Seeking advice from our client.
Number: 8 Created: 8/17/2007
[9126107] The response letter indicates that a note has been added, but l don't see
it.
[8117107] Wall mount light fixtures are shown on the elevations. Need to add note
that they will be down directional, shielded, etc.
Corrected — please see elevations and photometric plan
Be sure and return all of your redlined plans when you re -submit.
If you have any questions regarding these issues or any other issues related to this
project, please feel free to call me at (970) 221-6750.
Sincerely,
Shelby Sommer
Associate City Planner
Page 11
[8130107] Please revise detention calculations to reflect one 2-year release rate.
This basin defines the release rate to be .2 cfs per acre and dual release rates are
not utilized.
Detention has been solved in parking lot.
Department: Stormwater-Water-Wastewater Issue Contact: Roger Buffington
Topic: Water/Wastewater
Number: 75 Created: 101212007
[1012107] Notes P3 and P5 on overall utility do not appear to apply to this project.
Please remove.
Removed
Number. 76 Created: 101212007
[10/2/07] Revise note P4 as shown on redlined plans.
Note has been revised.
Number: 77 Created: 101212007
[10121071 Note P6 refers to Drawing P1 which was not found in utility plans.
Corrected
Number. 78 Created: 101212007
[10121071 Note P8 does not appear to apply to this project. Please remove.
Note has been removed.
Number. 79 Created. 101212007
[1012107] Revise note P9 as shown on redlined plans.
Note has been revised
Number. 80 Created: 101212007
[1012107] The backflow preventers referred to in notes P10 and PI may NOT be in
the meter vaults. Revise notes as sh7own on redlined plans.
The notes have been revised
Department: Zoning Issue Contact: Peter Barnes
Topic: Zoning
Number. 5 Created: 811712007
[9126107] Still need foundation plantings along south wall.
[81171071 Need 3 to 4 trees in the 5' landscape strip along the south lot line (Section
3.2.1(E)(4). Need foundation plantings per Section 3.2.1(E)(2)(d)
Page 10
Topic: Technical Services
Number: 81 Created: 101312007
110131071 The basis of bearings statement is incorrect. Township and Range are
incorrect.
Corrected
Number: 82 Created: 101312007
[10131071 Please check the square footage of boundary. City staff calculates 28,500
not 27,930.
Reviewing
Number: 83 Created: 101312007
[10131071 NW corner of Plat -monument not described
Corrected
Department: PFA Issue Contact: Carie Dann
Topic: Fire
Number: 54 Created: 8/31 /2007
[91281071 l apologize for not being more specific regarding my questions about
what's labeled "wall hydrant" What is in the wall behind the "wall hydrant" or "hose
bibb "? A bibcock is just a downward -facing faucet, so is this just a domestic -water
faucet on an exterior wall? In the fire service, a 'wall hydrant" is a very specific
device. A wall hydrant is typically installed in large buildings (warehouses) that need
water in close proximity to supply a sprinkler system. The fixture allows us to quickly
have water to support the FDC, particularly if there is a delay in getting a water
supply from a freestanding hydrant. In PFA's district, we might have 2-3 wall
hydrants. A 6, 000 SF building with good access and a suitable, nearby water supply
would not have a wall hydrant. If this truly is a water faucet (but I'm not sure that's
what it is), please label it that way.
[8131107] WALL HYDRANT: What is labeled the site plan (actually, it's elevations)
shows item #20 on the building as being a wall hydrant. Is this actually what it's
supposed to be? Should it actually be a sprinkler FDC? What would be the need for
having a wall hydrant, if that's what it actually is?
Please see the wording on the elevations and the cut sheet for a better explanation
of the hose-bibb.
Department: Stormwater-Water-Wastewater Issue Contact: Wes Lamarque
Topic: Stormwater
Number: 53 Created. 813012007
[10111071 The new release rate of. 11 cfs does not seem to be updated for the 100-
year storm, only the 10-year storm. Quantity detention needed for this release rate
would be over 6,000 cf, and only 2,917 cf is being provided. Please revise.
Page 9
[10131071 Please show any existing sidewalk on the west side of the alley. Truncated
domes must be installed where the sidewalk crosses the alley on both sides.
There is not an existing sidewalk on the west side of the alley.
Number: 90 Created: 101312007
[10131071 The landscaped medians along the alley should have a barrier curb on
both sides to prevent nuisance irrigation water from draining over the alley asphalt
and degrading the edge of asphalt.
Curbs have been added
Number. 91 Created: 101312007
[1013107] The minimum flowline grade allowed is 0.5 percent. The College
proposed flowline shown is 0.2 percent. See sheet C6 profile.
Corrected.
Number: 92 Created: 101312007
[1013107] Add a note to the plans stating that no part of the building foundation may
extend into the ROW on Hemlock.
Note added.
Number. 93 Created: 101512007
[1015107] Please see Technical services Comments Regarding the Plat. Lot 2
should be included on Plat Boundary area calculation. Need to also designate
maintenance of Lot 2 on the Plat.
We are reviewing with technical services and the assessor's office.
Number. 94 Created: 101512007
[1015107] Access and utility easement lines need to extend across Lot 2 to connect
to boundary with adjacent property.
See above note.
Number 95 Created: 101512007
[10151071 Need to adequately show existing grades and structures on the west side
of the alley to show if any off -site temporary construction easements will be needed
to grade and construct the alley as shown. Also needed to verify the proposed alley
design will work with existing structures. A letter of intent for any off -site easements
will be needed prior to hearing.
Alley improvements plan provided with this submittal.
Page 8
College Ave. This may require widening College in front of this site to accommodate
two left turn lanes onto Vine. This will require the access on College to be
permanently closed. Please provide a bold note on the Plat that indicates that the
City or CDOT may close the College access at the time improvements are
completed. This phase of College improvements may not affect other parcels on
College with existing access driveways ... not all accesses will likely be closed at
this time.
As per our conversation with Counsel on October 2"d, we have provided a note on
the Plat. Please see Plat.
Number: 84 Created: 101312007
[10131071 Please update the month and year on the cover sheet of the Utility Plans.
Revise the signature blocks on all sheets to remove the Current Planning title on the
bottom line. Planning will not be signing the Utility Plans.
Corrected.
Number. 85 Created: 101312007
[1013107] An off -site temporary construction easement may be needed to construct
the alley improvements. Please provide a letter of intent from the property owners or
a signed deed of dedication prior to scheduling a hearing for the project.
Please see alley improvement plan.
Number: 86 Created: 101312007
[1013107] There are still a few issues with drafting and labeling. Some line types
and hatch fills are too light and don't copy well. Please turn off the landscape layer
on the Utility Plan sheets. See redlines for clarification.
Corrected and darkened
Number. 87 Created: 101312007
[1013107] A handrail must be placed along the detention pond adjacent to the new
sidewalk. Please show/call out the hand rail on the plans and provide a detail.
A handrail has been added to the detention pond wall adjacent to the new sidewalk.
Number. 88 Created: 101312007
[1013107] Please use a darker line type for all new/proposed sidewalks and ramps in
the ROW and label them as new or proposed.
Darkened.
Number: 89
Created: 10/3/2007
Page 7
[1013107] The access driveway on College shall be constructed per LCUASS 707.
There is no pan used with this standard and the driveway is all concrete with radius
flares. The driveway must also intersect the street at 90 degrees.
[8129107] The College driveway access must be constructed per LCUASS DWG 707
with ped ramps and connecting sidewalks on both sides. Please show and call out
on the plans.
The access onto College has been changed to be 90 degrees and is to code.
Number: 50 Created: 8/29/2007
[1013107] No application has been submitted to CDOT as of 10-2-07.
[81291071 An access permit is required from CDOT. You may submit an application
to CDOT concurrently with the City review and the City will coordinate with CDOT
such that the access permit can be issued when the plans are approved.
We submitted an application to CDOT 10/3/07.
Number: 51 Created: 8/29/2007
[1013107] Street trees must be located such that they will not need to be removed
when College is widened. Please consult with Planning and locate the trees as
close to the sidewalk as possible.
[81291071 Please show the street tree locations on College on the Utility Plans. The
location of street trees on College is important such that the trees will not need to be
removed or relocated when College is widened. Please space the trees with respect
to the ultimate sidewalk location rather than centering them in the parkway between
the sidewalk and curb.
After consulting with planning, the street trees are in the appropriate places for future
street improvements.
Number: 52 Created: 8/29/2007
[10131071 Same comment
[8129107] Please revise the Site and Landscape plans accordingly to reflect all
changes requested on the Utility Plans related to sidewalks, ramps, on -site medians
etc...
Corrected on Utility Plan.
Number: 58 Created: 813112007
[1013107] Please provide a note on the Plat regarding the interim nature of the
College access as discussed in the October 2 meeting with the attorney. CDOT has
indicated to me that the conditional access permit they are providing for the College
access is revocable with only notification. No additional process will be warranted to
close this access driveway in the future when College improvements are completed.
[8131107] It is estimated that College improvements in front of this site may be
started as early as 2009 to accommodate the new Vine Drive alignment intersecting
Page 6
The note has been added.
Department: Current Planning Issue Contact: Dana Leavitt
Topic: Site Plan
Number: 36 Created: 8/29/2007
[10/2/07]
[8129107] In addition Peter Barnes's comments regarding the trash enclosure, the
interior space must be able to accommodate both trash containers and recycling
containers. Show a plan with dimensions for both length and width with containers
within structure per Section 3.2.5 of the Land Use Code.
On the elevation sheet we have included a detailed drawing of the trash enclosure,
showing that there is ample room for both a dumpster and recycling bins.
Department: Engineering Issue Contact: Randy Maizland
Topic: Engineering
Number. 33 Created: 812912007
[1013107] The alley intersection with Hemlock must be constructed per LCUASS 7-
IF, Detail 1. Please show this reconstruction on the plans. LCUASS also requires
500 feet of preliminary offske design for the alley. See redlines for additional
comments related to the alley plan and profile.
[8129107] No alley improvement design was submitted. The 20 foot alley off of
Hemlock must be improved to either 7-11 F or 7-12F and 500 feet of off -site
preliminary design must be provided. The alley intersection must also be
reconstructed to the current standard.
We have provided an alley plan and profile with this submittal.
Number: 34 Created: 8/29/2007
[1013107] The cost estimate provided is still under review at this time.
[8129107] The existing street flowline on College Avenue is not in the ultimate
location. Any new curb and gutter construction/reconstruction on College is only an
interim condition. This development will be required to escrow money for future
ultimate curb and gutter on College for the entire length of the College frontage. The
College access will be permanently removed and replaced with curb and gutter in
the future. The escrow payment will required prior to the issuance of a building
permit and will be specified in the development agreement. The developers
engineer shall prepare a cost estimate for the City to review for design and
construction.
Cost estimate revised per City's direction and included in this submittal.
Number: 39
Created: 8/29/2007
Page 5
We have spoke with Kathleen Walker several times regarding the bus shelter. We
are evaluating the impact of the shelter with our client, Advance Auto Parts.
Topic: Landscape Plan
Number: 73 Created: 9/28/2007
[9/28/07] The symbols for the existing trees and the proposed trees are very light
and difficult to read. They will not scan property. See redlines for problem areas
and other typos.
Number: 74 Created: 9/28/2007
[9/28/07] Canopy shade trees (riot ornamentals) are required in the landscape
islands on the south side of the parking lot. The small landscape island (at the
west end of the row of parking along the south side of the building) needs to be a
minimum of 8 feet wide and needs to feature a canopy shade tree.
Topic: Lighting Plan
Number: 18 Created: 8/21/2007
[9/28/07] This is looking much better. The lighting levels in the alley right-of-way are
still a bit high and need to be no more than 0.1 foot candle at 20 feet beyond the
property line. Please revisit and adjust as much as possible.
After some evaluation, we concluded that if we lower the light anymore than it
already is, and then the delivery truck would be likely to hit it since it would be out of
the line of vision. To provide some lighting to the back of the store, we have put a
light on the southwest comer of the building to replace the alley lamp post. The
lighting levels in the alley are now to City standards.
Number: 19 Created: 8/21 /2007
[9128107] The wall mounted fixtures should match the building ... tan perhaps? White
will be a stark contrast against a tan wall.
[81211071 Light pole finish color (Fixture type AA) should be a color other than red to
blend in with the site, not stand out (black, silver etc.) Wall mounted fixtures should
be in a color that matches and blends in with the building exterior.
The wall mounted fixtures have been changed to match the building color.
Topic: Site Plan
Number: 71 Created: 9/28/2007
[91281071 Several items on the site plan are very difficult to see and will not scan
properly. Please see redlines for details.
We have darken the lines on the plans so that they are easier to scan.
Number: 72 Created: 912812007
[91281071 Note #11 on the Site Plan needs to specify that the sign is subject to a
Sign Permit.
Page 4
main entry planting appears random, missing an opportunity to highlight the front
entry. It would be best to discuss this by phone rather than write out the details.
221.6225.
Left message for Clark Mapes, still waiting for a response.
Topic: Lighting Plan
Number: 96 Created: 10/7/2007
[10/7/07] Wall mounted lighting: This lighting must be cut-off with concealed lamps,
grazing the wall to highlight the masonry without creating glare.
Corrected — See elevations and photometric plan
Emergency light: Must be cut-off or downward facing. What kind of emergency is
this intended for — would it be on only in emergencies? (It appears to be more of an
everyday service light).
Please see note on plans: The Emergency Light is connected into the Building's
Emergency Battery Pack System and will come on when a power outage occurs.
Topic: Site Plan
Number: 98 Created: 10/7/2007
[10/7/07] Detention pond question: is this a vertical, 12" wall as shown? How does
the top of the wall meet adjacent paving - is it flush?
The detention pond wall is flush with paving.
Department: Current Planning Issue Contact: Shelby Sommer
Topic: Architectural Elevations
Number: 24 Created: 8/28/2007
[9128107] The Hemlock facade looks a little better as you have the changes in plane
and texture but still isn't designed with an appropriate pedestrian scale. Consider
items such as treillage with vines or windows to add interest along this long wall.
We have added spandrel glass windows along the Hemlock Street elevation to give
the facade an appropriate pedestrian scale.
Topic: General
Number: 70 Created: 9/17/2007
[1011107] Transfort will provide more specific$ regarding bus shelter requirements
soon. Design standards are included in the packet with your redlines.
[9117107] Kathleen Walker (TransFort): Bus accessibility (bus stop/shelter) is
required. Please contact Kathleen -at 970-221-6621 or kwalker@fcgov.com for more
information.
Page 3
Replace The EIFS fascia and banding with masonry. As a prominent element, this
should include brick, and could include smooth or ground face tinted block courses.
See above.
Make block panels smooth -face: Smooth face block would be more appropriate
above the wainscot, contributing to a more urban (less suburban) character.
Masonry fascia that includes a brick course would help integrate these panels.
The block on the building has been changed to smooth face block.
Glass block windows, north side of building: The fagade facing Hemlock Street
lacks any animating features. Glass block windows, especially near the College
Avenue corner of the building, would meet this need without compromising the
apparent need to maximize interior functions.
We have added spandril glass windows to the Hemlock Street facade to give it a
pedestrian friendly perspective.
Aluminum Storefront Color. Assuming this system needs to be red for the user, a
more subdued colonial red than the pure red specified.
Acknowledged.
Support post at entry: Other stores by this user have a support post at the entry
overhang. Is there a post? Drawings do not identify one. This post would be an
opportunity for a significant steel or masonry feature.
We have added a support post of steel.
Drawings: The elevations don't match/are not clear. The south elevation apparently
should show a raised parapet beyond, per the north elevation. Likewise, the east
elevation should apparently show the same parapet beyond.
Corrected
Electrical equipment. Should be painted to match masonry. (Same note as
downspouts).
Corrected
Topic: Landscape Plan
Number: 99 Created: 10/7/2007
[10/7/07] The assortment of plantings includes several plants ill -suited for the
situations. These include Black Ash, Viburnum Cardinal Candy, Purple Ice Plant,
Rocky Mountain Sumac, and Hydrangeas. Also, the assortment of plants at the
Page 2
MEAN STAFF PROJECT REVIEW
City of F� omens
Lucy Dinneen/Kay Stallworthy Date: 10/07/2007
Cadence Development LLC
8480 E. Orchard Rd. Ste#6900
Greenwood Village, CO 80111
Staff has reviewed your submittal for ADVANCE AUTO PARTS PDP - TYPE I, and
we offer the following comments:
ISSUES:
Department: Advance Planning Issue Contact: Clark Mapes
Topic: Architectural Elevations
Number: 97 Created: 10/7/2007
[10171071 Building plans don't adequately reflect initial and previous conversations
with the applicant re distinct identity described for this part of the city, in new
development and redevelopment projects. This identity will derive mainly from the
traditional character of Downtown combined with contemporary urban semi -industrial
characteristics, avoiding typical suburban character as described in the North
College Plan previously sent and discussed.
The artificial stucco, concrete block, and econo-utility brick do not contribute to this
local identity. Brick, as a material, works very well, but simply needs to be specified
in classic standard size rather than utility size. The precast sills also work very well.
Following are suggestions to meet the standards. A meeting to discuss the building
design maybe warranted.
The brick is now standard size rather than utility size.
Replace EIFS panels with brick: The EIFS panels should be replaced. with brick to
create a stronger building mass at the front entry, juxtaposed with the rest of the
building. A sign frieze could be created with masonry courses.
The EIFS has been replaced with masonry, smooth block that matches and blends
with the rest of the building.
if the additional brick is a problem, perhaps the use of brick as a wainscot should be
reconsidered — since much of that will be fronted by landscaping, that may be the
place for split face block, with brick used for higher visibility parts. The brick ribs are
a positive and highly visible element, so if the wainscot were block, the brick ribs
could be integrated by wrapping the wainscot around them.
Acknowledged.