Loading...
HomeMy WebLinkAboutSUNRISE RIDGE, FIRST FILING - PDP - 13-05A - CORRESPONDENCE - (6)placed. If fencing is to be allowed by the HOA, placing them 10 feet offset of the property line may be a better location. The storm sewers also need to be included in a drainage easement. Number: 25 Created: 1 /27/2006 [1/27/06] Off -site drainage easements on the lot to the south, as well as on the property to the west are required. Letters of intent are required before a public hearing. Department: Zoning Issue Contact: Jenny Nuckols Topic: Zoning Number: 4 Created: 1 /5/2006 [1/5/06] Regarding note #21 in Conceptual Review Staff Comments. Lot number 7 - the house will have to be setback at least 70 feet from the front property line in order to meet lot width requirements. See article 5 for the definition of Lot Width. Number: 5 Created: 1 /5/2006 [1/5/06] Need a note on the landscape plan regarding installation of landscaping prior to issuance of C.O.'s 3.2.1(1)(4) Comments from Current Planning: 1. The triangular piece of Lot One that was acquired from Village Homes is zoned L-M-N. This needs to be rezoned to U-E. Staff will take this rezoning outside the twice -per -year schedule but we will need the owner to complete the Rezoning Application. 2. Current Planning has comments on labeling on the site plan, landscape plan and plat. Please see redlines. Be sure and return all of your redlined plans when you re -submit. If you have any questions regarding these issues or any other issues related to this project, please feel free to call me at (970) 221-6750. Sincerely: 1.,4t Ted Shepard Chief Planner Page 6 Number: 14 Created: 1 /24/2006 [1/24/06] Street names shall be reviewed and verified by LETA prior to being put into service. Number: 15 Created: 1 /24/2006 [1/24/06] Address numerals shall be visible from the street fronting the property, and posted with a minimum of six-inch numerals on a contrasting background. (Bronze numerals on brown brick are not acceptable.) Department: Transportation Planning Issue Contact: David Averill Topic: General Number: 6 Created: 1 /18/2006 [1/18/06] Directional ramps need to be shown on site/utility plans at the crossings of Daylight Ct. and of Rock Creek Dr. at Strauss Cabin Rd. Also, if you are going to show the as yet un-named street to Sunrise Ridge 2nd, there should be directional ramps indicated on that crossing (Sheet U1 of utility plans shows a portion of this extension). Number: 7 Created: 1 /18/2006 [1/18/06] Please show a Type Ill barricade at the northern terminus of the sidewalk on Zeigler Rd. Number: 8 Created: 1 /18/2006 [1/18/06] Please show Bicycle Lane signing/striping on one of the less cluttered utility plan sheets or on a stand-alone signing/striping plan. Thanks. Number: 9 Created: 1 /18/2006 [1/18/06] The Transportation Memorandum is acceptable. Thanks. Department: Stormwater-Water-Wastewaterlssue Contact: Wes Lamarque Topic: Stormwater Number: 22 Created: 1 /27/2006 [1/27/06] Please provide a letter from the owners of the detention pond stating the modification and expansion of the pond is acceptable and also a maintenance agreement will be agreed upon in the future. Number: 23 Created: 1/27/2006 [1/27/06] Please document in the text of the report the detention volume required for the site only and the 2-year histroric release rate for the site only. Compare this with what is being proposed (including all the sub -basins B1-63 that are free releasing). Over -detaining can be an option to make up for the basins free -releasing, or a variance may also be considered. Number: 24 Created: 1 /27/2006 [1/27/06] For this case, the storm sewers in the lots are Ok due to the large size of the lots. Some thought needs to take place into exactly where the pipes should br Page 5 Department: Light & Power Issue Contact: Doug Martine Topic: Electric Number: 1 Created: 1 /4/2006 [1 /4/06] Prior to development Light & Power will need to know electric load information for each lot. The lots identified as "Duplex or single family" will need to be identified as to which they will be prior to electric system design. As an alternative the electric system can be designed, and Electric Development Charges based, on the assumption they are duplexes. Response to this comment is not required as a condition of development approval but will need to be addressed before electric system design. Topic: Landscape plan Number: 3 Created: 1 /4/2006 [1/4/06] A copy of the landscape plan showing planned streetlights was sent to One Earth Solutions on 1-4-05. The streetlights must be shown on the landscape plan and street tree locations adjusted to provide 40 ft. clearance between tree and streetlight standard (15 ft. if the tree is an ornamental). Topic: Utility plan Number: 2 Created: 1 /4/2006 [1/4/06] The utility plan does not show planned water or sewer services to each lot. It is assumed that neither of these will be at or near the side property lines. Department: PFA Issue Contact: Carle Dann Topic: fire Number: 11 Created: 1/24/2006 [1 /24/06] If the front of the house is farther than 150 feet from the street, either a fire lane or automatic fire sprinkler system may be required. (This information shall be included in the plat.) Number: 12 Created: 1 /24/2006 [1/24/06] Fire hydrants shall provide a minimum of 1,000 gallons per minute at 20 psi residual pressure, spaced not farther than 400 feet to any building, on 800-foot centers. Number: 13 Created: 1 /24/2006 [1/24/06] A dead-end street shall not exceed 660 feet in length. The tum-around at the end of the street shall have an outside turning radius of 50 feet or more, and in inside turning radius of 25 feet or more. Short fire lanes are permitted to facilitate a second point of access when the street is longer than 660 feet. All structures beyond the 660 feet must be fire sprinklered if a second point of access cannot be provided. (This information shall be included in the plat.) Page 4 Number: 31 Created: 1 /31 /2006 [1/31/06] Clarify the information regarding the existing residence on Lot 6. Please indicate if this is to remain. If so, the existing driveway access to Strauss Cabin Road must be eliminated and indicated as such. Number: 32 Created: 1 /31 /2006 [1/31/06] Are subdrains proposed on the development? Number: 33 Created: 1 /31 /2006 [1/31/06] Letters of intent are required from the Fossil Creek Inlet Ditch Company, the property owner to the south, and the Observatory Village (Willow Brook) development. Number: 42 Created: 1 /31 /2006 [1/31/06] Carrying over a comment from conceptual, we'll need to discuss in the future the providing of funds in lieu of construction for Strauss Cabin Road along the +/- 580 feet of frontage. Number: 43 Created: 1 /31 /2006 [1/31/06] The construction of the sidewalk along the south side of Rock Creek Drive may be better to defer until the second filing to prevent possible issues with the second filing utility connections requiring work along Rock Creek Drive that would cause the sidewalk to be damaged. I am following up with internal City utilities to discuss this further. Should it be deemed appropriate to delay the construction of the sidewalk, the developer will still be obligated for the sidewalk adjacent to Tract A as the tract of land is undergoing development under 24-95 of the City Code. We would need to look at providing for funds in lieu of constructing the sidewalk in this location. Topic: Plat Number: 16 Created: 1 /24/2006 [1/24/06] Tract B needs to be a utility easement in conjunction with the required 9' of utility easement behind the right-of-way. Number: 17 Created: 1 /24/2006 [1/24/06] Please provide a note on the plat indicating that Lot 12 shall not be allowed vehicular (driveway) access onto Strauss Cabin Road. Number: 18 Created: 1 /24/2006 [1/24/06] Tract A should probably be called out as a drainage easement as it lies within the pond expansion. Page 3 Number: 35 Created: 1/31/2006 [1/31/06] The series of grade breaks on Rock Creek Drive approaching Strauss Cabin Road is substandard as the curve created is not long enough. Number: 36 Created: 1/31/2006 [1/31/06] Rock Creek is required to have a street grade profile of no more than 4% for a distance of 200 feet from the intersection, which isn't being met with the series if grade breaks shown. Number:37 - -Created: 1/31/2006 [1/31/06] Vertical- lengths#or-Rock'Creek Drive and Daylight Court do not meet minimum sag and crest curve length requirements for their respective street classifications per 7-17 and 7-18. Number: 38 Created: 1/31/2006 [1/31/06] Items 35-37 indicating where design requirements are not being met was discussed internally and variance requests to these designs were viewed favorably upon should a redesign not be pursued. Any such variance requests should be thoroughly prepared n acco � d M iMPo-ocess rather than operating-under-Wn swimptiwthatinebrequests-will=be automatically granted. Number: 39 Created: 1/31/2006 [1/31/06] The variance request concept to create a crosspan across Rock Creek Drive at the Strauss Cabin intersection was discussed internally and viewed favorably upon. Please resubmit the variance request also with the PE stamp in accordance with variance request requirements. Number: 40 Created: 1/31/2006 [1/31/06] There needs to be an "interim" design for Strauss Cabin Road to specify how the Rock Creek Drive improvements will tie into the existing road, how are the grades and spot elevations shown in this condition, how do flows end up being conveyed to the ditch, etc. Number: 41 Created: 1/31/2006 [1/31/06] Provide a striping plan. Topic: General Number: 28 Created: 1/31/2006 [1/31/06] With the project discharging onto the drainage pond for Willow Brook that is being enlarged with this project and the project not proposing an HOA, how is maintenance responsibilities being worked out with Willow Brook? Some sort of maintenance agreement with Willow Brook should be worked out. Page 2 STAFF PROJECT REVIEW City of Fort ift, KELLY SMITH Date: 02/06/2006 7890 PHEASANT RUN LANE WELLINGTON, CO 80549 Staff has reviewed your submittal for SUNRISE RIDGE, FIRST FILING, PDP - TYPE I, and we offer the following comments: ISSUES: Department: Engineering Issue Contact: Marc Virata Topic: Construction Drawings Number: 19 Created: 1 /24/2006 [1 /24/06] In general, please use a lighter line weight for the existing contours/features in order to more easily follow the proposed grade changes. Number: 20 Created: 1 /24/2006 [1/24/06] Access ramps are required to be "directional' and not lead to the middle of the intersection. The two intersections with Rock Creek Drive being T-intersections should each provide for a third access ramp across the street. At the intersection of Strauss Cabin Road, one access ramp will be theoretically needed on the east side of the street which requires one access ramp on the west side to split in two directions. Number: 21 Created: 1 /24/2006 [1/24/06] The proposed contours relating to the detention pond enlargement southwest of the site on Sheets G1 and G2 seem to show grading along and within existing roads and existing private property. Number: 26 Created: 1 /31 /2006 [1/31/06] There appears to be several storm sewer lines that have inadequate cover requirements over the proposed street grade. Number: 27 Created: 1 /31 /2006 [1/31/06] Sheet U1 indicates proposed wood railroad ties on Lot 12 are these intended to act as retaining walls? Number: 30 Created: 1 /31 /2006 [1/31/06] With the offsite utility easement shown connecting to the Northern Lights Drive and Big Dipper Drive intersection being apparently done with this project, please specify patching limits for this work. An excavation permit along with street cut penalty fees would be required for this work. Number: 34 Created: 1 /31 /2006 [1/31/06] Sheet DR1 does not indicate a scale. Page I