HomeMy WebLinkAboutLITTLE BEAR'S CHILD CARE - PDP - PDP120017 - CORRESPONDENCE -Department: Zoning
Contact: Gary Lopez, 970.416.2338, glopez(fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 06/15/2012
06/1512012: Reminder that all signs and their locations are not approved by the PDP or the
FDP. A separate sign permit is required for approval, this includes refacing of existing signs.
Department: Technical Services
Contact: Jeff County, 970.221.6588, jcounty(a)fcgov.com
Topic: Construction Drawings
Comment Number: 9 Comment Originated: 06/19/2012
06/19/2012: There are line over text issues on sheet 3.
Topic: General
Comment Number: 10 Comment Originated: 06/19/2012
O6/19/2012: The 2 legal descriptions for the right of way dedication state that the land is for
easement purposes. Please change this to right of way.
Topic: Landscape Plans
Comment Number: 4 Comment Originated: 06/19/2012
O6/19/2012: Please block out around the text on sheet 3. See redlines.
Topic: Site Plan
Comment Number: 1 Comment Originated: 06/19/2012
O6/19/2012: Please increase the size of the legal description text on sheet 1. See redlines.
Comment Number: 2
06/19/2012: Please increase the text size on sheet 2. See redlines.
Comment Number: 3
O6/19/2012: Please block out around the text on sheet 2. See redlines.
Department: Traffic Operation
Contact: Ward Stanford, 970-221.6820, wstanford(a)fcaov.com
Topic: Construction Drawings
Comment Number: 1
Comment Originated:. 06/19/2012
Comment Originated: 06/19/2012
Comment Originated: 06/20/2012
06/20/2012: Signing and Marking notes should be revised to state "local entity traffic engineer"
at each instance that they currently state "local entity engineer". This is a permanent change to
the signing and marking notes. Please revise your standard note file to reflect the change.
Department: Water -Wastewater Engineering
Contact: Roger Buffington, 970.221.6854, rbuffington(7a fcgov.com
Topic: General
Comment Number: 2 Comment Originated: 06/20/2012
06/20/2012: If sign is moved, it is strongly suggested that the new location is coordinated with
the locations of the existing water/sewer services and fire line so that the sign does not
interfere with future maintenance of these services.
Topic: Landscape Plans
Comment Number: 1
Comment Originated: 06/19/2012
06119/2012: If additional landscaping is planned along Riverside, show existing water/sewer
services and fire line and provide the required separation distances.
Department: PFA
Contact: Ron Gonzales, 970.416-2864, rgonzales(.poudre-fire.org
Topic: General
Comment Number: 1. Comment Originated: 06/19/2012
O6/19/2012: Address numerals required to be visible from the street fronting the property.
Comment Number: 2. Comment Originated: 06/19/2012
O6/19/2012: This is classified as an 1.4 institutional day care facility. It is required to be
licensed by the State of Colorado.
Comment Number: 3. Comment Originated: 06/19/2012
06/19/2012: The existing fire sprinkler system shall be extended to cover any new areas in
need of proper fire protection coverage.
Comment Number: 4. Comment Originated: 06/19/2012
06/19/2012: Should grease -laden vapors be generated while heating meals, fire protection will
be required under a Type 1 hood.
Department: Stormwater Engineering
Contact: Wes Lamarque, 970.416.2418, wlamarpueMcgov.com
Topic: General
Comment Number: 1 Comment Originated: 06119/2012
06/19/2012: Please use the City's hydrology computation method per our Stormwater Criteria
Manual. This should actually reduce the quantity detention volume requirement.
Comment Number: 2 Comment Originated: 06/19/2012
O6/19/2012: Discussions need to take place on what treatment method is best for water quality.
Comment Number: 3 Comment Originated: 06/19/2012
O6/19/2012: Stormwater is ready for a public hearing.
Department: Technical Services
Contact: Jeff County, 970.221.6588, jcountyna fcgov.com
Topic: Building Elevations
Comment Number: 5 Comment Originated: 06/19/2012
06/19/2012: Please change the sheet number to 4 of 4.
Topic: Construction Drawings
Comment Number: 6 Comment Originated: 06/19/2012
O6/19/2012: Please change the datum for the benchmark on sheets 1 & 2. The City of Fort
Collins Vertical Control Network is on the 1929 Datum (unadjusted).
Comment Number: 7 Comment Originated: 06119/2012
O6/19/2012: Please remove "Riverside II Condo Amended" from the sub -title. The Site Plan
shows Lot 2, Viking I Subdivision being part of this project. Please add this to the sub -title.
Comment Number: 8 Comment Originated: 06/19/2012
06/19/2012: Please correct the lot designations on sheets 3 & 4. See redlines.
Department: Environmental Planning
Contact: Lindsay Ex, 970.224.6143, lex(a)fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 06/08/2012
06/08/2012: No comments.
Department: Forestry
Contact: Tim Buchanan, 970.221-6361, tbuchanan(a)fcgov.com
Topic: Landscape Plans
Comment Number: 1 Comment Originated: 06/20/2012
06/20/2012: Label all existing trees as to type and size with intent to protect, transplant or
remove. It appears all existing trees are can be retained. Meeting with City Forester on site can
provide this information to the applicant to record on the plan.
Comment Number: 2 Comment Originated: 06/20/2012
O6/2012012: Add tree protection notes in 3.2.1 G
Comment Number: 3 Comment Originated: 06/20/2012
O6/20/2012: There are two existing maple trees on the west border of the parking lot. These
two trees are not shown on the plan as existing. New trees are shown where these trees are
located.
Comment Number: 4 Comment Originated: 06/20/2012
O6/20/2012: Separation distances for trees are 10 between water and sewer mains and 6 feet
for service lines.
Department: Light And Power
Contact: Doug Martine, 970.224.6152, dmartine()fcgov.com
Topic: General
Comment Number: 1 Comment Originated:
06/05/2012
06/05/2012: Records show that the existing building has 5 electric meters of 100 amps each
(500 amps total capacity) at 120/240 volt single phase. If any changes to the existing electric
service is necessary, please contact Light & Power Engineering at (970)221-6700.
Comment Number: 2 Comment Originated:
06/05/2012
O6105/2012: Electric development charges will apply for the lot at 1230 E. Elizabeth, even if no
power is required to the site.
Comment Number: 3 Comment Originated:
06/05/2012
O6/05/2012: Clearance of 8 ft. on the front (door) side, and 3 ft. on the other three sides of the
transformer must be maintained. Also, the transformer must be accessible to utility personnel
and equipment. The electric meter(s) must be accessible to utility personnel at all times without
obtaining permission or an escort.
Comment Number: 4 Comment Originated:
06105/2012
O6/05/2012: There is an existing streetlight on Elizabeth St. as shown on the site plan. Street
tree locations must be adjusted to provide 40 ft. clearance between the light pole and street
trees (15 ft. if the tree is an ornamental type).
Department: Current Planning
Contact: Courtney Levingston, 970.416.2283, clevingston(a.fcnov.com
Topic: Site Plan
Comment Number: 3 Comment Originated: 06/14/2012
O6/14/2012: The Land Use Code only requires 1 handicapped parking space LUC3.2.2(K)
Department: Engineering Development Review
Contact: Andrew Gingerich, 970.221.6603, agingerichOfcoov.com
Topic: Construction Drawings
Comment Number: 3
Comment Originated: 06/19/2012
O6119/2012: Please confirm with Water/Wastewater but engineering would request that existing
and proposed (if applicable) water, sewer, and services be shown on the grading plan if a
utility plan is not provided.
Topic: General
Comment Number: 2
Comment Originated: 06/19/2012
06/19/2012: Thank you to the Owner, Applicant and Consultant's for addressing the conceptual
review comments adequately.
Comment Number: 4
Comment Originated: 06/19/2012
O6/19/2012: As mentioned in Conceptual Review this project is responsible for dedicating right
of way for East Elizabeth to meet the 76' wide right of way for collector with parking. The Viking
I subdivision plat shows 60' was dedicated previously, however the right of way proposed to
be dedicated by separate document is only 6' and the proposed dedication is shown as 7' on
the site plan. Please provide additional information to support only dedicating 6' of additional
right of way. If no other documents support a situation where this project is responsible for half
the remaining right of way then 8' will need to be dedicated.
Comment Number: 5
Comment Originated: 06/19/2012
O6/1912012: It appears that fencing is proposed inside of the existing access and utility
easement off of Elizabeth Street. The fence will need to be located outside of the easement.
Comment Number: 6 Comment Originated: 06/20/2012
06120/2012: The sign along Riverside exists within the Right of Way. Please remove the note
from the plans "existing sign to remain". Further discussions will need to occur with Zoning and
an encroachment permit may be an option.
Contact: Sheri Langenberger, 970.221.6573, slangenbergerMcgov.com
Topic: General
Comment Number: 1
Comment Originated: 06/1412012
06/1412012: The project owes an additional $215 for TDR fees. The acerage calculation on the
application did not match that identified on the site plan.
Department: Environmental Planning
Contact: Lindsay Ex, 970.224.6143, lexna fcgov.com
Topic: General
City of
Fort Collins
July 10, 2012
Troy Jones
MTA Planning & Architecture
108 Rutgers Ave
Fort Collins, CO 80525
RE: Little Bear's Child Care, PDP120017, Round Number 1
Community Development and
Neighborhood Services
281 North College Avenue
PO Box 580
Fort Collins, CO 80522
970.221.6750
970.224.6134 - fax
fcgov. com/developmentreview
Please see the following summary of comments from City staff and outside reviewing agencies for your
submittal of the above referenced project. If you have questions about any comments, you may contact the
individual commenter or direct your questions through the Project Planner, Courtney Levingston, at
970Al6-2283 or clevingston@fcgov.com.
Comment Summary:
Department: Current Planning
Contact: Courtney Levingston, 970.416.2283, clevingston@fcgov.com
Topic: General
Comment Number: 1
Comment Originated: 06/14/2012
06/14/2012: Is the Shed exisiting or proposed? If proposed, please provide detail on
elevations.
Comment Number: 2
Comment Originated: 06/14/2012
0611412012: Please call out the location of the transformer on landscape plans. All utilities must
be screened.
Comment Number: 3 Comment Originated: 06/14/2012
06114/2012: Please call out where the main entrance will be located.
Comment Number: 4 Comment Originated: 07/05/2012
07/05/2012: For final, please include the owners information on the title page.
Topic: Site Plan
Comment Number: 1 Comment Originated: 06/14/2012
06/14/2012: For final, please provide bike rack, trash enclosure and automobile parking stall
detail to ensure each meets the LUC standards.
Comment Number: 2 Comment Originated: 06/14/2012
06/14/2012: Plese call out the limits of development. I believe this is signified by the dashed
line, correct?