HomeMy WebLinkAboutOTTER BOX DISTRIBUTION/WAREHOUSE EXPANSION - FDP - 17-10/A - CORRESPONDENCE --[9/7/10] Please bury all riprap located within the floodway and provide temporary erosion
control until vegetation is established.
NE Response: The drawings have been updated.
Number: 50 Created: 9/7/2010
(9/7/10] Please label elevation of first WQ hole on the riser pipe.
NE Response: The detail has been updated.
Number. 51 Created: 9/7/2010
[9/7/10] Please see other minor comments on the redlined plans.
NE Response: The redlines have been addressed.
Number: 52 Created: 9/7/2010
[9/7/10] Please see the 100% Floodplain Checklist and the redlined plans and report for all
floodplain comments.
NE Response: The redlines and Checklist comments have been addressed.
If you have any questions regarding these issues or any other issues related to this project,
please feel free to call me at (970) 221-6750.
SinTcerely: ��
/A"y�, 1
Ted Shepard
Chief Planner
Page 3
Fire access roads (fire lanes) shall be provided for every building constructed within the
PFA's jurisdiction when any portion of an exterior wall of the first story of the building is
located more than 150 feet from fire apparatus access as measured by an approved route
around the exterior of the building or facility. This fire lane shall be visible by painting and
signage, and maintained unobstructed at all times. A fire lane plan shall be submitted for
approval prior to installation. Any new fire lane must meet the following general
requirements:
❑ Be designed as a flat, hard, all-weather driving surface (asphalt or concrete) capable of
supporting fire apparatus weights. Compacted road base shall be used only for temporary
fire lanes or at construction sites.
❑ Have appropriate maintenance agreements that are legally binding and enforceable.
❑ Be designated on the plat as an Emergency Access Easement.
❑ Maintain the required minimum width of 20 feet throughout the length of the fire lane
(30 feet on at least one long side of the building when the structure is three or more stories
in height).
If the building is equipped throughout with an approved automatic fire -sprinkler system, the
fire code official is authorized to increase the dimension of 150 feet.
2006 International Fire Code 503.1.1, 503.2.3, 503.3, 503.4 and Appendix D
Number. 35 Created: 7/28/2010
[9/7/10] The "proposed No Parking signs" shown on Sheet C200 should actually be
"proposed FIRE LANE - NO PARKING" signs as shown on Sheet C601.
NO PARKING SIGNS: Thank you for showing the "NO PARKING" signs. Please change
them to NO PARKING FIRE LANE; I'd be happy to provide you with a sign template.
NE Response: The notes on Sheet C200 have been corrected.
Number. 36 Created: 7/28/2010
[9/7/10] Knox Boxes should be mounted approximately 60 inches above grade but no
higher than 72 inches above grade.
KEY BOXES REQUIRED
Poudre Fire Authority requires a key box ("Knox Box") to be mounted in approved location(s)
on every new building equipped with a required fire -sprinkler system or fire -alarm system.
PLEASE NOTE: If only one Knox Box is currently in place, an additional Knox Box must be
installed. Knox Boxes are available at cost from the PFA Fire Prevention Bureau.
2006 International Fire Code 506.1; PFA BUREAU POLICY 88-20
VFR Response: The proposed Knox Box will be located between 60"-72" above grade.
Number: 39 Created: 7/28/2010
[9/7/10] Were you able to correct C7 and C11 so they meet requirements?
TURNING RADII
The required turning radii of a fire apparatus access road shall be a minimum of 25 feet
inside and 50 feet outside 2006 International Fire Code 5�3.2 4 and Appendix D103 3
NE Response: A variance has been approve by t e City an PFA regarding these
two existing radii.
Department: Technical Services Issue Contact: Jeff County
Topic: Plat
Number:
[9/3/10] The plat boundary closes.
V123110] The Plat boundary closes.
Department: Stormwater-Water-Wastewater
Topic: Stormwater
Number: 49
Created: 7/23/2010
Issue Contact: Wes Lamarque
Created: 9/7/2010
Page 2
Linda Ripley
Ripley Design, Inc.
401 W. Mountain Ave.
Fort Collins, CO 80521
STAFF PROJECT REVIEW
Date: 9/9/2010
Staff has reviewed your submittal for OTTER BOX DISTRIBUTIONNVAREHOUSE
EXPANSION PDP & ADDITION OF A PERMITTED USE - TYPE II & FINAL PLANS, and we
offer the following comments:
ISSUES:
Department: Engineering Issue Contact: Andrew Carney
Topic: General
Number: 45 Created: 9/2/2010
[9/2110] Along with this round of review I am providing the Information sheets for both the
Development Agreement as well as the Development Construction Permit. As the project
moves forward we can certainly begin work on both items. NE' Response : Both the
information sheet and the DCP application have been submitted.
Topic: Plat
Number. 17 Created: 7/27/2010
[9/2/10] Carried forward as a reminder. Please contact me for the dedication templates.
Each dedication is subject to a $250 TDR Fee as well as recording fees for recording the
document with Larimer County.NE Response: The one off site easement that would
require a separate dedication statement has been removed from the project.
Topic: Utility Plan
Number: 47 Created: 9/7/2010
[9/7/10] Detail 709 was included with the set. If chases are needed, please use detail D12B
for a concrete chase with a detached walk.
NE Response: Detail 709 has been replaced with Detail D-10.
Number. 48 Created: 9/7/2010
[9/7/10] Please add Detail 1606.
NE Response: Detail 1606 has been added.
Department: Light & Power Issue Contact: Doug Martine
Topic; Light and Power
Number: 44 Created: 9/1/2010
[9/1/10] In order to complete the final electric utility plans, Light & Power Engineering will
need a copy of the recorded replat AND a copy of the original plat showing original lots 9,
10, and 11. If any questions, please contact Doug Martine at (970)224-6152.
NE Response: Both plats will be copied to Doug Martine once the Replat has
Department: PFA Issue Contact: Carle Dann
Topic: Fire
Number: 28 Created: 7/28/2010
[917/10] The "proposed No Parking signs" shown on Sheet C200 should actually be
"proposed FIRE LANE - NO PARKING' signs as shown on Sheet C601.
EMERGENCY VEHICLE ACCESS NE Response: The notes on sheet C200 have been
Thank you for showing the Emergency Access Easement. Please make the east boundary
(dotted line) easier to differentiate as the EAE on the plat. Also, please correct EASEMET
on page S-2 of the site plan.
REQUIRED ACCESS
been recorded.
corrected.