[3/16/04] It is difficult to tell from the plan sets if there is an accessible ADA route
from the handicap parking stalls to the units. Please clarify this for the next submittal.
Number: 37 Created: 3/16/2004
[3/16/04] Bike parking is required for the new development. Please label and
identify on future plan sets. The bike racks will need to be located in a secure
location near the buildings main entrance and not impede pedestrian traffic.
Department: Water Wastewater Issue Contact: Jeff Hill
Topic: General
Number: 30 Created: 3/16/2004
[3/16/04] Our records indicate that the existing meter is located in the basement of
the current building. This proposed project will need to relocate the meter into a pit
outside. Show and label the location of the proposed meter pit and curb stop. Be
sure to adjust the landscape plan accordingly if the meter conflicts with the proposed
plant material.
Topic: Landscape Plan
Number: 31 Created: 3/16/2004
[3/16/04] Show the proposed meter pit and curb stop location on the landscape
plans and maintain the required landscape/utility separation distances.
See site, landscape and utility plans for other comments.
Department: Zoning Issue Contact: Peter Barnes
Topic: Zoning
Number: 26 Created: 3/12/2004
[3/12/04] The lot square footage must be shown on the plat, and the lot should be
labeled (i.e. Lot 1, or Tract 1, etc).
Number: 27 Created: 3/12/2004
[3/12/04] Show/label bike rack locations.
Number: 28 Created: 3/12/2004
[3/12/04] Something more than just rock mulch is required along the west side of
the structure.
Number: 29 Created: 3/12/2004
[3/12/04] In the Land Use Statistics box, under "Land Uses", need to clarify that the
"Existing Group Home (104 residents)" is going to be abandoned/demolished.
Otherwise, one gets the impression that the land uses are going to be the existing
group home plus the new proposed apartments.
Be sure and return all of your redlined plans when you re -submit and call If you have
any questions regarding these issues.
Page 4
Number: 20 Created: 3/2/2004
[3/2/04] Please use standard detail d-10 for the under -walk drain.
Number: 21 Created: 3/2/2004
[3/2/04] Please remove the drive -over curb and gutter detail since c&g in this area is
vertical.
Department: Light & Power Issue Contact: Doug Martine
Topic: Electric
Number: 1 Created: 3/1 /2004
[3/1/04] Normal electric development charges will apply with a credit given for the
existing electric service to be removed. In addition, charges to modify the electric
system will apply for installation costs of an underground power line from the source
in the alley approximately 200 ft. north of this site. A PRELIMINARY estimate of
these costs, based on currently available data, is in the $25,000.00 range. Electrical
heat is discouraged. Coordinate power requirements with Light & Power
Engineering (224-6152).
Department: PFA Issue Contact: Michael Chavez
Topic: General
Number: 33 Created: 3/16/2004
[3/16/04] ADDRESS NUMERALS; Address numerals shall be visible from the street
fronting the property, and posted with a minimum of 6 inch numerals on a
contrasting background. If bronze numerals are used they shall be on a black
background.
Number: 35 Created: 3/16/2004
[3/16/04] WATER SUPPLY: No commercial building shall be greater then 300 feet
from a fire hydrant. Each hydrant must be capable of delivering 1500 gallons per
minute at a residual pressure of 20 psi.
Number: 38 Created: 3/16/2004
[3/16/04] SPRINKLERS REQUIRED: This proposed building shall be fire
sprinklered. Poudre Fire Authority requires a "Knox Box" to be mounted on the front
of every new building equipped with a required fire sprinkler system or required fire
alarm system.
Department: Transportation Planning Issue Contact: Tom Reiff
Topic: Transportation
Number: 34 Created: 3/16/2004
[3/16/04] A Transportation Impact Study or an official waiver from the City's Traffic
Operations Department was not received. Please include the study or official waiver
with the next submittal.
Page 3
Topic: Site Plan
Number: 9 Created: 3/2/2004
[3/2/04] Please call out the existing ROW widths for the alley, Sherwood, and
Laurel, as well as the new ROW being dedicated along Laurel.
Number: 10 Created: 3/2/2004
[3/2/04] It appears that a 2'-3' column will be in the driveway entrance. Is this
correct?
Number: 11 Created: 3/2/2004
[3/2/04] Please clarify how many parking stalls will be removed on Sherwood Street
with the addition of the driveway for this project.
Number: 19 Created: 3/2/2004
[3/2/04] Please dimension the on -street parking stalls.
Number: 22 Created: 3/2/2004
[3/2/04] If the two first -floor units are supposed to be handicapped accessible, then
shouldn't additional sidewalks be provided so that residents can easily access the
front doors from the handicapped parking stalls provided? The current configuration
forces them into the pond, grass, or a very circuitous paved route.
Topic: Utility Plans
Number: 12 Created: 3/2/2004
[3/2/04] Please see the revised utility plan checklist for any additional items.
Number: 13 Created: 3/2/2004
[3/2/04] It would be helpful to have an overall utility plan separate from the grading
and drainage plan. It's difficult to see where everything is going on the current plan.
Number: 14 Created: 3/2/2004
[3/2/04] Sheet 4 - Please label and dimension all ROW, new and existing.
Number: 15 Created: 3/2/2004
[3/2/04] Please label the driveway as being constructed with concrete within the
ROW.
Number: 17 Created: 3/2/2004
[3/2/04] Please shift the trash enclosure slightly to the south so that the doors do not
open into the alley ROW.
Number: 18 Created: 3/2/2004
[3/2/04] Please label the driveway width proposed.
Page 2
STAFF PROJECT REVIEW
City of Fort Collins
s�
EAST POINT STUDIO, LLC Date: 03/22/2004
DON BROOKSHIRE
3207 KITTERY CT.
FT. COLLINS, CO 80526
Staff has reviewed your submittal for ATRIUM SUITES, 502 W. LAUREL PDP -
TYPE II, and we offer the following comments:
ISSUES:
Department: Engineering Issue Contact: Katie Moore
Topic: General
Number: 7 Created: 3/2/2004
[3/2/04] Please see redlines for any additional comments.
Number: 23 Created: 3/2/2004
[3/2/04] The sidewalk on Laurel is required to be a minimum of 6' wide. It is shown
as 4' on the plans, so there are two options for widening the walk: remove the walk
and replace it with a 6' walk, or add 4' of concrete to the additional walk per LCUASS
(4' is the minimum width of concrete that is allowed to be added to widen a
sidewalk).
Topic: Landscape Plan
Number: 8 Created: 3/2/2004
[3/2/04] Please show the utilities on the landscape plan, so that the separation
requirements can be verified.
Topic: Plat
Number: 2 Created: 3/2/2004
[3/2/04] Please use the current standard plat language. (See attached.)
Number: 3 Created: 3/2/2004
[3/2/04] According to City records I found, the ROW for Sherwood should be 100',
not 80'.
Number: 4 Created: 3/2/2004
[3/2/04] Please list the reception number or book and page number for the Laurel
Street ROW vacation shown and provide a width for it.
Number: 5
[3/2/04] Please fill in the title block.
Created: 3/2/2004
Number: 6 Created: 3/2/2004
[3/2/04] Please show the 15' utility easement along Laurel. It should match the
utility plans.