HomeMy WebLinkAboutFLATS @ THE OVAL - FDP - 26-08/A - CORRESPONDENCE - (13)fire alarm system. PLEASE NOTE: We likely will require TWO Knox Boxes for this
project: One for commercial, one for residential. 97UFC 902.4; PFA BUREAU POLICY 88-
20
Be sure and return all red -lined plans if/when you re -submit. ��
If you have any questions regarding these issues or any other issues re ated to th`iI project'
please feel free to call me at 221-6341.
Yours Truly,
Steve Olt
City Planner
cc: Susan Joy
Jon Sweet, Jim Sell Design
Aller-Lingle Architects
Current Planning file #26-08A
r.t_'
STAFF PROJECT REVIEW
City of Fort Collins
BP Laurel LLC Date: 4/29/2009
c/o Kevin Brinkman
3003 East Harmony Road, Suite #300
Fort Collins CO 80528
Staff has reviewed your submittal for FLATS AT THE OVAL (formerly Oval Flats) -
FINAL PLANS, and we offer the following comments:
ISSUES:
Department: Engineering Issue Contact: Susan Joy
Topic: Utility Plans
Number: 109 Created: 3/31 /2009
[4/28/09] Repeat: A2000 PVC pipe is only allowed in Local and Collector streets but not
Arterials. Both Howes and Laurel are arterial streets according to the master street plan.
Please change the plans to RCP and go ahead and submit mylars for signatures. Thank you.
[3/31/09] From Inspection:
1. Please detail the joint pattern for the concrete alley, show and dimension the alley pan,
page 8.
2. The storm line should be 15" RCP going into Howes Street, not PVC.
Department: Engineering Issue Contact: Randy Maizland
Topic: Utility Plans
Number: 79 Created: 12/17/2008
[4/28/09] Just need to remove the date and leave month and year otherwise you got
everything else.
[3/18/09] Repeat: Please change the date to the Month and Year and remove "imp." from
sheet 8 in the index or spell out. Needs to match the title on sheet 8 as well, so please change
one or the other to match.
[12/17/08] Please make some minor changes to the title at the top of the cover sheet. See
red -lines for clarification.
Department: PFA Issue Contact: Carie Dann
Topic: fire
Number: 59 Created: 9/5/2008
[4/22/09] Please contact me about Fire Riser Room location. Will it be interior entry or
exterior? If exterior, we might need another Knox Box at the Riser Room entrance,
depending on distance it is from main entrance Knox Box. Also, we can provide larger Knox
Boxes (at cost) that could accommodate probably both residential and commercial keys/fobs,
if you prefer that. If you go with a separate box for commercial and residential, each will
need a label (plate). You can see an example of this at the Northern Hotel west entrance.
[9/5/08] KNOX BOX REQUIRED: Poudre Fire Authority requires a "Knox Box" to be
mounted on the front of every new building equipped with a required fire sprinkler system or
Page 1