HomeMy WebLinkAboutMORNINGSTAR ASSISTED LIVING & MEMORY CARE - FDP - FDP130055 - SUBMITTAL DOCUMENTS - ROUND 1 -Enclosure Detail on sheet 2. See redlines. RESPONSE: Text size increased. Comment Number: 36 Comment Originated: 10/15/2013 10/15/2013: Please mask the text marked on sheet 3. See redlines. RESPONSE: Text has been masked. Department: Transportation Planning Contact: Emma McArdle, 970 224-6197, emcardle@fcgov.com Topic: General Comment Number: 1 Comment Originated: 09/09/2013 09/09/2013: Thank you for providing the bus stop as I requested in the Conceptual Review. Please make a change to it for me though, the stop needs to be connected to the curb with a 5' wide path, please add a 5' path from the curb to the sidewalk on the rear of the bus stop to accommodate this. Please feel free to contact me if you have any questions. RESPONSE: 5' path has been added as requested. Department: Water Wastewater Engineering Contact: Roger Buffington, 970-221-6854, rbuffington@fcgov.com Topic: Construction Drawings Comment Number: 4 Comment Originated: 10/15/2013 10/15/2013: Fire hydrant must be in a utility easement. RESPONSE: The utility easement has been adjusted based on the revised hydrant location and is shown on the Plat Topic: Landscape Plans Comment Number: 1 Comment Originated: 09/03/2013 09/03/2013: Adjust plantings to provide the required separation distances from water/sewer lines. RESPONSE: The landscape plan has been adjusted to provide the required separation distances from utility lines. 10/15/2013: Is the found #4 rebar with a yellow plastic cap stamped LS 14833 in the legend, supposed to be LS 14823? See redlines. RESPONSE: Plat corrected Comment Number: 24 Comment Originated: 10/15/2013 10/15/2013: Please provide current acceptable monument records for the aliquot corners shown. RESPONSE: Plat corrected Comment Number: 25 Comment Originated: 10/15/2013 10/15/2013: Please move the Point Of Commencement & Point Of Beginning as shown on the boundary. See redlines. RESPONSE: Plat corrected Comment Number: 26 Comment Originated: 10/15/2013 10/15/2013: Please change the direction of the Basis Of Bearings shown along the section line, to match the Basis Of Bearings Statement. See redlines. RESPONSE: Plat corrected Comment Number: 27 Comment Originated: 10/15/2013 10/15/2013: Please change the curve/line tables so the data reads the same direction as in the legal description. See redlines. RESPONSE: Plat corrected Comment Number: 28 Comment Originated: 10/15/2013 10/15/2013: Please make note to the effect that all easements shown outside of the boundary of the plat are existing easements. If that is not the case, then "to be dedicated by separate document, Reception No. " should be added to the text identifying the easement. RESPONSE: All easements shown outside of the boundary of the plat are existing Comment Number: 29 Comment Originated: 10/15/2013 10/15/2013: There are line over text issues. See redlines. RESPONSE: Plat corrected Comment Number: 30 Comment Originated: 10/15/2013 10/15/2013: Please label the dashed lines shown at the northeast comer of the property. See redlines. Comment Number: 7 Comment Originated: 09/04/2013 10/15/2013: Reminder for final compliance review. RESPONSE: The maintenance of the western channel has been noted in the Final Drainage Report. MVG will be responsible for their half of the channel maintenance starting at the common property line. 09/04/2013: Please provide a maintenance agreement for the swale that is shared by the two properties. If an agreement can not be formalized, please provide a maintenance obligation within the drainage report that lays out the responsibilities of the Developer. RESPONSE: See response above Comment Number: 8 Comment Originated: 10/15/2013 10/15/2013: Please label all slopes min. 4:1. RESPONSE: Slopes have been noted as being 4:1 min. Department: Technical Services Contact: Jeff County, 970 221-6588, jcounty@fcgov.com Topic: Building Elevations Comment Number: 11 Comment Originated: 10/14/2013 10/14/2013: No comments. RESPONSE: Acknowledged. Topic: Construction Drawings Comment Number: 12 Comment Originated: 10/14/2013 10/14/2013: Please correct the spelling of "Southwest" in the sub4itle on sheet 1. See redlines. RESPONSE: Spelling corrected Comment Number: 13 Comment Originated: 10/14/2013 10/14/2013: Please change the Township number from "6" to 7" in the sub -title on sheet 1. See redlines. RESPONSE: Township corrected Comment Number: 14 Comment Originated: 10/14/2013 10/14/2013: Please correct the elevation of benchmark 8-94. See redlines. RESPONSE: Benchmark corrected Topic: Landscape Plans Comment Number: 15 Comment Originated: 10/14/2013 10/14/2013: No comments. side of the building and a 28' EAE along the east side of the building. These easements are reflected on the Final Plat. Comment Number: 3 Comment Originated: 09/03/2013 09/03/2013: HYDRANT PLACEMENT The relocation of the hydrant on the SE corner of the building, shall be reviewed in future plans submittals. One additional hydrant on the west side of the building is also needed. RESPONSE: The existing fire hydrant at the SE corner of the building has been shown to be relocated slightly to the west in order to provide standard clearance from the back of the sidewalk. An additional hydrant has been added in the northern parking lot as previously discussed. Further discussion is required on the proposed hydrant location on the north side of the building. Comment Number: 6 Comment Originated: 10/15/2013 10/15/2013: EMERGENCY GENERATOR The storage and use of diesel fuel or propane, for the purposes of supplying an emergency generator, shall comply with any applicable sections of Chapter 34 of the International Fire Code on Flammable and Combustible Liquids. Any building, structure, or shelter housing the generator shall be properly signed and labeled. A separate permit is required if the fuel source is provided by an AST. Spill control may be required; TBD at time of building permit. RESPONSE: Acknowledged. Comment Number: 7 Comment Originated: 10/15/2013 10/15/2013: SEPARATE PERMITS FYI only - Separate permits are required for fire sprinkler and alarms systems. Separate permits are also required for kitchen hood systems, Above -ground Storage Tanks and BDA antenna if required. These are all deferred submittals, which can be applied for, if applicable, after the building permit is issued. RESPONSE: Acknowledged. Department: Stormwater Engineering Contact: Jesse Schlam, 970 218 2932, Ischlam@fcgov.com Topic: Erosion Control Comment Number: 1 Comment Originated: 08/27/2013 10/07/2013: Repeat RESPONSE: An Erosion Control Plan and separate Erosion Control Report has been added for this submittal. RESPONSE: Tree protection note #7 has been removed. Comment Number: 5 Comment Originated: 09/06/2013 09/06/2013: Consider using lanceleaf cottonwood or plains cottonwood in place of the narrowleaf cottonwood. The narrowleaf cottonwood produces and abundance of root suckers that can causes maintenance problems. RESPONSE: Narrowleaf Cottonwood has been replaced with Lanceleaf Cottonwood. Comment Number: 6 Comment Originated: 10/11/2013 10/11/2013: Update Landscape note number 1 to include these distances found in LUC3.2.1 K. 40 feet from street lights for canopy shade trees 15 feet from street lights for ornamental trees 10 feet from water and sewer mains 6 feet from water and sewer service lines 8 feet from driveways 20 feet from signs and traffic control devices RESPONSE: Landscape Note #1 has been revised to include the information provided above. Check street tree locations for compliance with these separations. A proposed street tree along Lockwood appears to be closer than 40 feet from the light. RESPONSE: Street tree locations have been checked for compliance with required separations. Any revisions that were necessary have been made. Comment Number: 7 Comment Originated: 10/11/2013 10/11/2013: The street tree just to the north of the north of the curb cut off Lockwood is very close to the intersection. Review for deletion of this tree. RESPONSE: There are no proposed trees to the north of the curb cut off Lockwood. Comment Number: 8 Comment Originated: 10/11/2013 10/11/2013: Please add these street tree notes: Street trees shall be installed by the developer at time of CO, unless time of year limits tree planting, in which case street trees shall be planted within than 6 months of CO .The Developer shall replace dead or dying street trees after planting unit final inspection and acceptance for maintenance by the City of Fort Collins Forestry Division. All street trees must be established, an approved species and of acceptable condition prior to acceptance. Street tree locations RESPONSE: As discussed, this will be addressed at Final. Comment Number: 8 Comment Originated: 09/04/2013 10/15/2013: The following was added to the comment below but apparently was added after the final letter was sent. "In checking with the City Engineer and Traffic Engineer, the striping for Lochwood and the current indication of where parking is allowed is going to remain. The amount of patching south of the start of the no parking along Lochwood is required to be half a lane width. For the area north where parking is allowed, a two foot patch is allowed." Note that the street patching note is still needed and the information can be shown at time of final, but the patching should follow the additional information shown above. RESPONSE: The standard street patching note is shown on the drawings and the limits of the sawcut relative to the no parking zones has been indicated. 09/04/2013: The construction plans should be showing the removal of the existing attached sidewalk/hollywood curb where detached sidewalk is being installed and show proposed patching along Lochwood Drive for the installation of the new (presumably vertical) curb and gutter. In checking with the City Engineer and Traffic Engineer, the striping for Lochwood and the current indication of where parking is allowed is going to remain. The amount of patching south of the start of the no parking along Lochwood is required to be half a lane width. For the area north where parking is allowed, a two foot patch is allowed. Add the City's standard note regarding limits of street repair: Limits of street cut are approximate. Final limits are to be determined in the field by the City Engineering Inspector. All repairs to be in accordance with City street repair standards. RESPONSE: A Demolition Plan has been added to the set that indicates the existing curb and sidewalk along Lochwood to be removed. Comment Number: 11 Comment Originated: 09/06/2013 10/15/2013: The submitted variance request was approved on 10/15 after review and consultation with Traffic Operations. Please indicate the approval of the variance on the construction plan set notes. RESPONSE: Acknowledged. The variance approval has been added to the General Notes. 09/06/2013: A variance request to the requirement of constructing a right turn lane from Horsetooth to Lochwood is required. Staff has indicated preliminary support in granting the variance, however. RESPONSE: Acknowledged. walkway, may be required" RESPONSE: As agreed, the walk will remain and will be within a 12' Public Access Easement. Comment Number: 22 Comment Originated: 10/18/2013 With the fencing detail; consider further embellishment of the wood fence design by providing a center trim piece and trim wrap (see redlines) so that this fencing, adjacent to the existing neighborhood to the west, is further articulated and further reduced to a human scale through more detailed articulation. RESPONSE: The fence detai! has been revised as requested. Please see Detail, Sheet 2 of 3. Comment Number: 23 Comment Originated: 10/18/2013 With the trash enclosure detail, please add a top screen such as a wood arbor trellis detail over the top of the enclosure so that the view of the trash is screened from above as well as the sides. This is intended to address comments from the neighborhood meeting. RESPONSE: Detail has been updated as requested on Sheet 2 of 3. Comment Number: 24 Comment Originated: 10/18/2013 Please provide a material detail and specification for the retaining wall. Because the retaining wall is a prominent feature needed to accommodate the placement of the proposed use and proposed building footprint, staff recommends that the wall material be designed with a patterned modular wall system with a field stone appearance similar to the main building, as opposed to a more utilitarian running bond pattern typically seen in commercial developments. RESPONSE: Included with the resubmittal is a cut sheet indicating the wall type and color. In addition, the following note has been placed on the site plan, wall elevations and utility Plans: "Retaining wall to be Keystone Half Century Ashlar or approved equal utilizing Half Century and Century units in Colorado Blend color." Topic: Landscape Plans Comment Number: 3 Comment Originated: 09/04/2013 The landscape plan needs to be reformatted. Plants are not readable at 1:30. Tree labels at tree centers are not readable and are awkward at 90 degrees. Comment Number: 15 Comment Originated: 10/15/2013 Site Details --The trash enclosure detail does not match the site plan. On the site plan, it does not appear that the interior of the enclosure is big enough to provide access through to the recycling bins. RESPONSE: The detail has been revised. Comment Number: 16 Comment Originated: 10/15/2013 The trash pick up time note needs to be updated to include deliveries and specific hours need to be listed. RESPONSE: The note has been adjusted to add hours of operation for deliveries and pick-up times. Comment Number: 17 Comment Originated: 10/15/2013 Landscape Plan --The plan is very difficult to read, ground cover and mulch patterns, line weights, scale of drawing, and line tones. Difficult to see existing trees and proposed utilities. Plan appears to have several utility conflicts and light pole conflicts. Resolution of tables and charts is poor and difficult to read. RESPONSE: The following changes have been made to resolve the legibility issues: 1. The landscape plans have been changed to 1 "=20' scale 2. The hatches have been lightened and moved to the back of other line work. 3. Some plant symbols have been revised to make them lighter. 4. Existing trees and proposed utilities have been darkened. All utility, light pole conflicts and table/chart issues have been resolved. Comment Number: 18 Comment Originated: 10/15/2013 Landscape Plan --Show existing neighborhood sidewalk as solid line. Turf is shown on top of the walk as well as an austrian pine. Consider more native hybrid ornamental variety in areas where serviceberry is used. Consider use of additional small evergreen trees in addition to tannebaum species. Staff is advocating for small evergreen tree groupings in appropriate areas along building foundations, as many past developments have relied too heavily on deciduous material. RESPONSE: The existing sidewalk line work has added to the plans. The turf has been revised so as not to cover the sidewalk. The Amur Maple and Skyrocket Juniper have been added to the plan in order to provide additional ornamental and evergreen variety. Community Development and Neighborhood Services 281 North College Avenue PO Box 580 Fort Collins, CO 80522 970.221.6750 970.224.6134 -fax kgov. corn/developmentreview October 18, 2013 Cathy Mathis TB Group 444 Mountain Ave. Berthoud, CO 80513 RE: Morningstar Assisted Living & Memory Care, PDP130024, Round Number 2 Please see the following summary of comments from City staff and outside reviewing agencies for your submittal of the above referenced project. If you have questions about any comments, you may contact the individual commenter or direct your questions through the Project Planner, Jason Holland, at 970-224-6126 or jholland @fcgov.com. Comment Summary: Department: Current Planning Contact: Jason Holland, 970-224-6126, jholland@fcgov.com Topic: General Comment Number: 10 Comment Originated: 10/15/2013 Elevations-- Please provide color paint samples on the detail sheet for the siding scheme and clarify whether the shingle siding is stained or painted and specify the color with a graphic sample. Please also clarify the site wall material, color and pattern. RESPONSE: The elevation sheets have been revised and incorporate the color palate for the proposed elevations. As discussed with city staff, the final colors may vary slightly based upon final Owner and Architect approval at time of construction. The colors proposed will coordinate with final selection of the stone, shingles and metal roofing selections. Comment Number: 11 Comment Originated: 10/15/2013 Elevations --The base course required with the building design is very low to the