HomeMy WebLinkAboutBOARDWALK CROSSING @ MASON STREET - PDP/FDP - FDP130003 - CORRESPONDENCE -required to be cu.ered and the rest fixed.
The south building with 5500 sq ft of retail is required 4 bicycle spaces. One of these is
required to be covered and the rest fixed.
All spaces shall be located close to pedestrian entrances of the building.
Site plan needs to indicate how many bikes spaces are available at each bike rack.
Comment Number: 2 Comment Originated: 03/19/2013
03/19/2013: In addition to the required modification request stated by Current Planning an
additional modification would be needed for the East side of drive aisle along the east property
line LUC 3.2.2(J) requires a 5ft landscape area between vehicle use areas and lot line.
Comment Num"r: 17 .,omment Originated: 03/21/2013
03/21/2013: Please correct the client's name in the title block.
Topic: Site Plan
Comment Number: 18 Comment Originated: 03/21/2013
03/21/2013: The legal description does not match the Subdivision Plat. Please change to
match.
Comment Number: 19 Comment Originated: 03/21/2013
03/21/2013: There are line over text issues on sheet 1.
Comment Number: 20 Comment Originated: 03/21/2013
03/21/2013: The square footage shown for the lots does not match the Subdivision Plat.
Please change to match.
Department: Traffic Operation
Contact: Ward Stanford, 970-221-6820, wstanford(a)fcgov.com
Topic: Construction Drawings
Comment Number: 1 Comment Originated: 03/18/2013
03/18/2013: The S&S Notes (and any other on other sheets if applicable) need to be revised
to state the "City Traffic Engineer" at each instance where the notes state "Local Entity"
engineer. The Signing and Striping installation is overseen by the City TE (or designate) versus
the City Engineer (or designate).
Comment Number: 2 Comment Originated: 03/18/2013
03/18/2013: Please verify the City's corner sight distance criteria is met at the Mason
intersections.
Comment Number: 3
TIS accepted.
Comment Originated: 03/21/2013
Department: Water -Wastewater Engineering
Contact: Roger Buffington, 970-221-6854, rbuffington(a)fcgov.com
Topic: Construction Drawings
Comment Number: 1 Comment Originated: 03/12/2013
03/12/2013: On Boardwalk, is there a conflict between the storm drain and the fire line? Will a
lowering be needed on the fire line?
Comment Number: 2 Comment Originated: 03/12/2013
03/12/2013: PVC can be used for fire lines. If used, tracer wire is required, and the Standard
Details for tracer wire (30) and locator stations (25) need to be included.
Department: Zoning
Contact: Noah Beals, 970.416-2313, nbealso_fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 03/19/2013
03/19/2013: Land Use Code (LUC) 3.2.2(C)(4) The north building with 6000 sq ft of retail and
6000 sq ft of office is required the minimum of 8 bicycle spaces. Two of these spaces are
Topic: Plat
Comment Number: 1 Comment Originated: 03/21/2013
03/21/2013: The boundary and legal description close.
Comment Number: 2 Comment Originated: 03/21/2013
03/21/2013: Please change the name of the Plat to "Boardwalk Crossing, Filing 3".
Comment Number: 3 Comment Originated: 03/21/2013
03/21/2013: Please add "Being a" to the existing title, and make all of that text the sub -title in
smaller size.
Comment Number: 4 Comment Originated: 03/21/2013
03/21/2013: Please add a border to the sheet.
Comment Number: 5 Comment Originated: 03/21/2013
03/21/2013: All easements (existing or proposed) must be shown with enough bearing &
distance or curve information to establish their position.
Comment Number: 6 Comment Originated: 03/21/2013
03/21/2013: Please label all properties surrounding the Plat as unplatted or if platted with the
subdivision plat name.
Comment Number: 7 Comment Originated: 03/21/2013
03/21/2013: Please label all easements with the size and reception numbers.
Comment Number: 8 Comment Originated: 03/21/2013
03/21/2013: Please label the Basis Of Bearings.
Comment Number: 9 Comment Originated: 03/21/2013
03/21/2013: If the easement line marked up on Lot 2 is part of the vacated drainage easement,
please remove it.
Comment Number: 10 Comment Originated: 03/21/2013
03/21/2013: You may want to hatch access and/or drainage easements for clarity.
Comment Number: 11 Comment Originated: 03/21/2013
03/21/2013: The square footage for the Boardwalk Crossing Filing 2 plat is 77154. This does
not match the square footage shown.
Comment Number: 12 Comment Originated: 03/21/2013
03/21/2013: Are there any Lienholders for this property? If so, please add the Lienholder
signature block.
Comment Number: 13
Comment Originated: 03/21/2013
03/21/2013: Please explain the "row easement" at the south end of the property. What type of
easement is it and to whom is it dedicated.
Comment Number: 14
Comment Originated: 03/21/2013
03/21/2013: All easements must be shown, regardless of the client's wishes. See Board Rules
6.5.2 and 6.10 and C.R.S. 38-51-106(b).
Comment Number: 15 Comment Originated: 03/21/2013
03/21/2013: Is there a title commitment for the subject property?
Comment Number: 16 Comment Originated: 03/21/2013
03/21/2013: Notes 7-9 appear to be ALTA or Land Survey Plat notes. Please remove.
Comment Number: 06 Comment Originated: 03/20/2013
03120/2013: PREMISE IDENTIFICATION
New and existing buildings shall be plainly identified. Address numbers shall be visible from
the street fronting the property, plainly visible, and posted with a minimum of six-inch numerals
on a contrasting background.
2006 International Fire Code 505.1
Department: Stormwater Engineering
Contact: Wes Lamarque, 970.416-2418, wlamargue(a.fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 03/15/2013
03/15/2013: Stormwater is ready for a hearing.
Comment Number: 2 Comment Originated: 03/15/2013
03/15/2013: Minor comments may apply at final compliance.
Department: Technical Services
Contact: Jeff County, 970-221-6588, jcountyaa)fcgov.com
Topic: Building Elevations
Comment Number: 22
03/21/2013: No comments.
Topic: Construction Drawings
Comment Originated: 03/21/2013
Comment Number: 24 Comment Originated: 03/21/2013
03/21/2013: Please correct the number and description of benchmark E-322 on all sheets it is
shown on. This description does not match the NGS description that is published.
Comment Number: 25 Comment Originated: 03/21/2013
03/21/2013: Please change the sheet descriptions in the index on sheet C1. They do not
match the actual sheet titles.
Comment Number: 26 Comment Originated: 03/21/2013
03/21/2013: Please move the street names and data into -the right of way on sheets C3 & C4.
Comment Number: 27 Comment Originated: 03/21/2013
03/21/2013: There are line over text issues on sheet C4
Comment Number: 28 Comment Originated: 03/21/2013
03/21/2013: Please change General Note #3 to reflect the new Plat (replat) being recorded for
this project.
Topic: Landscape Plans
Comment Number: 21
03/21/2013: There are line over text issues on sheet 2.
Topic: Lighting Plan
Comment Originated: 03/21/2013
Comment Number: 23 Comment Originated: 03/21/2013
03/21/2013: Please change the title to "Boardwalk Crossing At Mason Street", to match the
other sheets in the plan set.
Comment Num"r: 2 omment Originated: 03/06/2013
03/06/2013: After the plans are final, an AutoCAD drawing (version 2008) of the site plan will
need to be sent to Terry Cox at TCOX@FCGOV.COM.
Department: Park Planning
Contact: Craig Foreman, 970-221-6618,
Topic: General
Comment Number: 1
03/01/2013: No comments
Department: PFA
cforemanOfcgov.com
Comment Originated: 03/01/2013
Contact: Jim Lynxwiler, 970.416-2869, ilynxwiler&poudre-fire.org
Topic: General
Comment Number: 01 Comment Originated: 03/20/2013
03/20/2013: FIRE LANES
Fire Lanes shall be designated on the plat as an Emergency Access Easement.
Comment Number: 02
Comment Originated: 03/20/2013
03/20/2013: STRUCTURES EXCEEDING 30' (OR THREE OR MORE STORIES) IN HEIGHT
In order to accommodate aerial fire apparatus access, required fire lanes shall be 30 foot wide
minimum on at least one long side of the building. At least one of the required access routes
meeting this condition shall be located within a minimum of 15 feet and a maximum of 30 feet
from the building, and shall be positioned parallel to one entire side of the building.
2006 International Fire Code Appendix D; Poudre Fire Authority Administrative Policy 85-5.
This requirement may be offset by a NFPA13 sprinkler system.
Comment Number: 03 Comment Originated: 03/20/2013
03/20/2013: FIRE CONTAINMENT
Buildings exceeding 5000 square feet and shall be sprinklered or fire contained. If containment
is used, the containment construction shall be reviewed and approved by the Poudre Fire
Authority prior to installation.
Comment Number: 04
Comment Originated: 03/20/2013
03/20/2013: KEY BOXES REQUIRED
Poudre Fire Authority requires at least one key box ("Knox Box") to be mounted in approved
location(s) on every new building equipped with a required fire sprinkler or fire alarm system.
The top shall not be higher than 6 feet above finished floor.
2006 International Fire Code 506.1 and Poudre Fire Authority Bureau Policy 88-20
Comment Number: 05
03/20/2013: FDC
Comment Originated: 03/20/2013
Fire Department Connections shall be installed in accordance with NFPA standards. Fire
department connections shall be located on the street side of buildings, fully visible and
recognizable from the street or nearest point of fire department vehicle access. The location of
the FDC shall be approved by the fire department.
2006 International Fire Code 912.2
Topic: Construction Drawings
Comment Number: 6 Comment Originated: 03/22/2013
03/22/2013: Add asphalt patching limits around the north ramp configuration as asphalt patching
will most likely be required with construction of the ramps.
Comment Number: 7 Comment Originated: 03/22/2013
03/22/2013: Please update the symbols for the water meter pit on both buildings. Currently the
symbol reads a sewer manhole where the water meter pit symbol should be.
Comment Number: 8 Comment Originated: 03/22/2013
03/22/2013: Update the 30 foot Access easement on the south entrance to read 30 foot utility
and access easement (per the plat). Please update this on sheets C3 and C4
Comment Number: 9 Comment Originated: 03/22/2013
03/22/2013: Please update the following details on sheets C5 and C6 to our most current
drawings:
-LCUASS drawing 1601- standard sidewalk
-LCUASS drawing 1602- sidewalk detail
-LCUASS drawing 1607- Truncated Dome Warning for Access Ramps
-LCUASS drawing 1606- Pedestrian Ramp Detail (not drawing 1606(a))
-COFC Water Wastewater drawing- concrete sidewalk culvert detail D-12B
Comment Number: 10 Comment Originated: 03/22/2013
03/22/2013: It is not clear why LCUASS detail 2501- Sidewalk widening details on sheet C5 is
included. Please remove from details sheet or label as on -site if widening of the sidewalk is
happening interior to the site.
Topic: Plat
Comment Number: 1 Comment Originated: 03/22/2013
03/22/2013: The easements shown on the plat are very confusing to follow and to determine
the limits of each easement. Please clearly identify the limits of each easement shown on the
plat.
Department: Environmental Planning
Contact: Lindsay Ex, 970-224-6143, lex(cDfcgov.com
Topic: General
Comment Number: 1 Comment Originated: 03/18/2013
03/18/2013: No comments.
Department: Light And Power
Contact: Doug Martine, 970.224.6152, dmartine(a)_fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 03/06/2013
03/06/2013: The developer will need to coordinate power requirements and electric
development charges with Light & Power Engineering at (970)221-6700.
Topic: Site Plan
Comment Number: 1 Comment Originated: 03/11/2013
Parking numbers are within the allowable maximum number of spaces; however, there are 2
HC spaces shown on the plans, so the parking data should be revised to show this. The
spaces along Mason Street extend out closer to the street than Building 1 by several feet.
Section 3.10.4 of the TOD requires that parking not be located between the street and the front or
side of a building. A modification to this standard could be requested if parking is ultimately
proposed as shown on the plan.
Comment Number: 2
Comment Originated: 03/11/2013
The setback for the parking along Mason Street (an arterial street) is 15' from back of r-o-w. If
there is no way to provide this setback, a modification to this standard could be requested.
Comment Number: 3
Comment Originated: 03/11/2013
Please clarify on the trash enclosure note how materials and/or colors of the enclosure will be
complementary to the proposed buildings.
Comment Number: 4
Comment Originated: 03/11/2013
Both the C-G district and the TOD require buildings be oriented toward streets rather than
toward parking lots. Providing walkway connections out to the streets (as shown on the site
plan), as well as entrances and storefronts oriented toward the streets will help address this
standard. Building one appears to have at least some entrances oriented to the streets but
Building two shows west elevations with and without doors along Mason.
Comment Number: 5 Comment Originated: 03/11/2013
The CG district and TOD require that pedestrian -oriented outdoor spaces be placed next to
activity areas (ie. shops, offices, street corners, etc.). The area at the SE corner of Building 2
appears to be a plaza area. Please clarify the intent of this area and how it would serve as an
activity/outdoor space.
Department: Engineering Development Review
Contact: Tyler Siegmund, 970.221-6501, tsiegmundna.fcgov.com
Topic: Construction Drawings
Comment Number: 2
Comment Originated: 03/22/2013
03/22/2013: Please add note 11 on sheet C4 to sheet C3 as well and reference remove and
replace curb and gutter at the sidewalk chase location. (Add note- Remove and replace 6"
vertical curb and gutter per City of Fort Collins construction detail 701 on sheet C3)
Comment Number: 3 Comment Originated: 03/22/2013
03/22/2013: Please dimension and label the parkway along Mason St to be 10ft on sheet C3.
Dimension and label the parkway to be 10ft on x-section B-B as well.
Comment Number: 4 Comment Originated: 03/22/2013
03/22/2013: Update x-session A -A, the north side of Boardwalk has detached sidewalk
Comment Number: 5
Comment Originated: 03/22/2013
03/22/2013: Please show the handicap ramp that is to be built with this project at the south
entrance off of Mason St. This should be our standard directional ramp to accept pedestrians
from the south
Department: Current Planning
Contact: Sherry Albertson -Clark, 970.224-6174, salbertson-clark(aD-fcgov.com
Topic: Building Elevations
Comment Number: 1 Comment Originated: 03/11/2013
The minimum building height is 20' in the TOD. Building two does not appear to meet this
standard.
Comment Number: 2 Comment Originated: 03/11/2013
The minimum glazing requirements (60% on ground floor, 40% on upper floor) appear to be
met for both buildings.
Comment Number: 3 Comment Originated: 03/22/2013
The materials legend has something missing on the last two materials (brick? and ?).
Comment Number: 4 Comment Originated: 03/22/2013
Articulation is required in exterior building walls. Building 2 shows as a rectangular footprint on
the site plan, but the architectural elevations show some articulation - please clarify.
Comment Number: 5 Comment Originated: 03/22/2013
The commercial building standards (Section 3.5.(6) require that all facades have a recognizable
base and top. The base may consist of thicker walls, ledges or sills; integrally textured
materials such as stone or other masonry; integrally colored and patterned materials such as
smooth -finished stone or tile; lighter or darker colored materials, mullions or panels; or panels.
Please provide information on how the base is being achieved.
Topic: General
Comment Number: 1 Comment Originated: 03/11/2013
This project was submitted as a combined PDP and FP, which should be noted on the site and
landscape plans and architectural elevations.
Topic: Landscape Plans
Comment Number: 1
Comment Originated: 03/11/2013
The scale on the landscape plan appears to be 1'730' (rather than 1"/60').Tree diversity, water
budget, and interior parking lot landscaping are within the prescribed standards.
Comment Number: 2
Comment Originated: 03/11/2013
The parking spaces along Boardwalk and Mason need to be screened from at least 75% of the
light from headlights, to a minimum height of 30" for at least 70% of the length of the parking
area along the street.
Comment Number: 3 Comment Originated: 03/11/2013
Additional. street trees (2) should be provided on the Boardwalk frontage, near the corner of
Mason Street.
Topic: Lighting Plan
Comment Number: 1 Comment Originated: 03/11/2013
The Luminaire Locations table on the photometric plan should be revised to show the correct
number of each fixture (should read 3 AA2 and 9 WW fixtures).
F6rt Collins
� --.--
Community Development and
Neighborhood Services
281 North College Avenue
PO Box 580
Fort Collins, CO 80522
970.221.6750
970.224.6134 - fax
fcgov.com/d`eve/0pmentreview
March 22, 2013
Steve Steinbicker
Architecture West, LLC
4710 S. College Avenue
Fort Collins, CO 80525
RE: Boardwalk Crossing at Mason Street, FDP130003, Round Number 1
Please see the following summary of comments from City staff and outside reviewing agencies for your
submittal of the above referenced project. If you have questions about any comments, you may contact the
individual commenter or direct your questions through the Project Planner, Sherry Albertson -Clark, at
970-224-6174 or salbertson-cark@fcgov.com.
Comment Summary:
Department: Forestry
Contact: Tim Buchanan, 970.221.6361, tbuchanan(a)fcgov.com
Topic: Landscape Plans
Comment Number: 1 Comment Originated: 03/20/2013
03/20/2013: Place street trees between sidewalk and curb along Boardwalk unless there is a
site constraint.
Comment Number: 2 Comment Originated: 03/20/2013
03/20/2013: In Planting note #13 add the Utility/tree separation information found in 3.2.1 K.
Provide tree placement on the plan that incorporates these separation standards.
Comment Number: 3
Comment Originated: 03/20/2013
03/20/2013: Please use this information on soil improvement to Planting note # 16.
• The soil in all landscape areas, including parkways and medians, shall be thoroughly
loosened to a depth of not less than eight (8) inches and soil amendment shall be thoroughly
incorporated into the soil of all landscape areas to a depth of at least six (6) inches by tilling,
disking or other suitable method, at a rate of at least three (3) cubic yards of soil amendment
per one thousand (1,000) square feet of landscape area.
Comment Number: 4
Comment Originated: 03/20/2013
03/20/2013: Consider using a tree that is more upright than Ginalla Maple in the 5 foot
landscape area between the parking lot and the sidewalk. Red Barron Crabapple is more
upright and could be considered as a replacement.