April18,2008
Mr. Ted Shepard
City of Fort Collins
Planning and Zoning
P.O. Box 580
Fort Collins, CO 80521
RE: Harmony Technology Park 4a' Filing
Custom Blending
Dear Willkomm,
The Fort Collins — Loveland Water District and the South Fort Collins Sanitation District have reviewed
the above mentioned project and submit the following comments.
There is a discrepancy in the water tap size between the drawings (2 inch) and the tap application
(1'/2 inch).
The parcel number needs to be provided on the tap application.
Previously approved drawings indicate a 24 inch water line from Rock Creek to Precision Drive
in Technology Parkway.
Please do not hesitate to contact me at 226-3104, ext. 104, if you have any questions or require additional
information.
Respectfully,
M�Zry W. Farrill, P.E.
District Engineer
xc: Mr. Michael D. DiTullio, District Manager
Mr. Anthony Willkomm, Stantec Inc.
5150 Snead Drive, Fort Collins, CO 80525 Phone (970) 226-3104 Fax (970) 226-0186
2. On the Lighting Plan, be sure to include a quantity for the number of fixtures, not
just the lamps per fixture.
Be sure and return all of your redlined plans when you re -submit.
If you have any questions regarding these issues or any other issues related to this project,
please feel free to call me at (970) 221-6750.
Sincerely:
P•-jc
Ted Shepard
Chief Planner
Page 4
t
Topic: Utility Plans
Number: 50 Created: 5/7/2008
[5/7/08] Why is the storm drainage being discharged into the pond through a subdrain
system and a level spreader?
Department: Stormwater-Water-Wastewater Issue Contact: Roger Buffington
Topic: WaterMastewater
Number: 16 Created: 2/19/2008
[5/8/08]
[2/19/08] Information pertaining to water service size is conflicting in various spots.
Number: 53 Created: 5/8/2008
[518/08] Water main from Rock Creek to Precision to be 24".
Number: 54 Created: 5/8/2008
[5/8/08] Add 24" butterfly valve at point of connection near Rock Creek.
Number: 55 Created: 5/8/2008
[5/8/08] Use joint restraint for the water main lowerings rather than thrust and gravity blocks.
Provide calculations on the required restrained lengths on each side of the lowerings and
label clearly on the plans. Add a note (as outlined in the redlines) regarding MEGALUGS or
pre -approved equal.
Number: 56 Created: 5/8/2008
[5/8108] Label lengths of pipe between valves, fittings, etc, etc.
Number: 57 Created: 5/8/2008
[5/8/08] Add butterfly valve, air release valve and tracer wire (2) details.
Number: 58 Created: 5/8/2008
[5/8/08] See redlined plans for other comments.
Department: Zoning Issue Contact: Jenny Nuckols
Topic: Zoning
Number: 5 Created: 2/7/2008
[4/24/08]
[2/7/08] Please show building envelope, footprint and dimensions on site plan.
4-24-08 Building dimensions are still not shown on the site plan
Number: 7 Created: 2/8/2008
[4/24/08]
[218/08] Add note to landscape notes regarding installation of landscaping prior to issuance
of CO.
4-24-08 Landscape assurance note needs to include all landscaping, not just that in the
drainage tract, but all landscaping on that site.
Comments from Current Planning
1. Please consider adding a small cluster of evergreen trees south of the proposed
tanks.
Page 3
I
Topic: General
Number: 10 Created: 2/8/2008
[5/6/08] Carried over for reference.
[2/8/08] The offsite pond (Pond B) shown on the northwest corner of Technology Parkway
and Rock Creek Drive is considered development and as such the street frontages abutting
Pond B needs to be obligated for. Sidewalk along Technology Parkway and Rock Creek
Drive abutting Pond B would need to be escrowed for if not being built at this time. If a
repay was filed with the City for the construction of Rock Creek Drive, the frontage abutting
Pond B would also be required.
Number: 11 Created: 2/8/2008
[5/6/08] Carried over for reference.
[2/8/08] The offsite pond (Pond B) should have a 9 foot utility easement dedicated along
Technology Parkway and Rock Creek Drive.
Number: 44 Created: 5/2/2008
[5/2/08] Please note that the Engineering Development Review Manager has determined
that there is $300 owed in TDR Fees from the PDP.
Number: 49 Created: 5/7/2008
[5/7/08] As a heads -up, the additional width in Technology Parkway that encompasses the
center turn lane which was previously a median, is not reimbursable from street oversizing.
Topic: Plat
Number: 37 Created: 2/20/2008
[5/7/08] Technical Services has the following revised comments:
1. Boundary and legal close but have minor differences.
2. Remove all references to Cambridge Avenue.
[2/20/08] Technical Services has the following comments:
1. No north arrow and scale plat.
2. Plat closes, legal does not match plat at curve C7. Area is good.
3. Show how all the adjoining streets were dedicated.
4. Minor line over text issues.
5. Looks good as a preliminary plat.
6. Who owns and maintains Tract A?
Number: 46 Created: 5/7/2008
[5/7/08] The "sight visibility easement' specified on the plat and other documents should be
called out as a "sight distance easement' on the various documents. In addition, please
provide our standard sight distance easement language on the plat.
Department: Stormwater-Water-Wastewater Issue Contact: Basil Harridan
Topic: Detention Pond Landscaping
Number: 45 Created: 5/6/2008
[5/6/08] Thank you for providing adequate landscaping for the detention pond on Tract A.
The lower portion of the pond is to be planted with a wetland seed mix, will there be
sufficient water in this pond to sustain wetland vegetation? If not what would be done to
address that. `
Page 2
STAFF PROJECT REVIEW
City of Fort Collins
BHA Design, Inc Date: 5/12/2008
1603 Oakridge Drive -
Fort Collins, CO 80525
Staff has reviewed your submittal for HARMONY TECH PARK, 3RD FILING, CUSTOM
BLENDING PDP - TYPE I AND FINAL PLANS, and we offer the following comments:
ISSUES:
Department: Engineering Issue Contact: Marc Virata
Topic: Construction Drawings
Number: 15 Created: 2/19/2008
[5/6/08] Please remove the reference to "plus added median" below the typical cross
section on Sheet C-003. Is the use of the broken yellow line for the inside of the reversible
lane ideal given that there are no turning movements currently to necessitate entering the
center lane?
[2/19/08] With the median on Technology Parkway intended to have landscaping per C-003
then additional information at the time of final will be required, such as landscaping plan,
subdrain systems, etc.
Number: 32 Created: 2/20/2008
[5/6/08] The applicant's response is fine, though interestingly, I'm now realizing that west of
Technology Parkway may not necessarily be a public street. Maybe a note on the
construction plan should be provided indicating that Precision Drive may or may not develop
as a public street west of Technology Parkway. Information shown for reference only.
[2/20/08] For the future Precision Drive section please provide horizontal curve data.
Number: 33 Created: 2/20/2008
[5/6/08] See response to #32.
[2/20/08] For the future Precision Drive section, please clarify the profile view information,
the lines aren't apparent as which might be proposed, existing, or other.
Number: 47 Created: 5/7/2008
[5/7/08] Please update the details in LCUASS, many of the details are not the current
version.
Number: 48 Created: 5/7/2008
[5/7/08] The typical road sections sheet seems to have the Precision Drive cross section
shown incorrectly at the future sidewalk would be in the 11' parkway delineation.
Number: 51 Created: 5/7/2008
[5/7/08] Please add additional spot elevations at the PI per LCUASS 7-28.
Number: 52 Created: 5/7/2008
[5/7/08] The use of a cross pan at the high point of a flowline (Tech Parkway and Precision)
is odd and technically not to standard. Can itjust be eliminated? Perhaps in general it
might be better not to build the curb return at the west leg of this intersection since it may
not be a public street or a street for that matter with future development.