HomeMy WebLinkAboutSUBWAY @ 651 SE FRONTAGE RD. - PDP - PDP120016 - CORRESPONDENCE - (4)•
COMMITTED TO EXCELLENCE
May 31, 2012
Jason Holland, Project Planner
Current Planning, City of Ft Collins
Re: Preliminary Plat Review - PDP120016
Hi Jason,
Steve Miller, Assessor
200 West Oak Street, Suite 2000
PO Box 1190
Fort Collins, CO 80522-1190
I C 9C 0T
JUN 0 4 2012 D
I am sending along a question instead of any comments on areas of concern in
regards to the Plat of Interchange Business Park. It is not clear to me what
changes will be taking place. If you wouldn't mind just emailing me with a brief
description of the scope of the project I would appreciate it. That way I can
double check our usual criteria for preliminary preview and get back to you if I
do have any concerns. I do have the copy of the old original plat of Interchange
Business Park that was sent along with your project comment sheet.
Thank you,
Megan Harrity
Subdivisions, Larimer County Assessor's Office
970-498-7065
mharrity@larimer.org
Phone:970-498-7050 Fax:970-498-7070 www.larimer.oro/assessor
Department: Zoning
Contact: Noah Beals, 970.416-2313, nbeals(a)fcgov.com
Topic: General
Comment Number: 14 Comment Originated: 06/04/2012
06/04/2012: LUC 3.2.2(J) Parking Lot Setbacks from property line along a non -arterial street is
10 ft.
LUC 3.2.1(E) 6% of the interior parking lot is required to be landscaped.
Comment Number: 15
Comment Originated: 06/06/2012
O6/06/2012: LUC 3.2.2(C)(5)(a) Walkways shall connect street sidewalks with building entries
with Directness and continuity.
The proposed sidewalk connection does not meet the standard, more connections along the
north and east sided of the property to the public right of way are needed.
Department: Zoning
Contact: Noah Beals, 970-416.2313, nbeals@fcaov.com
Topic: General
Comment Number: 7 Comment Originated: 05/31/2012
05/31/2012: Land Use Code (LUC) 4.21(F) Development located within one -quarter mile of the
centerline of 1-25 shall be subject to Division 3.9 of LUC.
Comment Number: 8 Comment Originated: 06/01/2012
O6/01/2012: 3.9.4(A) Parking lot Perimeter Landscaping 75% of all parking lot areas shall be
screened from nearby streets, public right or ways, public open spaces by at least one of the
following three methods: 1) a berm 3 feet tall with maximum slope of 3:1 in combination of
evergreen shrubs and trees 2) hedge at lest 3 ft tall consisting of a double row of shrubs
capable of growing into hedge within 3 years of installation 3) decorative fence or wall between
3 to 4 ft in height in combination with trees and shrubs.
Comment Number: 9
Comment Originated: .06/01/2012
06/01/2012: 3.9.5(B) Buildings that face public street adjionding developments or connecting
pedestrian frontage shall be articulated, fenestrated and proportioned to human scale along at
least 60% of the facade using features such as windows, entrances, arcades, arbors or
awnings.
The proposed elevations on the south and east side of the building is divided by hardie board
trim, but this does not adequitly meet this standard.
Comment Number: 10
Comment Originated: 06/01/2012
06101/2012: 3.9.5(B)(2) Building Facades facing a primary access street shall have clearly
defined, highly visible customer entrances that feature at least two of the following:
Canopies/porticos, overhangs, recesses or projections of at least 3% of the wall, length,
Arcades, Distinctive roof forms, Arches, Outdoor patios, Display windows, Planter or wing walls
the incorporate landscaped areas and/or places for sitting.
Comment Number: 11
Comment Originated: 06/01/2012
06/01/2012: 3.5.3(B)(2) Requires a commercial building to meet build -to -lines, meaning the
building should not sit back any further from the property then 15ft.
Since the original plat established building envelopes and setbacks the proposed building
should be brought to the north and east building envelope line.
Comment Number: 12
Comment Originated: 06/01/2012
O6/01/2012: LUC 3.5.3(C) Horizontal masses shall not exceed a height:width ratio of 1:3 without
substantial variation in massing that includes a change in height and projecting or recessed
elements
The proposed elevations on the east side of the building is divided by hardie board trim, but
this does not adequitly meet this standard.
Comment Number: 13 Comment Originated: 06104/2012
06/04/2012: LUC 3.5.3 (D)(6)(b)2. A recognizable "top" a sloping roofs with overhangs and
brackets.
1
Department: Technical Services
Contact: Jeff County, 970.221.6588, jcounty(o)fcgov.com
Topic: Lighting Plan
Comment Number: 4
06/11/2012: No comments.
Topic: Site Plan
Comment Number: 1
06/11/2012: No comments.
Department: Traffic Operation
Contact: Ward Stanford, 970.221.6820, wstanfordna fcgov.com
Topic: Construction Drawings
Comment Number: 1
Comment Originated: 06/11/2012
Comment Originated: 06/11/2012
Comment Originated: 06/18/2012
06/18/2012: Construction Notes, sheet C2: Please revise each location where "Local Entity
Engineer" is used under the Traffic Signing and Pavement Marking Construction Notes, to state
"Local Entity Traffic Engineer".
Department: Zoning
Contact: Noah Beals, 970.416.2313, nbeals(afcgov.com
Topic: General
Comment Number: 1 Comment Originated: 05/31/2012
05/31/2012: An access easement with the lot to the west (OUTLOT B of INTER CHANGE
BUSINESS PARK) will need to be recorded.
Comment Number: 2 Comment Originated: 05/31/2012
05131/2012: Any work on the lot to the west (OUTLOT B of INTER CHANGE BUSINESS PARK)
does not receive approval from this POP and FDP. The lot to the west is located in the county
and any work on this lot will need county approval.
Comment Number: 3 Comment Originated: 05/31/2012
05/31/2012: No signs or their locations are approved by the POP and FDP. Sign and locations
are approved through a separate sign permit.
Comment Number: 4 Comment Originated: 05/31/2012
05/31/2012: Need elevations for all structures (trash/recycling enclosures and freezers...).
Comment Number: 5 Comment Originated: 05/31/2012
05/3112012: Mechanical/utility equipment (vent, conduits, meters, RTU... ) locations need to be
identified on the plans (site, landscaping, and elevations) with a note on how they will be
screened/painted.
Comment Number: 6 Comment Originated: 05/31/2012
05/3112012: Trash Enclosure needs to be designed with a walk-in access without having to
open the main service gate.
C
Department: Park Planning
Contact: Craig Foreman, 970.221.6618, cforeman(a)fcgov.com
Topic: General
Comment Number: 1
05/21/2012: No comments
Department: Stormwater Engineering
Contact: Wes Lamarque, 970.416.2418, wlamargue(a)fcgov.com
Topic: General
Comment Originated: 05/21/2012
Comment Number: 1 Comment Originated: 06/07/2012
06/07/2012: A drainage easement is required for the limits of the detention pond.
Comment Number: 2 Comment Originated: 06/07/2012
06/07/2012: Please document in the text of the drainage report the outfall to the west of the site
since this was not the originally designed path for this site. Explain the route all the way to
Boxelder Creek. Drainage easements must exist down to Boxelder Creek to use the west
outfall.
Comment Number: 3 Comment Originated: 06/07/2012
06/07/2012: A release rate of .03 cfs is not practical and clogging would most likely occur with
an orifice this small. This site can use .25 cfs as a release (.50 cfs/acre). The City of Fort
Collins does not use Urban Drainage's hydrology criteria.
Comment Number: 4 Comment Originated: 06/07/2012
O6/07/2012: The detention pond is undersized. The required detention with a .03 cfs release is
4,500 cf and 3,000 cfs for a .25 cfs release. Please revise.
Comment Number: 5 Comment Originated: 06/07/2012
O6/07/2012: RCP is required within the City ROW. Please revise the detention pond's outlet
pipes.
Comment Number: 6 Comment Originated: 06/07/2012
06/07/2012: Please use the City's standard water quality outlet structure.
Department: Technical Services
Contact: Jeff County, 970.221.6588, jcounty@fcgov.com
Topic: Building Elevations
Comment Number: 3 Comment Originated: 06/11/2012
O6/11/2012: No comments.
Topic: Construction Drawings
Comment Number: 5 Comment Originated: 06/11/2012
06/11/2012: There are line over text issues on sheets C4 & C5.
Topic: Landscape Plans
Comment Number: 2 Comment Originated: 06/11/2012
06/11/2012: No comments.
1
Department: Forestry
Contact: Tim Buchanan, 970.221-6361, tbuchanan(a)fcgov.com
Topic: Landscape Plans
Comment Number: 1 Comment Originated: 06/12/2012
06/12/2012:
Not all of the trees are clearly labeled. The tree and shrub list should include size, method of
transplant and number used. Standard transplant method is Balled and Burlapped. Minimum
sizes for trees are:
Shade Trees 2.0 inch caliper
Ornamental Trees 1.5 inch Caliper
Evergreen Trees 8 feet height.
Comment Number: 2
06/12/2012: Please add these landscape notes:
Comment Originated: 06/12/2012
• The soil in all landscape areas, including parkways and medians, shall be thoroughly
loosened to a depth of not less than eight (8) inches and soil amendment shall be thoroughly
incorporated into the soil of all landscape areas to a depth of at least six (6) inches by tilling,
discing or other suitable method, at a rate of at least three (3) cubic yards of soil amendment
per one thousand (1,000) square feet of landscape area.
• A permit must be obtained from the City forester before any trees or shrubs as noted on
this plan are planted, pruned or removed on the public right-of-way. This includes zones
between the sidewalk and curb, medians and other city property. This permit shall approve the
location and species to be planted. Failure to obtain this permit may result in replacing or
relocating trees and a hold on certificate of occupancy.
Department: Light And Power
Contact: Doug Martine, 970.224.6152, dmartine(cDfcgov.com
Topic: General
Comment Number: 1
Comment Originated: 05/31/2012
05/3112012: Power requirements, a location for an electric transformer, and electric
development charges will need to be coordinated with Light & Power Engineering
(970)221-6700.
Comment Number: 2 Comment Originated: 05/31/2012
05/31/2012: Relocation of the existing electric equipment will be at the expense of the
developer.
Comment Number: 3
Comment Originated: 05/3112012
05/31/2012: Light & Power will need a copy (paper or pdf) of the recorded plat.
Comment Number: 4 Comment Originated: 05/31/2012
05/31/2012: An AutoCad (v.2008) drawing of the final site plan will need to be sent to Terry Cox
at TCOX@FCGOV.COM.
Department: Engineering Development Review
Contact: Tyler Siegmund, 970.416.2779, tsleg mundna fcgov.com
Topic: General
Comment Number: 8 Comment Originated: 06/15/2012
06/13/2012: An access easement or right of way will need to be dedicated where the sidewalk
along the SE Frontage Rd routes around the existing utility boxes. Without a replat, this
process will need to be done by separate document using the City's Transportation
Development Review Fee form (TDRF). For additional information on these fees, please see:
hftp://www.fcgov.com/engineering/dev-review.php
Since you are not planning on replating the property, all easement vacations (if needed) and
referenced dedication above will need to be done by separate document.
a. Each easement dedication request has a TDRF of $250 for the processing and review of
the dedication. The recording fees will also need to be provided once we know how many
documents and pages there are. Please contact me if you need more information about this
process.
Comment Number: 9
Comment Originated: 06/15/2012
O6/1312012: To achieve pedestrian connectivity level of service, a sidewalk and handicap
ramps will need to be installed along the west side of the SE Frontage Rd up to the traffic light
to accommodate pedestrians accessing the development.
Comment Number: 10 Comment Originated: 06115/2012
O6/13/2012: Reinforced Concrete Pipe (RCP) is required for drainage facilities in the right of
way. Please revise the plans.
Comment Number: 11 Comment Originated: 06/15/2012
06/13/2012: A meting with CDOT has been rescheduled for Friday, June 22nd to discuss
concerns and requirements related to the development. Revised comments that address their
concerns will be provided shortly after the scheduled meeting.
Department: Environmental Planning
Contact: Lindsay Ex, 970.224.6143, lex(@,fccjov.com
Topic: General
Comment Number: 1 Comment Originated: 06/08/2012
06/08/2012: No comments.
Department: Forestry
Contact: Tim Buchanan, 970-221.6361, tbuchanan(cDfcaov.com
Topic: Landscape Plans
i
117
Department: Current Planning
Contact: Jason Holland, 970.556.3176, Iholland(a)fcgov.com
Topic: Site Plan
Comment Number: 1
Comment Originated: 06/08/2012
O6/0812012: Recycling will be required within the trash enclosure. Refer to section 3.2.5 and the
standard details that were sent to the design team via email.
Comment Number: 2
Comment Originated: 06/08/2012
O6/08/2012: Please verify that the HC ramp to the south meets standard clearance
requirements at top of ramp. It appears that the ramp may be too close to the comer of the
building, verify with engineering staff that this is acceptable.
Comment Number: 3
Comment Originated: 06/08/2012
06/08/2012: The 4.5' sidewalk dimension in front of the building is tight. A minimum of five to
six feet is preferred to the face of curb.
Department: Engineering Development Review
Contact: Tyler Siegmund, 970-416.2779, tsiegmund(7a fcgov.com
Topic: General
Comment Number: 1
Comment Originated: 06/13/2012
06/13/2012: Update general note #19 on the cover sheet to reference current project drainage
and erosion control study
Comment Number: 2
Comment Originated: 06/13/2012
06/13/2012: Update Geotech report reference to current project geotech report
Comment Number: 3 Comment Originated: 06/13/2012
O6/13/2012: Label the radius on the horizontal control plan for new the drive approach off of
State Highway 14 Frontage Road
Comment Number: 4 Comment Originated: 06/13/2012
O6/13/2012: An access easement/agreement from the adjacent property owner to the west will
be required for the west point of access
Comment Number: 5 Comment Originated: 06/13/2012
O6/13/2012: A letter of intent for a construction easement will be required from the adjacent
property owner for the improvements proposed on the west property line. An additional letter
of intent from the adjacent property owner will also be required for the access easement for the
west point of access to the development. These letters will need to be provided prior hearing.
Comment Number: 6 Comment Originated: 06/13/2012
06/13/2012: An access easement will need to be dedicated where the sidewalk in the public
right of way routes around existing utility boxes.
Comment Number: 7 Comment Originated: 06/13/2012
06/13/2012: The lot to the west is currently located in county limits, any work proposed on this
lot will need county approval.
L
Fort Collins
June 19, 2012
Chad Knoth
Excell fund Development, LLC
3400 E. Bayaud Ave. #290
Denver. CO 80209
RE: Subway at 651 SE Frontage Rd, PDP120016,. Round Number 1
1
Community Development and
Neighborhood Services
281 North College Avenue
PO Box 580
Fort Collins. CO 80522
970.221.6750
970,224.6134 - fax
fcgov.com/deve/0pmentreview
Please see the following summary of comments from City staff and outside reviewing agencies for your
submittal of the above referenced project. If you have questions about any comments, you may contact the
individual commenter or direct your questions through the Project Planner, Jason Holland, at 970-556-3176
or jholland@fcgov.com.
Comment Summary:
Department: Current Planning
Contact: Jason Holland, 970-5563176, tholland(c fcgov.com
Topic: Landscape Plans
Comment Number: 4
Comment Originated: 06/08/2012
06/08/2012: Related to to comment three: 3.2.1(E)(2)(d) requires at least five feet of
landscaping in front of 50% of the building. An effort to put more landscaping at the building
entrance and building face should be investigated. Perhaps the eastern 25' building setback
along the frontage road could be reduced. The LUC code may allow a 15- 25' building
setback range. At a minimum, a shade tree should be placed in a cut-out or tree grate directly
south of the HC parking space. A proposed tree south of the building can be relocated to
meet this requirement. Refer to redline plan.
Comment Number: 5
Comment Originated: 06/08/2012
06/08/2012: The parking median to the west needs landscape shrubs or perennial material and
an additional shade tree. Please show some options for this.
Comment Number: 6 Comment Originated: 06/08/2012
06/08/2012: Please add the standard City landscape notes to the plans and show tabulations
for tree species diversity.
Comment Number: 7 Comment Originated: 06/08/2012
06/08/2012: The plant list needs to show the common/scientific name, quantity, size/caliper,
and water use for each plant.
Comment Number: 8 Comment Originated: 06/08/2012
06/08/2012: Please note that irrigation plans are required prior to issuance of builing permit.