Department: Stormwater-Water-Wastewater Issue Contact: Roger Buffington
Topic: WaterMastewater
Number: 20 Created: 9/27/2010
[9/27/10] A discussion is needed on water metering. For duplexes, separate meters are
normally required for each unit. It may make sense to also provide separate meters for the
triplex. Please call to discuss this matter (221-6854).
Number: 21 Created: 9/27/2010
[9/27/10] Extend separate sewer services from the buildings to the manhole shown in the
alley.
Number: 22 Created: 9/27/2010
[9/27/10] Label all sewer service clean -outs in paved areas as traffic -rated and add
Standard Detail 15.
Number: 23 Created: 9/27/2010
[9/27/10] Label curb stops.
Department: Zoning Issue Contact: Jenny Nuckols
Topic: Zoning
Number: 3 Created: 9/20/2010
(9/20/10] Handicap Van Accessible parking space needs to be an overall width of 16' with
an HC Van Accessible sign at the front of the space between 3' and 5 tall.
Number: 4 Created: 9/20/2010
[9/20/10] According to the plans this is two lots, but only one address is being called out.
Each lot should have its own address.
Number: 5 Created: 9/20/2010
[9/20/10] Elevations: Please note which drawing belongs to which building. This can be
done by separate addresses when second address is determined.
Number: 6 Created: 9/20/2010
[9/20/10] Please note the max building height on the elevations.
Number: 7 Created: 9/20/2010
[9/20/10) Please note building colors on the elevations.
Number: 8 Created: 9/20/2010
[9/20/10] I'd recommend a bike rack for each building.
Number: 9 Created: 9/20/2010
[9/20/10] Foundation plantings are needed along the east wall of the easterly most building.
As well as along the west wall to match the wall of the building across the courtyard.
Number: 10 Created: 9/20/2010
[9/20/10] I'm guessing that grass is going to be installed along West Laurel, on either side of
the sidewalk - No grass symbol is called out in the Planting schedule/key
Page 4
Topic: Photometric Plan
Number: 16 Created: 9/24/2010
[9/24/10] Please add a north arrow & scale to the Photometric Plan.
Topic: Site Plan
Number: 14 Created: 9/24/2010
[9/24/10] There are scanning issues on the Site Plan. Please "block out" the text in
hatching.
Topic: Subdivision Plat
Number: 11 Created: 9/24/2010
[9/24/10] The boundary of the Plat closes.
Number: 12 Created: 9/24/2010
[9/24/10] Please change the Subdivision Plat title. We prefer not having numbers or
addresses. We suggest "Appleblossom Subdivision".
Number: 13 Created: 9/24/2010
[9/24/10] There is a "5.00"' dimension on the Plat, that doesn't appear to be defining
anything.
Topic: Utility Plan
Number: 17 Created: 9/24/2010
[9/24/10] Please correct the sheet index on the Utility Plan. See redlines.
Number: 18 Created: 9/24/2010
[9/24/10] There are scanning issues on sheets C1.0 & C4.0 of the Utility Plans.
Number: 19 Created: 9/24/2010
[9/24/10] Please correct the north arrows on sheets C4.0 & C4.1 of the Utility Plans.
Department: Stormwater-Water-Wastewater Issue Contact: Wes Lamarque
Topic: Stormwater
Number: 24 Created: 9/28/2010
[9/28/10] The water quality feature near Laurel Street does not meet City standards. The
design needs to meet criteria in the Urban Drainage Manual. This.may include providing
approved media and an underdrain.
Number: 25 Created: 9/28/2010
[9/28/10] It appears the water quality feature near Laurel Street was implemented due to
the outfall pipe required for the pervious pavement. A positive outfall is required for the
outfall pipe. This can be done by a water quality feature that meets the Urban Drainage
Manual's criteria, or by a positive outfall via pipe or curb chase.
Number: 26 Created: 9/28/2010
(9/28/10] The slopes along the east property boundary are too steep and drainage could
negatively impact the property to the east. Small retaining walls may be required just east of
the parking lot and the structure.
Page 3
• A permit must be obtained from the City forester before any trees or shrubs as noted
on this plan are planted, pruned or removed on the public right-of-way. This includes zones
between the sidewalk and curb, medians and other city property. This permit shall approve
the location and species to be planted.
Department: Light & Power Issue Contact: Doug Martine
Topic: Light & Power
Number: 1 Created: 9/10/2010
[9/10/10) A 6 ft. wide utility easement will be necessary along the entire north property line
of Lot #1. Installation of a pad type electric transformer will be necessary at the N.W. corner
of lot #1. Electric development and system modification charges will apply.
Department: PFA Issue Contact: Carle Dann
Topic: Fire
Number: 27 Created: 9/29/2010
CONFLICTING INFORMATION
The letter from the applicant states there will be two duplexes constructed. The Statement of
Planning Objectives states there will be one duplex and one triplex. If there are two
duplexes, then the only requirements (fire hydrant location and address being mounted on
the structures) has already been communicated and acknowledged.
Number: 28 Created: 9/29/2010
FIRE SPRINKLERS
If a triplex is on fact being proposed, the following comment shall apply:
RESIDENTIAL AUTOMATIC FIRE SPRINKLERS
An automatic sprinkler system installed in occupancies in accordance with Section 903.3
shall be provided throughout all buildings with a Group R (Residential) fire area. Residential
or quick -response standard sprinkler heads shall be used in dwelling units and guest -room
portions of the building. 2006 International Fire Code 903.2.7
Department: Transportation Planning Issue Contact: Matt Wempe
Topic: Transportation Planning
Number: 2 Created: 9/14/2010
[9/14/10] Please consider an alternative location for the bicycle parking (perhaps the
courtyard?). The ideal location is on a hard surface, well -lit, protected from the elements,
and near the main entrance of the building. The current location, next to the trash cans,
doesn't seem like it would meet many of these criteria.
Department: Technical Services Issue Contact: Jeff County
Topic: Landscape Plan
Number: 15 Created: 9/24/2010
[9/24/10] There are scanning issues on the Landscape Plan. Please "block out" the text in
hatching.
Page 2
" STAFF PROJECT REVIEW
Citv of Fort Collins
Prue Kaley, Mark Goldrich Date: 10/1/2010
The Birdsall Group - Jim Birdsall
444 Mountain Ave.
Berthoud, CO 80513
Staff has reviewed your submittal for 712 W. LAUREL STREET PDP - Type II (aka
Appleblossom LLC), and we offer the following comments:
ISSUES:
Department: Engineering Issue Contact: Susan Joy
Topic: General
Number: 30 Created: 9/30/2010
[9/30/10] A utility coordination meeting was held on September 22, 2010. Easement
requirements and utility locations were discussed in hopes of reducing our standard
easements off the alley. As the result of that meeting, the site layout was "flipped" and will
be routed via email for final approval from the utilities. Once this approval is received, the
project is ok to go to the public hearing. In the event this is not completed in time for the
hearing, I am still allowing the project to proceed with the condition that further utility
requirements may alter the final easements in Final Compliance and the developers may
proceed at their own risk.
Number: 31 Created: 9/30/2010
[9/30/10) All preliminary requirements have been satisfied on the plan sets and we're ready
for the Final Compliance submittal.
Number:32 Created: 9/30/2010
[9/30/10] 1 only have redlines from Tech Services to return. Nothing from me.
Department: Forestry Issue Contact: Tim Buchanan
Topic: Landscape Plan
Number: 29 Created: 9/29/2010
[9/29/10] A large significant Blue Spruce located on the east center portion of the lot is
shown to be removed. Five upsized mitigation trees need to be provided for this tree.
Mitigation trees need to be (shade trees 3.0 inch caliper, Evergreen Trees 8 feet height or
ornamental trees 2.5 inch caliper). A large significant Norway Maple is located about 5-6
feet off the north wall of the proposed west building. Foundation placement this close to the
tree will do significant root damage. The applicant should explore spanning the zone of the
root system with an alternative to a traditional foundation. Add tree protection notes from
3.2.1 G.
Add the following planting notes:
• The soil in all new landscape areas, including parkways and medians, shall be
thoroughly loosened to a depth of not less than eight (8) inches and soil amendment shall
be thoroughly incorporated into the soil of all landscape areas to a depth of at least six (6)
inches by tilling, disking or other suitable method, at a rate of at least three (3) cubic yards of
soil amendment per one thousand (1,000) square feet of landscape area.