HomeMy WebLinkAboutREMINGTON ROW (FORMERLY REMINGTON ANNEX) - FDP - FDP130017 - CORRESPONDENCE -Department: Water-Wastewaer Engineering •
Contact: Roger Buffington, 970-221.6854, rbuffington(a)fcgov.com
Topic: Construction Drawings
Comment Number: 1 Comment Originated: 06/11/2013
06/11/2013: Label/note the curb stops on the water services.
Comment Number: 2 Comment Originated: 06/11/2013
06/1112013: Will lowerings be required on the fire lines crossing the electric duct bank?
Pothole?
Department: Zoning
Contact: Noah Beals, 970.416.2313, nbeals(cDfcgov.com
Topic: General
Comment Number: 1
Comment Originated: 06/11/2013
O6/11/2013: Plans should be labeled Final Plan now (rename all the PDP labels)
Comment Number: 2 Comment Originated: 06/11/2013.
O6/11/2013: On the site plan include a note with reference to the approved modifications.
Comment Numberq *Comment Originated: 06/12/2013
O6/12/2013: The City would like to discuss the landscaping in the PLDs. Cobble rock has not
worked well in the past in other developments.
Comment Number: 3 Comment Originated: 06/12/2013
O6/12/2013: Please add details for the outlet works for the detention ponds in the parking lot
and the front yard PLDs.
Comment Number: 4 Comment Originated: 06/1212013
06/12/2013: Please see other minor redlined comments on the utility plan set.
Department: Technical Services
Contact: Jeff County, 970.221-6588, jcounty(rDfcgov.com
Topic: Building Elevations
Comment Number: 1
O6/12/2013: No comments.
Topic: Construction Drawings
Comment Originated: 06/12/2013
Comment Number: 2 Comment Originated: 06/12/2013
06112/2013: There are line over text issues on sheets HC01, UT01, GR01 & RDOt. See
redlines.
Comment Number: 3 Comment Originated: 06/12/2013
O6/12/2013: Please mask the text in hatched areas on sheets HC01, DR01 & UT01. See
redlines.
Topic: Landscape Plans
Comment Number: 4 Comment Originated: 06/12/2013
O6112/2013: There are line over text issues on sheet 1-1. See redlines.
Comment Number: 5 Comment Originated: 06/12/2013
O6/12/2013: Please mask the text in hatched areas on sheet PDP2. See redlines.
Topic: Plat
Comment Number: 6 Comment Originated: 06/12/2013
O6/12/2013: Should "Remington Annex" in the Owners signature block be "Remington Row"?
See redlines.
Topic: Site Plan
Comment Number: 7 Comment Originated: 06/12/2013
O6/12/2013: There are line over text issues on sheet PDP2. See redlines.
Comment Number: 8 Comment Originated: 06/12/2013
06/12/2013: Please mask the text in hatched areas on sheet PDP2. See redlines.
Department: Traffic Operation
Contact: Ward Stanford, 970.221.6820, wstanford(o)fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 06/12/2013
O6/12/2013: No Comments.
Topic: General •
40
Comment Number: 1
Comment Originated: 05/30/2013
05/30/2013: Unique street addresses will be assigned to each structure and will eliminate the
building letter designations. The north structure will be addressed as 705 Remington St and the
south structure will be addressed as 715 Remington St. Unit addresses can be requested
through the GIS Department for these two structures as specified below. The middle structure
will be assigned 711 Remington St and no additional unit designation will be necessary.
Comment Number: 2
Comment Originated: 05/30/2013
05/30/2013: Projects with three or more tenant units require the Unit Level Addressing form to
be completed and submitted to the GIS Department once plans have met final approval through
Development Review and are recorded with the City. This can occur anytime during
construction, but before any utilities are set within the structure to ensure the meter banks match
the official addressing for the structure.
The Unit Level Addressing form can be obtained by contacting the GIS office at
gis@fcgov.com or (970) 416-2483. Addressing will be determined by the GIS Department.
Department: Park Planning
Contact: Craig Foreman, 970.221.6618, cforeman(&fcaov.com
Topic: General
Comment Number: 1
05/17/2013: No comments
Department: PFA
Contact: Jim Lynxwiler, 970-416.2869, ilynxwilerftoudre-fire.org
Topic: General
Comment Number: 01
06/1112013: All prior fire department concerns have been resolved.
Department: Stormwater Engineering
Contact: Jesse Schlam, 970-218-2932, 0schlam0fcgov.com
Topic: Erosion Control
Comment Number: 1
Comment Originated: 05/17/2013
Comment Originated: 06/11/2013
Comment Originated: 05/29/2013
05/29/2013: The current Erosion Control Materials Submitted do not meet requirements. See
redlines for corrections in the Erosion Control Plan. The plan should also include a sequence
chart. The Erosion Control Report (Stormwater Management Control) submitted was incomplete,
please address 1) Nature and Purpose of the Construction in the Site Description, 2) Need an
actual number of percent vegetation, 3) Seed/Sod Mix, 4) Soil Amendment Requirements, 5)
Mulch Requirements. If you need clarification concerning this section, or if there are any
questions please contact Jesse Schlam 970-218-2932 or email @ jschlam@fcgov.com
Contact: Wes Lamarque, 970.416.2418, wlamarauena.fcgov.com
Topic: General
Comment Numbe4P
*Comment Originated: 06/12/2013
06/12/2013: The alley plan and profile sheet has me a little confused with the information being
shown with how the transition from inverse crown to slope to one side occurs. I would envision
that the plan view would show a flowline that transition from the center to the east side of the
alley as it heads north through the identified transition area. Perhaps that is what's occurring,
though I'm not sure. Perhaps some cross -sections in three locations along the transition area
would help identify what is to occur.
Comment Number: 4 Comment Originated: 06/12/2013
O6/12/2013: Is a 50.51 % flowline grade actually occurring and is the centerline profile
approaching Laurel Street having a reverse grade compared to the right flowline? It might be
beneficial to meet of line for more clarity on my part.
Comment Number: 5 Comment Originated: 06/12/2013
06/12/2013: Please provide a concrete joint pattern detail for the alley to illustrate panel size,
dowelling, joint type, etc.
Comment Number: 6
Comment Originated: 06/1212013
06112/2013: I'm understanding that variances were approved to not require a utility easement
along Remington Street and require a 5' utility easement along the alley. Please have this
variance approval identified on general note #48.
Topic: General
Comment Number: 1
06112/2013:
Comment Originated: 06/12/2013
An easement from the property owner located on the southeast corner of the alley and Laurel
Street is needed for the offsite work.
Topic: Plat
Comment Number: 7 Comment Originated: 06/12/2013
O6112/2013: The certification of dedication language on the plat has been updated. Please
provide a contact information email address for me to forward the current language.
Department: Environmental Planning
Contact: Lindsay Ex, 970.224.6143, lex fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 05/22/2013
05/22/2013: No comments.
Department: Historical Preservation
Contact: Karen McWilliams, 970.224.6078, kmcwilliams(a)fcclov.com
Topic: General
Comment Number: 1 Comment Originated: 06/11/2013
06/11/2013: Per Hogestad, the owners' historic preservation architect, is reviewing some
design alterations contained in the submitted Final Plans. These design changes are not
anticipated to be significant, and should not affect the projects compliance with LUC Section
3.4.7.
Department: Internal Services
Contact: Todd Reidenbach, ,
City of
Fort Collins
June 13, 2013
Jeff Hansen
Vaught Frye Larson Architects
401 Mountain Avenue
Suite 100
Fort Collins, CO 80521
RE: Remington Row (formerly Remington Annex), FDP130017, Round Number 1
Community Development and
Neighborhood Services
281 North College Avenue
PO Box 580
Fort Collins, CO 80522
970.221.6760
970.224.6134 - fax
fcgov. com/deve/opmentreview
Please see the following summary of comments from City staff and outside reviewing agencies for your
submittal of the above referenced project. If you have questions about any comments, you may contact the
individual commenter or direct your questions through the Project Planner, Courtney Levingston, at
970-416-2283 or clevingston@fcgov.com.
Comment Summary:
Department: Current Planning
Contact: Courtney Levingston, 970.416.2283, clevingstonbfcnov.com
Topic: Building Elevations
Comment Number: 2 Comment Originated: 06/07/2013
06107/2013: Since GIS has determined that each building will be assigned a separate address,
please update the east graphics on PDP3
Topic: General
Comment Number: 1
Comment Originated: 06/07/2013
06/07/2013: The bike racks are shown only 9 inches from the wall. These will need to be at
least 24 inches from the wall according to the standards contained in Section 17.4.2 of the
Larimer County Urban Area Street Standards. 9 inches is not enough room to secure the bike
to the rack.
Department: Engineering Development Review
Contact: Marc Virata, 970-221.6567, mvirata(&fcgov.com
Topic: Construction Drawings
Comment Number: 2
Comment Originated: 06/12/2013
06/12/2013: The spacing of the street cuts shown on Remington Street has three street cuts
occurring at a distance of 64 feet. At a distance of less than 75 feet, LCUASS requires that the
street repair be expanded to extend from the westernmost patch through to the easternmost
patch. This should be indicated on the plans.