowed within the easement.
Please provide a design for the retaining wall and include them in the utility
plan set. They would need to be signed off and stamped by the structural,
engineer who designed it, not by Loonan and Associates, so you don't have
to worry about having to stamp somebody else's work. Please call if you
have any questions Jim : )
Topic: Utility Plans - Horizontal Control
Number: 100 Created: 3/30/2007
[3/30/07] Comments 97 & 98 apply here as well.
Topic: Utility Plans - Retaining Wail Details
Number: 102 Created: 3 / 30 / 2007
[3/30/07] Not enough information given to construct this wall. Will need a
full design for the portion of wall affecting the UE (see highlighted area on
sheet 5).
Topic: Utility Plans -Utility
Number: 97 Created: 3 / 30 / 2007
[3/30/07] Remove the word "pedestrian" from the access easement label.
Number: 98 Created: 3 / 30 / 2007
[3/30/07] The existing detention pond easement was labeled as "to be
vacated" on sheet 3... is this true?
Number: 99 Created: 3 / 30 / 2007
[3/30/07] The retaining wall design to be designed by others needs to be
included in the plan set (see comment 96) and included in this plan set.
Please refer to the detail/sheet number where it will be shown.
Department: Light & Power Issue Contact: Doug Martine
Topic: Landscape Plan
Number: 75 Created: 12/ 11 /2006
[3/21/07]
[12/11/06] There are existing streetlights at the N.E. and S.E. corners of lot
# 1. The planned street trees must be relocated to provide a minimum of 40
ft. clearance (15 ft. if the tree is an ornamental) to the streetlights.
Page 3
Number: 107 Created: 4 / 6 / 2007
[4/6/07] From Technical Services:
1. Boundary closes.
2. Missing distance on 9' Utility and Access easement along east side of
property.
Topic: Site Plan
Number: 104
[3/30/07] See red -lines.
Topic: Utility Plans - Cover Sheet
Created: 3 / 30 / 2007
Number: 89 Created: 3 / 30 / 2007
[3/30/07] Add a variance to line 48 stating that a variance was granted to
allow the sidewalk within the utility easement along Blue Spruce and
Conifer.
Topic: Utility Plans - Details
Number: 101 Created: 3 / 30 / 2007
[3/30/071 Sheet 9 - See 706 for driveway drainage requirements (HP at
Bow).
Topic: Utility Plans - Drainage & Erosion Control
Number: 94 Created: 3 / 30 / 2007
[3/30/071 Remove the word "pedestrian" from all access easement labeling
(see red -lines).
Topic: Utility Plans - Existing Conditions
Number: 93 Created: 3 / 30 / 2007
[3/30/071 Vacate the easement by plat, not separate document (much
easier). You can do it either way though. If done by separate document,
please provide me a copy of the recorded document vacating the easement if
this was dedicated to a private party. If dedicated to the City, then we'll
need to go through a separate vacation process, which costs more $$ (much
easier to do by plat).
Topic: Utility Plans - General Notes Sheet 2
Number: 91 Created: 3/ 30/ 2007
[3/30/07] Title Appendix E2 as "Construction Notes".and remove the
General Notes and Specifications title (that's Appendix E1).
Number: 92 Created: 3 / 30 / 2007
[3/30/07] See Stormwater for the specific seed mix requirements (note 14).
Page 2
STAFF PROJECT REVIEW
City of Fod Collins
e
Architecture West LLC Date: 04/09/2007
c/o Heather Butler
4710 South College Avenue
Fort Collins, CO 80525
Staff has reviewed your submittal for United Way Housing Services Day
Center - Final Plans, and we offer the following comments:
ISSUES:
Department: Current Planning Issue Contact: Steve Olt
Topic: Stormwater
Number: 111 Created: 4 / 9 / 2007
[4/9/07] See red -lined Site & Landscape Plans for Current Planning's
comments. We are ready to accept mylars with revisions addressing these
latest comments. Be sure to submit the latest red -lined plans with a paper
copy re -submittal or the mylars submittal.
Department: Engineering Issue Contact: Susan Joy
Topic: General
Number: 95 Created: 3 / 30 / 2007
[3/30/071 Continue the sidewalk to the north straight back vs trying to
curve it around. David Averill and I met on site and felt that aligning your
sidewalk to the one to the north would function much better and
determined that an access easement across the neighboring drive would not
be necessary. Please show the sidewalk to the north on all plan sets so we
can see how yours will tie in. Please contact David Averill for any questions
you might have regarding this connection.
Topic: Landscape Plan
Number: 103 Created: 3 / 30 / 2007
[3/30/07] See red -lines.
Topic: Plat
Number: 90 Created: 3 / 30 / 2007
[3/30/071 The drainage easement shown in the lower SE corner of the
property is stated to be vacated on sheet 3 of the utility plans..:is this
correct?