HomeMy WebLinkAbout3425 S. SHIELDS ST. MIXED-USE - PDP - 28-07 - CORRESPONDENCE - (9)As we discussed at staff review, we will not have another formal round of review before
hearing. Please address pre -hearing issues and return plans for the above commenters to
review. We'll want a week or so turnaround time and then you and I can schedule an
informal meeting to review. Be sure and return all of your redlined plans when you re-
submit.
If you have any questions regarding these issues or any other issues related to this project,
please feel free to call me at (970) 221-6206.
Sincerely,
nne H. As en
City Planner
Page 7
[9/7/07] The existing 3/4-inch water service is a FCLWD service; therefore, contact district
to regarding the future use of that service.
Number: 14 Created: 9/7/2007
[9/7/07] At final, profiles of sewers required.
Number: 15 Created: 9/7/2007
[9/7/07] See redlined plans for other comments.
Topic: Plat
Number: 16 Created: 9/7/2007
[917/07] For existing sanitary sewer along Shields, provide additional easement to equal 10
feet from centerline of sewer on the west.
Department: Zoning Issue Contact: Jenny Nuckols
Topic: ZONING 1�
Number: 1 Created: 8/24/2007
[8/24/07] Two rows of parking between the commercial building and the residential
buildings: only 15 spaces allowed in a row without an intervening landscaped island. I Vim"
would recommend adding a landscaped island in the center of each row with required trees
and plantings.
Number: 2 Created: 8/24/2007
[8/24/07] 1 don't see any ramps near the handicap spaces accessing the sidewalks. Please
review.
Number: 3 Created: 8/24/2007
[8/24/07] 1 see two areas called out for trash/recyclables. Will this be adequate for 36
residential units as well as the commercial building? Please review.
Number: 4 Created: 8/24/2007
[8/24/07) Please provide more detail for the planting areas around the buildings. Types,
counts etc.
Number: 5 Created: 8/24/2007
[8/24/07] What are the existing trees along Shields? They don't look to be adequate to
comply with the street tree requirements.
Number: 6 Created: 8/24/2007
[8/24/07] You are showing shrubs and perennials in the Water quality pond. Is that correct?
Number: 7 Created: 8/24/2007
[8/24/07] 3.2.1(E)(4)(b) Screening - parking lots with more than 6 spaces need to be
screened from abutting uses. lc?wU;, i
Number: 8 Created: 8/27/2007
[8/27/07] Site Plan: Please show and label building envelopes, footprints.
Page 6
Please enlarge size of basin designations as they cannot be easily read.
Please show direction of flow for all off -site basins. Basin OS-1 contributes flow onto the
site, please route this fllow through the site, though no detention is required for that basin.
Please show spillway location in detention pond.
Topic: Grading Plan
Number: 36 Created: 9/11 /2007
[9/11/07] The level of detail of the grading plan is OK for as preliminary submittal. At final
spot elevations should be provided around buildings.
Swale on north property line should be better defined. Flows form the existing single family
homes to the north or the off -site basin to the west should not be blocked as they historically
drain to the south. Provide spillway cross section, show how the flows enter Shields Street.
A sidewalk chase may be needed.
At final provide spillway elevation and design. Make sure spillway is directed to the east, to
Shields Street.
Topic: Utility Plans
Number: 35 Created: 9/ 11 /2007
[9/11/07] Please call out the size and type of the proposed storm sewer on the utility plan.
At final you will need to identify that line as a private line to be owned and maintained by the
owner.
Please identify proposed inlet size and types.
Also identify all existing drainage infrastructure.
At final please provide storm sewer profiles showing all crossings. Storm line should be
RCP in parking lot.
Department: Stormwater-Water-Wastewater Issue Contact: Roger Buffington
Topic: Water/Wastewater
Number: 9 Created: 9/7/2007
[9/7/07] Revise water main to 8-inch to provide fire flow capacity for hydrants and fire
sprinkler systems.
Number: 10 Created: 9/7/2007
[9/7/07] Show curb stop locations on domestic water services.
Number: 11 Created: 9/7/2007
[917/07] Move curb stop/meter pit for the commercial building as noted on plans.
Number: 12 Created: 9/7/2007
[9[7/07] Move sanitary sewer so that manholes are on drive centerlines.
Number: 13
Created: 9/7/2007
Page 5
Number:40 Created:9/11/2007 - _-
[9/11/07] Submit C-1 forms for building loads and electric panel sizes.
Number: 41 Created: 9/11 /2007
[9/11/07] Prior to next submittal contact Light and Power to complete design of elect
system for the Overall Utility Plan.
Department: PFA Issue Contact: Carie Dann
Topic: Fire
Number: 47 Created: 9/12/2007
[9/12/07] Conceptual review comments mentioned names for the private drives; this is not a
consideration for us, since there are no private drives on the site.
Number: 48 Created: 9/12/2007
[9/12/07] Conceptual review comments mentioned an emergency access easement for the
perpetual access easement off of Richmond Drive. PFA does not need nor require this to be
an EAE.
Number: 49 Created: 9/12/2007
[9/12/07] The International Fire Code/Uniform Fire Code variations of requirements
mentioned in conceptual review comments is not a consideration for this project. That
comment can be disregarded.
Number: 50 Created: 9/12/2007
[9/12/07] As noted by Chris Matkins, the C-shaped Emergency Access Easement on the
drive aisles around the residential units will be 30 feet. Width was shown in correctly on the
site plan.
Number: 51 Created: 9/12/2007
[9/12/07] WATER SUPPLY: Fire hydrants, where required, must be the type approved by
the water district having jurisdiction and the Fire Department. Hydrant spacing and water
flow must meet minimum requirements based on type of occupancy. Minimum flow and
spacing requirements include: Commercial and multi -family dwellings, 1,500 gpm at 20 psi
residual pressure, spaced not further than 300 feet to the building, on 600-foot centers
thereafter. These requirements may be modified if buildings are equipped with automatic fire
sprinkler systems. 97UFC 901.2.2.2
Number: 52 Created: 9/12/2007
[9/12/07) ADDRESSING: PFA, GIS and Engineering Tech Services recommends
addressing both lots (all four buildings) off of Shields Street.
Department: Stormwater-Water-Wastewater Issue Contact: Basil Hamdan
Topic: Details
Number: 42 Created: 9/11 /2007
[9/11/07] At final please provide details for the water quality outlet structure. Place structure
within embankment to minimize visual obtrusion.
Topic: Drainage Plan
Number: 37 Created: 9/11/2007
[9/11/07] Please discuss in the drainage report how off -site flows will be handled through the
site.
Page 4
Number: 29 Created: 9/10/2007
[9/10/07] Street trees must be provided at least 30-40' on center. Please add trees from the
approved street tree list to your Shields frontage.
Number: 30 Created: 9/10/2007
[9/10/07] The plan is sufficiently detailed for hearing purposes, but you will need to call out
shrubs and all other plantings for final plan review.
Topic: Lighting Plan
Number:34 Created: 9/10/2007
[9/10/07] Fixtures DD1 and CC also need house side shields.
Department: Current Planning Issue Contact: Dana Leavitt
Topic: Plat
Number: 17 Created: 9/10/2007
[9/10/07] No comments.
Department: Engineering Issue Contact: Marc Virata
Topic: General
Number: 38 Created: 9/11 /2007
[9/11/07] The traffic study indicates that southbound vehicles will apparently pass by the
driveway entrance off Shields and enter the site from Richmond Drive. Please note that per
LCUASS requirements, Richmond Drive meets warrants for a right turn lane. Follow-up with
Traffic Operations on whether the Traffic Engineer has some concerns with the traffic study
and/or any impacts of this development to the existing traffic operations.
Number: 46 Created: 9/12/2007
✓ [9/12/07] The project should be providing a 6 foot detached walk per our arterial standards
as indicated in the conceptual review comment letter.
Topic: Plat
Number: 43 Created: 9/11 /2007
[9/11/07] Add the attached private drive maintenance note on the plat.
Number: 44 Created: 9/12/2007
[9/12/07] The plat should specify the legal entity of the two individual owners: are they
o / ma; agers of BCS LLC, owners as individuals?, etc.
n'VINumber.45 Created: 9/12/2007
Cps [9/12/07] The conceptual review comments indicated the requirement of right-of-way
dedication to a 4 lane arterial standard which would be approximately 7.5 feet. This was not
provided on the plat. Likewise a 15' utility easement be dedicated on the plat which was
Q� Iso not provided.
U
„/n Department: Light & Power Issue Contact: Alan Rutz
Topic: General
Number: 39 Created: 9/11 /2007
[9/11/07] Contact Light and Power to coordinate transformer and meter locations.
Page 3
your next submittal. Staff is likely to support this modification because there is not another
viable option, so long as the crosswalk is given ample enhancement.
Topic: Site Plan
Number: 22 Created: 9/10/2007
[9/10/07] The sidewalk connection at the south side of the Shields access needs work so
opr that it is continuous and useful and drawn to show that clearly.
Number: 23 Created: 9/10/2007
[9/10/07] Handicap accessible ramps need to be shown on the site plan. In many cases,
dipping the sidewalk may be the best way to provide access without impeding through ped
traffic. In some cases, it may make sense to switch the location of the parking space and
the loading zone. See redlines. �'�1�N=��
Number: 24 O rea�tedd:: 9/1100�/2007
[9/10/07] Please do not show utilities on the site plan, just the landscape plan and utility
plans.
Number: 25 Created: 9/10/2007
[9/10/07] Unless you are planning to put Jimmy Carter and Nelson Mandela at the top of
your light posts, please change your general notes to refer to luminaires not luminaries!
Number: 26 Created: 9/10/2007
[9/10/07] Please add a sheet index. Where is page 6 of 8?
Number: 27 Created: 9/10/2007
[9/10/07] A maximum of 40% of the residential parking can be compact, which in this case
would be 24 spaces. Total residential parking needs to be at least 60, with at least 3 HC
accessible spaces. For commercial parking, there are no minimums required, however you
must provide HC accessible spaces based on the total number of commercial spaces
provided, which in this case would be 3 not 2.
Topic: Elevations
Number: 31 Created: 9/10/2007
[9/10/07] Can you please provide a color and material sample board before the hearing?
Thanks.
re4A�. /
Number: 32 Created: 9/10/2007
[9/10/07] This project is over 40 feet tall so it needs to have a supplementary review per
i Section 3.5.1 (G)(1). There are a few extra materials that will need to be provided before
the next staff review and before the hearing. Let me know if you have any questions about
what is needed.
Number: 33 Created: 9/10/2007
[9/10/07] On page 5 of 8, please enlarge the called out dimensions on the right hand side of
the page. Aging eyes cannot make them out....
Topic: Landscape Plan
Number: 28 Created: 9/10/2007
[9/10/07] There are some scanning issues on this plan. Please correct.
Page 2
Cite of Fort Collins
STAFF PROJECT REVIEW fiee
Gha►ye
VF RIPLEY Date: 9/12/2007
401 W MOUNTAIN AVE
FT COLLINS, CO 80521
Staff has reviewed your submittal for 3425 S SHIELDS ST. MIXED USE PDP - TYPE I, and
we offer the following comments:
1ph-'�
ISSUES:
Department: Current Planning Issue Contact: Anne Aspen
Topic: General
Number: 19 Created: 9/10/2007
[9/10/07] The following departments and agencies have no issues with the proposed: GIS
(though they note that PFA is reviewing the addressing and may have comments),
Transfort, and Comcast.
Number: 18 Created: 9/10/2007
[9/10/07] The US Post Office responds as follows: Centralized delivery using a minimum of 3
centralized box units (industry type III) is required. Revise plan to show the required CBU
locations as approved by the US Postal Service. In all cases the CBUs must be located in
the public right-of-way or a designated easement. Be advised that the responsibility of
purchase and maintaining the CBUs with the concrete pads is that of the
owner/developer/builder/HOA. Prior to occupancy within the development approved mail
receptacles will be in place. Delivery Agreement will be in place prior to any delivery of mail.
Contact Bonnie Ham, Growth Coordinator, USPS
301 E. Boardwalk, FC, CO 80525 i&c B41
phone:225-4130
cell: 214-3668
fax: 225-4139 on 3-e,PJ� 3(t,
v4
Number: 20 Created: 9/10/2007
[9/10/07] Please try to arrange the drawings so that the info boxes take up less room and
the drawing itself can be larger and more legible.
Number: 21 Created: 9/10/2007
[9/10/07] Many minor comments on redlines. Please be sure to return redlines with next
submittal.
Number: 53 Created: 9/12/2007
[9/12/07] During the staff review meeting we discussed a couple of items that I want to
document here:
t, +We need to do a site visit to examine the sidewalk and related issues. Call me prior to the
hearing to arrange a time. I will coordinate with Marc, Kathleen Bracke, Tim Buchanan and
Basil. A96,
+As Linda graciously pointed out, you will need a modification of standards for the
connecting walkway standard and an enhanced crosswalk between Shields and the
residential component of the project. Please submit a draft of the modification letter with