HomeMy WebLinkAboutUNITED WAY HOUSING SERVICES DAY CENTER - PDP - 30-06 - CORRESPONDENCE -Number: 8 Created: 11 / 7 / 2006
[11/7/06] Please label the property lines on the Site Plan
Number: 9 Created: 11 / 7/ 2006
[11/7/06] West elevation suggestion: Use the same window configuration
on each side of the entrance to keep a symmetrical look.
Number: 10 Created: 11 / 7/ 2006
[11/7/06] Elevations depict the main entrance on the west side with a
double door. The Site Plan shows the west side with a single door. Please
clarify.
It has been determined that this development request could possibly be
placed on the agenda for the January 18, 2007 Planning & Zoning Board
public hearing. However, there are some issues and concerns with various
City departments that must be addressed before this item could go to the
Board. This could be done through another formal round of review (if re-
submitted quickly) or by working directly with the appropriate
representatives of the departments. Staff will be setting the P 8v Z Board
agenda on December 20, 2006.
Be sure and return all red -lined plans when you re -submit.
If you have any questions regarding these issues or any other issues related
to this project, please feel free to call me at 221-6341.
Yours Truly,
Awc5w
Steve Olt
City Planner
cc: Susan Joy, Engineering ... 221-6605
Jenny Nuckols, Zoning ... 416-2313
Janet McTague, Light & Power ... 224-6154
Carie Dann, Poudre Fire Authority ... 416-2869
Roger Buffington, Water/Wastewater ... 221-6854
Wes Lamarque, Stormwater ... 416-2418
Current Planning file #30-06
Page 9
Department: Stormwater-Water-Wastewater Issue
Contact: Roger Buffington
Topic: Water/Wastewater
Number: 32 Created: 11 / 21 / 2006
[ 11 / 21 / 06] Label all waterline fittings, valves, etc. Indicate length of water
line segments between valves, fittings, etc.
Number: 33 Created: 11 / 21 / 2006
[ 11 / 21 / 06] Move curb stop out of sidewalk and to within 2 ft of meter pit.
Curb stop must be in easement or R.O.W.
Number: 34 Created: 11 / 21 / 2006
[ 11 / 21 / 06] Each building must have separate water and sewer services.
Will services be stubbed in for the future building?
Number: 35 Created: 11 / 21 / 2006
[ 11 / 21 / 06] Is separate irrigation tap planned?
Number: 36 Created: 11 / 21 / 2006
[ 11 /21 /06] See plans for other comments.
Department: Zoning Issue Contact: Jenny Nuckols
Topic: ZONING
Number: 2 Created: 11 / 7 / 2006
[ 11 / 7 / 06] Please remove topography lines from the final Site Plan.
Number: 3 Created: 11 / 7 / 2006
[ 11 / 7 / 06] Please show and label the building envelope and footprint on the
Site Plan.
Number: 4 Created: 11 / 7 / 2006
[11/7/06] How tall will the masonry wall be around the play area.
Number: 5 Created: 11 / 7/ 2006
[11/7/06] There are no handicap spaces called out on the Site Plan. Please
label and note dimensions of HC spaces. NOTE: There must be at least on
van accessible space with an overall width of 16 feet.
Number: 6 Created: 11 / 7/ 2006
[11/7/06] What type offence is proposed around the existing storage areas
near the trash enclosure?
Number: 7 Created: 11 / 7 / 2006
[11/7/06] Provide a bike rack near the main entrance and note its location
on the Site Plan.
Page 8
Department: Stormwater-Water-Wastewater Issue
Contact: Wes Lamarque
Topic: Floodplain
Number: 30 Created: 11 / 21 / 2006
[ 11 / 21 / 06] The City's Dry Creek floodplain will be revised in the near
future and this revision will remove the site form the 100-year floodplain.
The site still will be partially in the FEMA 500-year floodplain until the
Physical Map Revision is approved by FEMA in approximately 2 years.
Number: 31 Created: 11 / 21 / 2006
[ 11 / 21 / 06] Please show and label FEMA 500-year floodplain on the plat
and drainage plan.
Topic: Stormwater
Number: 25 Created: 11 / 21 / 2006
[ 11 / 21 / 06] Please discuss in detail the reasoning behind this site only
detaining for on -site runoff and not off -site runoff from the north and west.
In the discussion, describe where the other lots that are undeveloped will
detain and outfall. This is needed because this proposal is changing the
existing design for all 4 of these lots. Please discuss how the interim
(existing) undeveloped off -site flows will drain. This site may need to route
these off -site flows through the site. Please remove discussion with City
Staff in the text and only include the explanations.
Number: 26 Created: 11 / 21 / 2006
[ 11 / 21 / 061 The .06 cfs release rate for the detention pond is impractical
(being less than the water quality release rate) and also will probably have
clogging problems. It is suggested that you request a variance to allow
basin F to release undetained and keep the detention pond release rate
equal to the site release rate of .36 cfs. This will allow for a practical release
and still provide adequate detention and still improve the situation for the
regional downstream drainage system.
Number: 27 Created: 11 / 21 / 2006
[ 11 / 21 / 06] The minimum size for storm sewers is 15 inches. This is for
clogging purposes. Please revise storm sewers 2 and 3 to 15 inches. Storm
sewer 1 can stay at 10 inches as the drainage area is extremely small.
Number: 28 Created: 11 / 21 / 2006
[ 11 / 21 / 06] Please use the City standard water quality outlet structure
detail. I can email you this new detail.
Number: 29 , Created: 11 / 21 / 2006
[ 11 / 21 / 06] Please change the text on the plat to read Drainage Easement,
not Detention Pond Easement.
Page 7
Department: PFA Issue Contact: Carie Dann
Topic: Fire
Number: 47 Created: 11 / 21 / 2006
[ 11 / 21 / 06] FIRE DEPARTMENT CONNECTION: Fire department
connections shall be installed remote from the buildings, and located on the
street or fire lane side of buildings, fully visible and recognizable from the
street or nearest point of fire department vehicle access or as otherwise
approved by the fire code official. 2006 International Fire Code 912.2.1 and
PFA Bureau Policy
Number: 48 Created: 11 / 21 / 2006
[ 11 / 21 / 06] WATER SUPPLY: Fire hydrants, where required, must be the
type approved by the water district having jurisdiction and the Fire.
Department. Hydrant spacing and water flow must meet minimum
requirements based on type of occupancy. Spacing and flow requirements
include: Commercial, 1,500 gpm at 20 psi residual pressure, spaced not
further than 300 feet to the building, on 600-foot centers thereafter. 97UFC
901.2.2.2
Number: 49 Created: 11 / 21 / 2006
[ 11 / 21 / 06] KNOX BOX REQUIRED: Poudre Fire Authority requires a "Knox
Box" to be mounted on the front of every new building equipped with a
required fire sprinkler system or fire alarm system. 97UFC902.4; PFA
BUREAU POLICY 88-20
Number: 50 Created: 11 / 21 / 2006
[ 11 /21 / 06] ADDRESS NUMERALS: Address numerals shall be visible from
the street fronting the property, and posted with a minimum of six-inch (6)
numerals on a contrasting background. (Bronze numerals on brown brick
are not acceptable). 97UFC 901.4.4
Number: 51 Created: 11 / 21 / 2006
[11/21/061 ASSEMBLY AREAS: Will any areas of the building be
considered an Assembly Occupancy?
Number: 52 Created: 11 / 22 / 2006
[11/22/06] TURNING RADII: Minimum turning radii (drive aisle) is 25 feet
inside, 50 feet outside.
Department: Traffic Operations Issue Contact: Eric Bracke
Topic: Traffic
Number: 1 Created: l l / 1 / 2006
[ 11 / 1 / 06] No issues or concerns from Traffic Operations. The TIS is
accepted.
R
Page 6
N
Number: 41 Created: 11 / 21 / 2006
[ 11 / 21 / 06] See redlines.
Topic: Utility Plans
Number: 42 Created: 11 / 21 / 2006
[ 11 / 21 / 06] Cover Sheer -Project title is incorrect. Provide 2 benchmarks.
Add line 49 and reference the soils report. Provide a soils report.
Corrections required to line 19 and 40.
Number: 43 Created: 11 / 21 / 2006
[ 11 / 21 / 06] Sheet 2 - Add notes from E2.
Number: 44 Created: 11 / 21 / 2006
[ 11 / 21 / 06] Remove the word "min" when dimensioning row, etc. Must
dimension the actual.
Number: 45 Created: 11 / 21 / 2006
[ 11 / 21 /06] Grading plan - label all slope ratios. Grades behind a public
walk need to be flat to nearly flat for a minimum of two feet. Label TOW and
BOW. Depending on height of retaining wall, details may be required. A
sidewalk chase is proposed in the ramp off Conifer and needs to be moved.
A 12" HDPE storm pipe is shown terminating at the detention pond - please
add the appropriate FES or will this be a "weep hole" in the wall?
Number: 46 Created: 11 / 21 / 2006
[ 11 / 21 / 06] Telephone pedestals, electric vaults, etc are shown in the
sidewalk. Are these existing? Proposed? Will need to move some of them.
Department: Light & Power Issue Contact: Janet McTague
Topic: General
Number: 11 Created: 11 / 9 / 2006
[11/9/06] Need to coordinate a transformer location within 10 feet of a
paved surface.
Number: 12 Created: 11 / 9 / 2006
[11/9/06] We'll need a C-1 form indicating electrical requirements for the
building.
Number: 13 Created: 11 / 9 / 2006
[11/9/061 Relocation of existing electric facilities, if necessary, is paid for
by the developer.
Page 5
Number: 19 Created: 11 / 20 / 2006
[11/20/061 The correct row, parkway widths, sidewalk & utility easements
were not dedicated and designed. Please see 7-5F for Conifer and 7-6F for
Blue Spruce. You have the option of dedicating additional row to the back
of the sidewalk or dedicating an access easement, whichever is acceptable to
you. There are pros and cons to each.
Number: 20 Created: 11 / 20 / 2006
[11/20/061 Grades behind a public sidewalk need to be flat to nearly flat
for a minimum of 2'. Label all slope ratios on the grading sheet.
Number: 21 Created: 11 / 20/ 2006
[11/20/061 Both driveways need to be designed and SHOWN on the plans
in accordance with 706.
Number: 22 Created: 11 / 20 / 2006
[ 11 / 20 / 06] Please label all easements as "proposed" or "existing".
Number: 23 Created: 11 / 20/ 2006
[11/20/061 The emergency access easement requires a 50' outside turning
radius and 25' inside turning radius.
Number: 24 Created: 11 / 20 / 2006
[11/20/061 The Horizontal Control Plan is missing a lot of information.
Please dimension all sidewalks, parkways, row, UE's (existing and
proposed), parking stall widths and lengths (or label as typical if typical),
etc.
Number: 37 Created: 11 / 21 / 2006
[ 11 / 21 / 06] You can vacate the access easements for the shared driveways
by this plat and not worry about vacating the easement on the neighboring
property. Those property owners can do that when they (re)develop.
Number: 39 Created: 11 / 21 / 2006
[ 11 / 21 / 06] Show existing features (driveways, sidewalks, etc) within 150' of
the project boundaries (all plan sets).
Number: 40 Created: 11 / 21 / 2006
[ 11 / 21 / 06] There are no sight distance easements required with this
project. Sight distance easements are only required where they fall outside
the row and this is not happening with this project.
Topic: Site Plan
Number: 38 Created: 11 / 21 / 2006
[ 11 / 21 / 06] Remove all contours.
Page 4
way. Therefore, a request for a modification of this standard must be
submitted for review by staff and the Planning and Zoning Board.
* Please reference Section 2.8.2(H) of the Land Use Code for the criteria to
use in the requests for modifications of the standards.
Number: 61 Created: 11 /28/2006
[11/28/061 The details at the bottom of the Site Plan need to be slightly
enlarged to make them legible.
Number: 62 Created: 11 / 28/ 2006
[11/28/061 On the Vicinity Map, East Vine Drive does not run north -
south east of the SITE. That street actually is Redwood Street.
Topic: Subdivision Plat
Number: 67 Created: 11 / 28 / 2006
[11/28/06] If the Building Envelopes as shown on the subdivision plat
would need to be changed in the future then a formal replat of the property,
going to a public hearing, would be required. The plat cannot be changed
administratively through the Minor Amendment process.
Topic: Utility Plans
Number: 70 Created: 11 / 28 / 2006
[11/28/061 Len Hilderbrand of Xcel Energy indicated that they will need to
open a street cut to install a new gas service to this development. There is a
6" MW gas main in Blue Spruce Drive.
Department: Engineering Issue Contact: Susan Joy
Topic: General
Number: 14 Created: 11 / 20 / 2006
[11/20/061 Please title ALL plan sets "United Way Housing Services Day
Center".
Number: 15 Created: 11 / 20 / 2006
[ 11 / 20/ 06] There were a lot of comments given at the initial conceptual
review that were not addressed with this submittal. More detailed
comments to follow with Final Compliance.
Number: 16 Created: 11 / 20/ 2006
[11/20/061 The plan sets do not conform to the scanning requirements set
forth in Appendix E6.
Number: 18 Created: 11 / 20 / 2006
[11/20/061 Directional ramps are required in the City of Fort Collins.
Page 3
Topic: Site Plan
Number: 53 Created: 11 / 28/ 2006
[11/28/06] The sidewalk along the east side of the entry drive from Conifer
Street must be 10' wide. It currently is shown as 5' wide.
Number: 54 Created: 11 / 28/ 2006
[11/28/06] There are overlapping utility facilities at the northeast corner of
the site.
Number: 55 Created: 11 / 28/ 2006
[11/28/06] Regarding bicycle parking on the site, with 30 vehicle parking
spaces there must be at least 2 bicycle spaces (5% of vehicle parking, per
the Land Use Code); however, considering the nature of the land use and
clients using the facility, there should be additional bicycle parking
provided. How many bicycles can the rack as shown accommodate? This
should be indicated on the Site Plan.
Number: 56 Created: 11 / 28 / 2006
[11/28/061 If the future 5,000 square foot building on Lot 2 were to develop
as General Office use then there would be 2 parking spaces too many on
that lot (3 spaces/ 1,000 square feet of building, per the Land Use Code).
Number: 57 Created: 11 /28/2006
[11/28/06] What does EXT. mean in the fenced stor'g. areas?
Number: 58 Created: 11 / 28 / 2006
[11/28/06] The handicapped ramps at the corner of Conifer Street and
Blue Spruce Drive need to be "directional" ramps.
Number: 59 Created: 11 / 28/ 2006
[11/28/06] The handicapped parking stall symbol as shown in the Legend
is not being shown in the stalls on the plan.
Number: 60 Created: 11 / 28/ 2006
[11/28/061 A request for a modification of the standard set forth in Section
3.5.3 of the Land Use Code, regarding the required "build -to" lines, must be
submitted for review by staff and the Planning and Zoning Board. The
Housing Services Day Center building does not satisfy this standard as it
relates to Blue Spruce Drive. It is 17' from the street right-of-way.
* Also, Neither the Housing Services Day Center building nor the future
building on Lot 2 satisfy the standard set forth in Section 4.28(E)(2)(b)
of the Land Use Code. Their setbacks from Conifer Street must be no
more than 30' from the street right-of-way for at least.30% of the
building face and they are shown as being 45' to 50' from the right -of -
Page 2
® STAFF PROJECT REVIEW
City of Fort Collins
Architecture West, LLC Date: 11/28/2006
c/o Heather Butler
4710 South College Avenue
Fort Collins, CO 80525
Staff has reviewed your submittal for United Way Housing Services Day
Center, PDP - Type 2 (Planning & Zoning Board review), and we offer the
following comments:
ISSUES:
Department: Current Planning Issue Contact: Steve Olt
Topic: General
Number: 68 Created: 11 / 28/ 2006
[ 11 / 28 / 06] Rick Lee of the Building Department is forwarding a copy of
the current Codes & Standards that his department will be enforcing. Also,
a pre -submittal Code Review meeting is required prior to submitting for
building permit.
Topic: Landscape Plan
Number: 63 Created: 11 /28/2006
[11/28/06] Per Section 3.2.1(E)(4)(a) of the Land Use Code, there must be 2
additional trees in the parking lot setback area along the west property line
and 1 additional tree in the parking lot setback area along the north
property line (see red -lined Landscape Plan).
Number: 64 Created: 11 / 28/ 2006
[11/28/06] Per Section 3.2.1(E) (4) (b) of the Land Use Code, there must be
additional shrub plantings, for screening purposes, in the setback areas to
the parking lots along the west and north property lines (see red -lined
Landscape Plan).
Number: 65 Created: 11 / 28 / 2006
[ 11 / 28/ 061 Need additional shrub plantings along the south side of the
south retaining wall for the detention pond along Conifer Street.
Number: 66 Created: 11 / 28 / 2006
[11/28/06] There are 6 Juniper trees along the north property line that
appear to be off of the property. If so, then a landscape easement will be
required and must be obtained from the property owner to the north.
Number: 69 Created: 11 / 28/ 2006
[11/28/06] A copy of comments from Tim Buchanan, the City Forester, is
attached to this comment letter.
Page 1