Comment Number: 1
Comment Originated: 11/16/2011
11/16/2011: The legal description on the site plan needs to include "Lake Street Townhome
P.U:D.". This property is a platted subdivision.
Department: Water -Wastewater Engineering
Contact: Roger Buffington, 970.221-6854, rbuffington()fcgov.com
Topic: Construction Drawings
Comment Number: 1
Comment Originated: 11/15/2011
11/15/2011: Sewer televising records for the 10-inch sewer in Lake indicate three sewer
services extending to this site. Show and label these services on the utility plans. Add
appropriate notes and labels for the abandonment of any services which are not being used.
Comment Number: 2 Comment Originated: 11/15/2011
11/15/2011: Will the sewer service shown for the building be connecting to an existing sewer
service which extends to the site?
Comment Number: 3 Comment Originated: 11/15/2011
11/15/2011: Re -locate the curb stops and meter pits or re-route the underground electric
service so that it is not between the curb stops and meter pits. Provide 5 feet of separation
from the curb stops and meter pits. Schedule a meeting with Justin Fields from Light & Power
and myself to review options.
Comment Number: 4 Comment Originated: 11/15/2011
11/15/2011: Remove the interior water meter setting detail from the plans.
Comment Number: 5
Comment Originated: 11/15/2011
11/15/2011: Provide profiles of the water services, sewer service and fire line to show how
these will relate to the detention pond retaining wall and the detention pond elevations.
Comment Number: 6 Comment Originated: 11/15/2011
11/15/2011: Is the east 1-inch water service an irrigation service?
Comment Number: 7 Comment Originated: 11/15/2011
11/15/2011: See redlined utility plans for other comments.
Comment Number: 3 Comment Originated: 11/16/2011
11/16/2011: Provide the calculations for occupant loads that show room available for expected
crowds
Comment Number: 4 Comment Originated: 11/16/2011
11/16/2011: PFA discourages placing gates or other obstructions within or on the emergency
access easements (fire lanes). In this case only, a gate will be allowed as an item that has
been approved through negotiation with the neighborhood and the City.
Department: Stormwater Engineering
Contact: Wes Lamarque, 970-416-2418, wlamargue &fcgov.com
Topic: General
Comment Number: 1
Comment Originated: 11/15/2011
11/15/2011: Please label the Grading and Drainage Plan as the grading plan and include the
drainage basin exhibit in the plan set and label drainage plan.
Comment Number: 2 Comment Originated: 11/15/2011
11/15/2011: Please include the detention pond summary table and the basin summary table on
the drainage plan.
Comment Number: 3
Comment Originated: 11/15/2011
11/15/2011: The inlet on the east parking lot will not allow water to enter the detention pond up
to the 100-year water surface elevation. Water needs to be able to drain into the pond for the
duration of the 100-year storm. Another inlet set at the 100-year water surface elevation along
the parking lot gutter would resolve this issue.
Comment Number: 4 Comment Originated: 11/15/2011
11/15/2011: Drainage details are needed in the plan set.
Comment Number: 5 Comment Originated: 11/15/2011
11/15/2011: Please use detail D-10 of the City's standard Stormwater details for the sidewalk
culvert at the pond outfall. A concrete channel detail is also needed for this outfall.
Comment Number: 6 Comment Originated: 11/15/2011
11/15/2011: Reminder that a drainage easement is required dedicated to the City of Fort
Collins for the limits of the detention pond.
Comment Number: 7
Comment Originated: 11/15/2011
11/15/2011: Please add seed mix specifications on the landscape plan for the "lawn" located
in the detention pond that meet the guidelines in the Stormwater Detention Landscape
Standards.
Department: Technical Services
Contact: Jeff County, 970-221-6588, icounty(a)fcgov.com
Topic: General
Comment Number: 2 Comment Originated: 11/16/2011
11/16/2011: There are easements on this site that the building will be built over. These
easements will need to be vacated.
rate would be between 19-21 Ibs/PLS and would ideally be drill seeded between 1/4 - 1/2"
deep. Also, the use of a Kentucky Bluegrass hybrid (which ultimately uses less water and is
more drought tolerant) is also recommended. Thanks!
Department: Forestry
Contact: Tim Buchanan, 970-221-6361, tbuchanan(cDfcgov.com
Topic: General
Comment Number: 5
Comment Originated: 11/17/2011
11/17/2011: The code requirement for soil cultivation and amending should replace landscape
note #13.
Topic: Landscape Plans
Comment Number: 1
Comment Originated: 11/17/2011
11/17/2011: This comment is offered. At the SE area of the site the curb that runs east and west
by 6 parking places is very close to 4 walnut trees that are shown to be retained. Standard curb
with grading will likely damage the root system. The curb near these trees needs further
discussion and review because of how close it is to the trees. Forestry is available to meet on
site to review and discuss.
Comment Number: 2
Comment Originated: 11/17/2011
11/17/2011: Fallgold Ash is used as a street tree. This species is not on the City street tree list.
Select a species from the street tree list such as Skyline Honeylocust or Bur Oak to replace
Fallgold Ash.
Maximize use of canopy shade trees in the parkway with ornamental trees being used near
street lights. Ornamental trees should be at least 15 feet from street lights, and shade trees 40
feet.
Comment Number: 3
Comment Originated: 11/1712011
11117/2011: This comment is offered: In the plant list these three ornamental trees are listed at
#15 container. As to code they should be specified as 1.5 inch caliper BB.
Comment Number: 4
Comment Originated: 11/17/2011
11/17/2011: There is a nice hedge located along the east boundary of the east most house on
the south side of Summer Street. It appears to be on the property line. Will it be retained or
impacted by the proposed construction. It provides a nice vegetative barrier between the
properties.
Department: PFA
Contact: Ron Gonzales, 970-221-6635, rgonzalesftoudre-fire.org
Topic: General
Comment Number: 1 Comment Originated: 11/16/2011
11/16/2011: Address numerals are required to be visible from the street fronting the property.
Comment Number: 2 Comment Originated: 11/16/2011
11/16/2011: The mosque is required to be fire sprinklered.3
Topic: General
Comment Number: 6 Comment Originated: 11/15/2011
11/15/2011: As I understand it the following easements by separate document are to be
dedicated.
10 foot access easement (NS across site)
Emergency access and access easement (from Summer to Lake)
8 feet of row (along Lake Street)
9 foot utility easement (along Lake Street)
Drainage easement for detention pond
I can provide you with draft language for these documents; just let me know who you want it
emailed to. There is a $250 processing fee (TDRF) for each easement dedication and the
applicant is responsible for the recording fees for each document. The recording fees typically
are between $31 and $51 per document, the final amount being dependent on the number of
pages each document is.
Comment Number: 7
Comment Originated: 11/15/2011
11/15/2011: Development Agreement
I need the information for development agreement sheet filled out and returned so I can start
working on getting a draft development agreement together.
Comment Number: 8
11/15/2011: Existing plat
Comment Originated: 11/15/2011
Assuming that the property is platted and that plat is the Lake Street Townhomes, then although
the right-of-way was vacated by Ordinance #72, 1995 all the easements that were platted on that
plat still exist and should be shown on these plans. Other than the utility easements that will be
running under the proposed building I don't think the existing easements will hurt anything you
have proposed. It does seem you should vacate the easements that will be under the
building. The processing fees for an easement vacation are $400 (TDRF) per each type of
vacation. I will need the application fee and a drawing showing (a marked up plat will do.for
now) showing the area(s) proposed for vacation in order to route the request out to the utilities.
Once we know it is okay to vacate the utility easement I will need a legal description prepared
by a licensed surveyor and sketch describing and showing the area being vacated. The
vacation resolution can be approved administratively and the applicant is responsible for the
filing fees to record the document.
Topic: Site Plan
Comment Number: 5
Comment Originated: 11/15/2011
11/15/2011: Assuming that this property is platted the legal description on the cover should
start with Lake Street Townhome P.U.D, being a tract ...
Department: Environmental Planning
Contact: Lindsay Ex, 970.224.6143, lexpfcgov.com
Topic: Landscape Plans
Comment Number: 1
Comment Originated: 11/15/2011
11/15/2011: Is there a chance you would substitute Western Wheatgrass (Pascopyrum smithii)
for the Crested Wheatgrass you have specified in the landscape plans for the dryland grass
areas? Crested Wheatgrass is an introduced species and is less desirable in the City. Seeding
Comment Number: 5
Comment Originated: 11/16/2011
On the Landscape Plan, the note indicates that nuisance trees are to be removed at the
owner's option. Shouldn't these trees be removed as a matter of course?
Comment Number: 6
Comment Originated: 11/16/2011
On the architectural character elevations, the color of the split -face c.mu. should be further
defined as "earthtone" is vague.
Comment Number: 7
Comment Originated: 11/16/2011
On the architectural character elevations, there is no color specified for the detention pond
retaining wall at building foundation. This color should be specified and Staff recommends that
it be a darker tone than the building field.
Comment Number: 8
Comment Originated: 11/16/2011
On the Lighting Plan, there are ten locations where the foot-candle measurement, 20 feet west
of the property line, are greater than one -tenth. This should be addressed as the two adjoining
properties are residential. Please consider moving the fixtures further east and/or providing an
automatic dimmer switch to lower the foot-candles after 10:00 p.m.
Department: Engineering Development Review
Contact: Sheri Langenberger, 970.221.6573, slangenbergercD_fcgov.com
Topic: Construction Drawings
Comment Number: 1
Comment Originated: 11/15/2011
11/15/2011: Cover Sheet
Assuming that this property is platted the legal description on the cover should start with
Lake Street Townhome P.U.D, being a tract ...
Note 47. Remove the word 'list' and replace with 'NA'.
Comment Number: 2
Comment Originated: 11/15/2011
11/15/2011: Sheet C.3 -Add the standard street cut note to this sheet: Limits of street cut are
approximate. Final limits are to be determined in the field by the City Engineering Inspector.
All repairs to be in accordance with City street repair standards.
Comment Number: 3 Comment Originated: 11/15/2011
11/15/2011: Sheet C.3 -may want to add a note regarding the potential demolition of the
sidewalk west of the site on the south side of Summer Street.
Comment Number: 4
Comment Originated: 11/15/2011
11/15/2011: Sheet C.6 -on the Summer Street connection enlargement you are showing the
addition of 3.45 feet to the existing sidewalk. Standards allow for a minimum of 4 foot in width
to be added, so this needs to be changed to show that 4 feet is being added not 3.45. Also
adding to the sidewalk can only be done if the existing sidewalk is in good condition, so the
following note needs to be added to this detail. Four feet of additional sidewalk shall be
added to this existing sidewalk between the property line and the driveway to the east
providing that the existing sidewalk is deemed in good shape by the City Engineering
Inspector. If the City Engineering Inspector deems the existing sidewalk needs to be repaired
or replaced due to damage, heaving, and/ or breakage the existing curb, gutter, and sidewalk
shall be replaced with a vertical curb and 6 foot minimum sidewalk. If this occurs the curb
transition shall move west to the most western curb panel being replaced.
Cityof
�:ort
Community Development and
Neighborhood Services
281 North College Avenue
PO Box 580
Fort Collins, CO 80522
970.221.6750
970,224.6134 - fax
t6gov. com/de velopmentreview
November 18, 2011
Dana Lockwood
Lockwood Architects, Inc.
1027 W. Horsetooth Rd., Ste 200B
Fort Collins, CO 80526
RE: Islamic Center of Fort Collins, FDP110017, Round Number 1
Please see the following summary of comments from City staff and outside reviewing agencies for your
submittal of the above referenced project. If you have questions about any comments, you may contact the
individual commenter or direct your questions through the Project Planner, Ted Shepard, at 970-221-6343 or
tshepard@fcgov.com.
Department: Current Planning
Contact: Ted Shepard, 970-221-6343, tshepard(cDfcgov.com
Topic: General
Comment Number: 1
Comment Originated: 11/16/2011
The trash enclosure must be moved further north so as to be furhter away from the Kessler
house. Mr. Kessler has contacted the Current Planning Department and is emphatic that the
trash enclosure be shifted north.
Comment Number: 2
Comment Originated: 11/16/2011
Has any further consideration been given to the design of the operable gate? Since this is
Final Plan, the design of the gate should be finalized and shown on the site plan as a detail.
Comment Number: 3 Comment Originated: 11/16/2011
Signs indicating Mosque Only or No Public Parking should be installed in the parking lot south
of the gate.
Comment Number: 4
Comment Originated: 11/16/2011
On the Landscape Plan, it is unclear whether or not any significant trees are to be removed.
Staff is concerned about the removal of the 24-inch Walnut. If so, please indicate and then also
indicate how and where these trees are to be mitigated per Section 3.2.1(F).