HomeMy WebLinkAboutPURA VIDA PLACE - PDP - 4-11 - CORRESPONDENCE - (3)Number: 9 Created: 2/9/2011
[2/9/111 per Sec. 4.9(E)(1)(g) of the land use code, a flat pitched roof isn't allowed.
Minimum roof pitch must be 2:12 and maximum is12:12. The roof pitch will have to be
changed to comply, or a modification will be needed.
Number: 10 Created: 2/9/2011
[2/9/11] Need to show building height dimension on elevation drawings.
Number: 11 Created: 2/9/2011
[2/9/11] Need to label the species of each tree/plant/shrub in the landscape areas.
Number: 12 Created: 2/9/2011
[2/9/11] Need an elevation drawing of the trash enclosure, showing height and materials.
Number: 13 Created: 2/9/2011
[2/9/11] Need to add a note on the plan that all roof -top or ground mounted mechanical
units will be screened from view from street and adjacent properties.
Be sure and return all of your redlined plans when you re -submit.
If you have any questions regarding these issues or any other issues related to this project,
please feel free to call me at (970) 221-6750.
Sincerely:
T
Ted Shepard
Chief Planner
Page 7
Number: 20 Created: 2/22/2011
[2/22/11] Please provide 2 sub -basins on the drainage plan, a north and a south basin
quantifying the flows that travel north and south.
Number: 21 Created: 2/22/2011
(2/22/11] Please provide a basin summary table on the drainage plan.
Number: 22 Created: 2/22/2011
[2/22/11 ] Please fix the existing spot elevations around the perimeter of the site so they can
be read.
Department: Stormwater-Water-Wastewater Issue Contact: Roger Buffington
Topic: Water/Wastewater
Number: 23 Created: 2/22/2011
[2/22/11 ] Provide water service sizing calculations for the 2-inch domestic water service.
Number: 24 Created: 2/22/2011
[2/22/11 ] If the existing sewer service is a 4-inch service and needs to be abandoned, the
proposed 6-inch sewer service could be installed at that location by cutting the existing
sewer and installing an 8 x 6 wye or tee fitting at that location.
Number: 25 Created: 2/22/2011
[2/22/11] If a clean -out on the proposed sewer service falls in a paved area, a traffic -rated
clean -out will be required. Include the Std Detail 15 for the traffic -rated clean -out.
Number: 26 Created: 2/22/2011
[2/22/11] A locator station and tracer wire will be required for the PVC fire line. Include Std
Details 25 and 30.
Department: Zoning Issue Contact: Peter Barnes
Topic: Zoning
Number: 5 Created: 2/9/2011
[2/9/11] The parking stall lengths are shown on the site plan, but I don't see the stall widths.
They need to be shown as well.
Number: 6 Created: 2/9/2011
[2/9/11] There needs to be sidewalk ramps by the handicap parking spaces.
Number: 7 Created: 2/9/2011
[2/9/11] A 6' tall wood fence along the side lot lines abutting the parking area is required.
The site plan labels an existing wood fence, but doesn't indicate the height.
Number: 8 Created: 2/9/2011
[2/9/11] Need to show building footprint dimensions on site plan, or show a building
envelope line with dimensions.
Page 6
Number: 16 Created: 2/22/2011
FIRE DEPARTMENT CONNECTION
Fire department connections shall be installed remote from the buildings or in an approved
location, and located on the street or fire lane side of buildings, fully visible and recognizable
from the street or nearest point of fire department vehicle access or as otherwise approved
by the fire code official.
PLEASE NOTE: PFA will require a remote FDC (not an on -building FDC) be installed near
the curb face of Laurel Street. For an idea of what this will look like, there's an example
directly across Laurel Street, the FDC servicing Parmalee Hall.
2006 International Fire Code 912.2 and PFA Fire Prevention Bureau Policy
Number: 17 Created: 2/22/2011
KEY BOXES REQUIRED
Poudre Fire Authority requires a key box ("Knox Box") to be mounted in approved location(s)
on every new building equipped with a required fire -sprinkler system or fire -alarm system.
Knox Boxes are required to be installed approximately 60 inches above grade and no higher
than 72 inches above grade. 2006 International Fire Code 506.1
Number: 18 Created: 2/22/2011
WATER SUPPLY
Fire hydrants, where required, must be the type approved by the water district having
jurisdiction and the Fire Department. Hydrant spacing and water flow must meet minimum
requirements based on type of occupancy. Minimum flow and spacing requirements include:
• Commercial and multi -family dwellings 1,500 gpm at 20 psi residual pressure, spaced
not further than 300 feet to the building, on 600-foot centers thereafter
• Residential within Urban Growth Area, 1,000 gpm at 20 psi residual pressure, spaced
not further than 400 feet to the building, on 800-foot centers thereafter
• Residential outside Urban Growth Area, 500 gpm at 20 psi residual pressure, spaced
not further than 400 feet to the building, on 800-foot centers thereafter.
— These -requirements -may -be -modified -if buildings-are-equipped-with-automaticfire-sprinkler-- -----
systems.
PLEASE NOTE: Three hydrants meet the distance requirement: across Laurel Street
(Parmalee Hall, and in the northeast quadrant of Laurel and Whitcomb streets, and Laurel
and Sherwood streets.
2006 International Fire Code 508.1 and Appendix B
Department: Stormwater-Water-Wastewater Issue Contact: Roger Buffington
Topic: Landscape Plan
Number: 27 Created: 2/22/2011
[2/22/11] Show proposed sewer service on landscape plan and adjust tree location to
provide required separation.
Department: Stormwater-Water-Wastewater Issue Contact: Wes Lamarque
Topic: Stormwater
Number: 19 Created: 2/22/2011
[2/22/11] Documentation is needed in the drainage report showing that the proposed sub -
basin draining into the alley has equal to or less impervious area and flows.
Page 5
addition to normal electric development charges, the costs to relocate the electric facilities
will be the responsibility of the developer or builder.
Number: 3 Created: 2/9/2011
[2/9/11] If a fire booster pump is required, please contact Light & Power Engineering (970-
221-6700) early in the design of the electric system for the building.
Number: 4 Created: 2/9/2011
[2/9/11] Each unit must have its own electric meter, and the meters must be outdoors.
Please coordinate the location of the transformer and other electric utility facilities with Light
& Power Engineering.
Topic: Utility Plan
Number: 2 Created: 2/9/2011
[2/9/11 ] The existing electric utility facilities are not shown on the utility plan (they should
be). However, they are shown (some inaccurately) on the architectural site plan.
Department: PFA
Topic: Fire
Number: 14
REQUIRED ACCESS
Issue Contact: Carle Dann
Created: 2/22/2011
Fire access roads (fire lanes) shall be provided for every facility, building or portion of a
building hereafter constructed or moved into or within the PFA's jurisdiction when any
portion of the facility or any portion of an exterior wall of the first story of the building is
located more than 150 feet from fire apparatus access as measured by an approved route
around the exterior of the building or facility. This fire lane shall be visible by painting and
signage, and maintained unobstructed at all times. A fire lane plan shall be submitted for
approval prior to installation. In addition to the design criteria already contained in relevant
—standards-and-policies,-any-new fire -lane -must -meet -the -following -general -requirements:- --
❑ Be designed as a flat, hard, all-weather driving surface (asphalt or concrete) capable of
supporting fire apparatus weights. Compacted road base shall be used only for temporary
fire lanes or at construction sites.
❑ Have appropriate maintenance agreements that are legally binding and enforceable.
❑ Be designated on the plat as an Emergency Access Easement.
❑ Maintain the required minimum width of 20 feet throughout the length of the fire lane
(26 feet on at least one long side of the building when the structure is three or more stories
in height).
If the building is equipped throughout with an approved automatic fire -sprinkler system, the
fire code official is authorized to increase the dimension of 150 feet.
PLEASE NOTE: We need to address and resolve this issue of emergency vehicle access.
The north side of the structure, as well as most of the west and east sides, is out of access
due to no drive access to the parking lot. The farthe
250 feet from Laurel Street. We cannot count on the
2006 International Fire Code 503.1.1, 503.2.3, 503.3
Number: 15
SPRINKLER REQUIREMENTS
This proposed building shall be fire sprinklered.
2006 International Fire Code Section 903
st point of the first -floor exterior is about
alley as an access point.
, 503.4 and Appendix D
Created: 2/22/2011
Page 4
Number: 58 Created: 2/28/2011
[2/28/11] Must be in Engineering Scale.
Number: 60 Created: 2/28/2011
[2/28/11] Project is not located on the vicinity map.
Topic: Utility Plan
Number: 39 Created: 2/23/2011
[2/23/11] Scanning issues, see redlines and comment #34. Sheet 6's sport elevations were
impossible to read.
Number: 40 Created: 2/23/2011
[2/23/11] Please label and dimension all row and easements and whether they are existing
or proposed.
Number: 41 Created: 2/23/2011
[2/23/11] Please label and dimension all existing and proposed sidewalks. All onsite
sidewalks must be a minimum of 4' wide.
Topic: Utility Plan - Cover
Number: 36 Created: 2/23/2011
[2/23/11] Please remove the word "final" from the final utility plan title.
Number: 37 Created: 2/23/2011
[2/23/11 ] The index indicates that a plat was included in the plan set for reference, however,
none was to be found. Either include the plat or remove it from the project title.
Topic: Utility Plan - Sheet 3
—Number:-42— — ----- - Created:-2/23/2011—------
[2/23/11] Please label the existing wood walls along Laurel in the row and the 15' LIE are to
be removed.
Topic: Utility Plan - Sheet 6
Number: 44 Created: 2/23/2011
[2/23/11] Show existing and proposed contours plus an additional existing or proposed
contour for a minimum of 50' offsite.
Topic: Utility Plan - Sheet 9
Number: 49 Created: 2/28/2011
[2/28/11] See redlines. Final comments on detail sheet to be given in Final Compliance.
Department: Light & Power Issue Contact: Doug Martine
Topic: Light & Power
Number: 1 Created: 2/9/2011
[2/9/11] Power is available from an existing Tx 6' fiberglass vault adjacent to the alley
approximately 50 ft. east of the west property line. This vault is oriented such that the 6'
direction is north -south, so it will not fit in the planned island in the parking lot. Rotating this
vault will cost approximately $8,000. There are also other electric facilities on this lot. In
Page 3
Number: 43 Created: 2/23/2011
[2/23/11] This project must construct a 6' sidewalk along the entire frontage. Any tapering
to meet existing conditions must occur offsite and use radii rather than angle points. Any
sidewalk width added must be done in 4' min increments. Anything less than that requires
that the existing sidewalk be removed and reconstructed to the proposed width.
Topic: Landscape Plan
Number: 54 Created: 2/28/2011
[2/28/11] Please label and dimension all existing and proposed row and easements.
Number: 55 Created: 2/28/2011
(2/28/11] Please add the sight distance note from the plat.
Number: 56 Created: 2/28/2011
[2/28/11 ] Project title does not match the plat.
Number: 59 Created: 2/28/2011
[2/28/11] Must be in Engineering Scale.
Topic: Plat
Number: 45 Created: 2/23/2011
(2/23/11] Please dedicate the 8' UE off the alley and the appropriate sight distance
easements off each driveway access to the alley. Please add the SIDE language to the plat.
Number: 46 Created: 2/28/2011
[2/28/11] Please label the existing Laurel Street row.
Number: 47 Created: 2/28/2011
--[2/28/11]-Please-labe1-the-row-ded ication-off-Lau rel-with-V-so-that-it is -clear what is being
dedicated.
Number: 48 Created: 2/28/2011
[2/28/11] Please label how the 40' of Laurel row was vacated.
Topic: Site Plan
Number: 50 Created: 2/28/2011
[2/28/11] Please remove all utility and landscape information.
Number: 51 Created: 2/28/2011
[2/28/11] Please label and dimension all existing and proposed sidewalks. Sidewalks must
be 4' minimum onsite.
Number: 52 Created: 2/28/2011
[2/28/11] Please show all existing features within 150' of the property boundaries.
Number: 53 Created: 2/28/2011
[2/28/11] Please see scanning requirements in Appendix E6.
Number: 57 Created: 2/28/2011
[2/28/11_1 Project title does not match the plat.
Page 2
STAFF PROJECT REVIEW
City of Fad Collins
Odell Architects Date: 3/1/2011
Elizabeth Johnson
1024 Cherokee St Suite 200
Denver, CO 80204
Staff has reviewed your submittal for PUMA VIDA PLACE PDP TYPE II, and we offer the
following comments:
ISSUES:
Department: Engineering Issue Contact: Susan Joy
Topic: General
Number: 28 Created: 2/23/2011
[2/23/11 ] Per Pavement Management: The Laurel Street overlay was completed on
7/31/06. Any street cuts made within 5 years of that date will have triple street cut fees
applied.
Number: 29 Created: 2/23/2011
[2/23/11] Please coordinate the sidewalk culvert locations with Tim Buchanan in the
Forestry Dept so that the trees aren't killed or harmed with the installation of the culverts.
Number: 30 Created: 2/23/2011
[2/23/11] Please dedicate an 8' utility easement off the south side of the alley along your
frontage.
Number: 31 Created: 2/23/2011
[2/23/11] Please dedicate sight distance easements off each of the parking lot driveways
_-- into the alley per LCUASS-figure 7=16. — — -� - —
Number: 32 Created: 2/23/2011
[2/23/11] The trash enclosure (or any part of the structure including footings, etc) may not
be located within the -8' UE or the sight distance easement or located in such a way that the
doors swing out into public row.
Number: 33 Created: 2/23/2011
(2/23/11] This project is responsible for repairing and/or reconstructing the alley along the
frontage and as far offsite as necessary to correct the existing drainage problem.
Number: 34 Created: 2/23/2011
[2/23/11] Please see scanning requirements in Appendix E6 and bring all plan sets up to
standard.
Number: 35 Created: 2/23/2011
[2/23/11] All plan sets must show all existing features within 150' of the project boundaries.
Most concerned with driveways and sidewalks or anything else in public row.
Number: 38 Created: 2/23/2011
[2/23/11] The title survey and the plat indicate 40' of vacated Laurel row. Please label with
the ordinance number vacated by City Council.