HomeMy WebLinkAboutHARMONY TECH PARK 5TH FILING (INFRASTRUCTURE) - PDP - 22-08 - CORRESPONDENCE - (3)provided. The site plan submitted only shows the large one in the
center of the project.
B. In general the design of this site must conform to the drainage basin
design of the McClellands Creek Master Drainage Plan as well the
City's Design Criteria and Construction standards.
C. The city wide new development fee is $4,420/acre ($0.1015/sq.ft.) for
new imperviousness over 350 square feet. No fee is charged for
existing impervious area. This fee is to be paid at the time each
building permit is issued.
D. Onsite detention is required. In this part of the McClellands drainage
basin, the release rate is 0.2 cfs/ac for the 10 year storm and 0.5 cfs/ac
for the 100 year storm. Water quality treatment is required as
described in the Urban Storm Drainage Criteria Manual, Volume 3 —
Best Management Practices (BMPs). Extended detention is the usual
method selected for water quality treatment. For further information,
please contact Glen Schlueter, 221-6700.
12. The proposed round -about should be addressed in the Transportation
Impact Study. There is some flexibility in the design. Please refer to the
Street Standards Appendix One.
13. The vacation of a segment of Timberwood Drive will follow the Replat that
dedicates new right-of-way. This process requires a hearing by the
Planning and Zoning Board first, followed by two readings by City Council.
The Transportation Development Review Fee is $800.00. For Final
Compliance, the Replat would reflect the vacated portion and dedicate the
new portion. Please note that at the public hearing for the P.D.P.,
Engineering will add a Condition of Approval that the vacation follows all
required procedures.
14. Please note that it appears most private drives will also need to be platted
as Emergency Access Easements for Poudre Fire Authority. In addition,
they may also need to be platted as Public Access Easements, and, if
applicable, Utility Easements.
15. Please check with Matt Baker, 221-6605, Street Oversizing Fund
Administrator, regarding any repays that may be due for improvements to
the Harmony Road and Ziegler Road, including the intersection.
16. Please be sure that the off-street bicycle/pedestrian system is called out
as per the approved O.D.P. For further information, please contact Marc
Virata, 221-6605.
8: The fire department connection shall be installed remote from the
buildings, and located on the street or fire lane side of buildings, fully
visible and recognizable from the street or nearest point of fire department
vehicle access. If possible, a fire hydrant shall be located within 100 feet
of the FDC. In addition, a "Knox Box" must be mounted on the front of
every new building equipped with a required fire sprinkler system or fire
alarm system.
9.. Fire lanes may be required and must be visible by painting and signage,
and maintained unobstructed at all times. Minimum turning radii is 25 feet
inside and 50 feet outside. A fire lane plan shall be submitted for approval
prior to installation. Fire lanes must meet the following general
requirements:
0 Be designed as a flat, hard, all-weather driving surface (asphalt or
concrete) capable of supporting fire apparatus weights. Compacted
road base shall be used only for temporary fire lanes or at
construction sites.
0 Have appropriate maintenance agreements that are legally binding
and enforceable.
0 Be designated on the plat as an Emergency Access Easement.
0 Maintain the required minimum width of 20 feet throughout the
length of the fire lane.
For further information, please contact Carie Dann, 221-6570.
10. Water and Wastewater: Existing mains: 16-inch water main in Lady
Moon to the existing Timberwood, 12-inch water main in Lady Moon from
Timberwood to Precision, 12-inch water main in Technology Parkway from
Harmony to the south edge of Intel site. The developer will be required to
install a 16-inch main in the new alignment of Timberwood from Lady
Moon to Technology Parkway and south to Precision. Please note that
sewer service in this area will be provided by the SFCSD. For further
information, please contact Roger Buffington, 221-6700.
11. Stormwater:
A. The drainage plan for this site is being revised as requested for the 4th
Filing PDP presently being processed. Please refer to the latest round
of comments for that project. One suggestion is to add all the
detention areas to the site plans so it is clear where detention is being
spaces. For general office, the maximum is no more than three spaces.
per 1,000 square feet of gross floor area, or :75 space per employee on
the largest shift, or 4.5 spaces per 1,000 square feet if all additional
parking spaces gained by the increased ratio (over.3/1,000 sq. ft.) are
contained within a parking garage/structure. For sites that do not have the
ability to park along a public street, or where there is no opportunity for
shared parking, the number of spaces may be increased by 20%. Please
note that for labor intensive uses, such as call centers, applicants may
avail themselves of the Altemative Compliance or Exception to the
General Office Parking Standard which allow for the maximum number of
parking spaces to be determined on a customized basis for the particular
needs of a specific end -user.
4. In accordance with the Harmony Corridor Plan, an 80-foot setback from
Harmony Road, as measured from the future edge of pavement, must be
provided. This area can platted as a separate tract, and maintained by an
association or included in individual lots to be maintained by the lot owner.
5. The site will continue to be served electrical power by the City of Fort
Collins. Existing system is installed along the south side of Harmony
Road and along Lady Moon Drive. System will be installed along
Precision Drive in conjunction with the development of the Third Filing
(Custom Blending). There is no system in Technology Parkway. Street
lights, with proper separation from street trees, will have to be designed
along all public streets. As you are aware, Light and Power does not
provide street lighting for internal private drives.
Normal development charges will apply for all end -users. Where multiple
buildings are located in close proximity, a shared transformer may be the
most efficient. Any change to the existing system will be at the
developer's expense. For further information regarding electrical service,
please call Rob Irish, 221-6700.
6. The site will be served by the Poudre Fire Authority. Hydrant spacing and
water flow must meet minimum requirements based on type of occupancy.
Minimum flow and spacing requirements for commercial is 1,500 gpm at
20 psi residual pressure, spaced not further than 300 feet to the building,
on 600-foot centers thereafter. These requirements may be modified if
buildings are equipped with automatic fire sprinkler systems.
7. For buildings with fire sprinklers, standpipes and fire pumps must meet
minimum requirements. For example, buildings four or more stories in
height are required to be equipped with firefighting standpipes in every
stairwell. The standpipe system must be capable of supplying a minimum
100 psi to the top floor; an approved fire pump may be required to obtain
this minimum pressure.
CONCEPTUAL REVIEW STAFF COMMENTS
h a =3
City of Fort Collins
ITEM: Harmony Technology Park 5th Filing Infrastructure
Project Development Plan
MEETING DATE: May 5, 2008
APPLICANT: MAVD Development Company c/o Mrs. Angie
Milewski, B.H.A. Design, 1603 Oak Ridge Drive, Fort
Collins, CO 80525
LAND USE DATA: Request to subdivide and design the streets, utilities and
stormwater improvements for Parcels S and E (north of.. Precision Drive) of the
Harmony Technology Park O.D.P., Third Amendment, approved in March of
2008. This would be known as an Infrastructure Project Development Plan as
there would be no buildings associated with this filing. The area is bounded by
Harmony Road on the north, Lady Moon Drive on the east, Precision Drive on
the south and Technology Parkway on the east. Timberwood Drive bisects the
site and would be re -aligned as per the O.D.P. Third Amendment. The area is
currently platted as Harmony Technology Park, Second Filing. The Infrastructure
P.D.P. would include a replat and be titled the Fifth Filing and contain
approximately 58 acres.
COMMENTS:
The site is zoned H-C, Harmony Corridor, and within the Basic Industrial
Non -retail Employment Activity Center sub -area of the Harmony Corridor
Plan. This sub -area permits a mix of office and light industrial uses as
primary uses and allows up to 25% secondary uses. The Harmony
Technology Park O.D.P., Third Amendment was approved by the Planning
and Zoning Board on March 20, 2008.
2. Since no buildings are proposed, the Replatting and Utility Plans would be
processed as an Administrative (Type One) review.
3. In the course of determining the optimum parcel size for future office
buildings or mixed -use buildings, keep in mind that parking is generally
regulated such that a development cannot exceed a maximum amount of
COMMUNITY PLANNING AND ENVIRONMENTAL SERVICES 281 N. College Ave. P.O. Box580 Fort Collins, CO80522-0580 (970)221-6750
PLANNING DEPARTMENT
Current Planning
281 N. College Ave.
PO Box 580
Fort Collins, CO 80522
City of Fort Collins
May 13, 2008
Mrs. Angie Milewski
BHA Design, Inc.
1603 Oak Ridge Drive
Fort Collins, CO 80525
Dear Angie:
For your information, attached is a copy of the Staff's comments for Harmony
Technology Park 5th Filing — Infrastructure Project Development Plan which as
presented before the Conceptual Review Team on May 5, 2008.
The comments are offered by staff -to assist you in preparing the detailed components
of the project application. Modifications and additions to these comments may be
made at the time of formal review of this project.
If you should have any questions regarding these comments or the next steps in the
review process, please feel free to call me at 970-221-6750.
Sincerely,
Ted Shepard
Chief Planner