HomeMy WebLinkAboutWILLOW BROOK, FILING THREE - PDP - 32-10 - CORRESPONDENCE - UTILITY PLANSFORT COLLINS•LOVELAND WATER DISTRICT SOUTH FORT COLLINS SANITATION DISTRICT v d� December 7, 2010 Mr. Ted Shepard, Planner City of Fort Collins P.O. Box 580 Fort Collins, CO 80525 RE: #32-10 Willow Brook - 3`d Filing PDP — Type I First Submittal Dear Mr. Shepard, The Fort Collins - Loveland Water District and the South Fort Collins Sanitation District have reviewed the above mentioned project and submit the following comments. The waterline note on sheet 3 of 13 needs to be correct to indicate a minimum of 5 feet bury and a maximum of 6 feet. The existing fire hydrants located along the north and south property line are 8 inch stubs for future use. The 8 inch valve cannot be reused on a 6 inch fire hydrant lateral. There is one existing'/4 inch irrigation tap generally located 200 feet east of Lady Moon and south of Rock Creek. What is the proposed use onsite? The meter is the property of the District and is to be removed by the District upon request by the owner. The remaining 5 - % inch service stubs do not have meters. The proposed water line connections on Galileo Drive indicate tapping valves with cut -in valves. This needs to be corrected to indicate cut -in valves and swivel tees. The proposed relocated fire hydrant assembly call out on Rock Creek Drive indicates an "FG" assembly, it should indicate an "FH" assembly. The District will provide further comment when the construction drawings are submitted for review. Please do not hesitate to contact me at 226-3104, ext. 104, if you have any questions. or require additional information. Respectfully, Mrwrry W. Farrill, P.E. District Engineer xc: Mr. Michael D. DiTullio, District Manager Village Homes 5150 Snead Drive, Fort Collins, CO 80525 Phone (970) 226-3104 Fax (970) 226-0186 TST, INC. CONSULTING ENGINEERS December 17, 2010 Mr. Terry Farrill Fort Collins -Loveland Water District South Fort Collins Sanitation District 5150 Snead Drive Fort Collins, CO 80525 Re: Willow Brook Filing No. 3 — Observatory Village Project No. 0963.0005.00 Dear Mr. Farrill, This letter is in response to the comments for the first review of the Preliminary Development Plan for Willow Brook Filing No. 3 — Observatory Village. We believe that we have adequately addressed any comments that you have made and that the revised plan reflects the changes required by the District for Preliminary Plan. 1. Waterline note on sheet 3 has been corrected to indicate 5 to 6 feet of bury. 2. Notes on the demolition and utility plans have been corrected to indicate a 6" valve is required and to relocate the 8" valve as possible. 3. Notes have been corrected to state that the pit should be relocated and to "protect in place" the irrigation meterlservice since it appears to still be in use. 4. Notes have been modified to clarify that the sleeve is a solid sleeve for cutting in a tee and valve, not a wet -tap saddle. Tee has been changed to "swivel" type. 5. "FG" has been corrected to "FH". Thank you for your comments and consideration of the project plan. We look forward to your review and comments and will gladly answer any questions that you may have. Sincerely, TST, INC. CONSULTING ENGINEERS 760 Whalers Way Bldg C Suite 200 Fort Collins, CO 60525 970.226.0557 metro 303.595,5.9103 fax 970. 226.0204 info@tstinc.co Ryan O. Banning, P.E. w .tstinc.co ROB 0