Contact: Roger Buffington, 970.221-6854, rbuffington(cDfcqov.com
Topic: Construction Drawings
Comment Number: I Comment Originated: 07/17/2012
07/17/2012: The existing sewer service is noted as a drop connection in the utility database. If
the invert of the new service is more than 2 feet above the sewer exiting the MH, install an
outside drop connection.
Topic: Landscape Plans
Comment Number: 2 . Comment Originated: 07/17/2012
07/17/2012: Show the fire line and domestic water service on the landscape plan and adjust
trees and shrubs to provide the required separation distances.
Department: Zoning
Contact: Noah Beals, 970.416-2313, nbeals(a)fcqov.com
Topic: General
Comment Number: 1 Comment Originated: 07/16/2012
07/1612012: Sheet Al the north building elevation A note pointing to the Metal Panel labels it
as CMU Block
k
Department: Light And Power
Contact: Doug Martine, 970.224-6152, dmartine@fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 06/25/2012
O6/2512012: Builder will need to coordinate power requirements, electric meter location, and
electric development charges with Light & Power Engineering (221-6700).
Comment Number: 2 Comment Originated: 06/25/2012
06/25/2012: After the site plan is final an AutoCad drawing (V2008) needs to be sent to Terry
Cox (TCOX@FCGOV.COM).
Department: Stormwater Engineering
Contact: Wes Lamarque, 970-416.2418, wlamargue@fcgov.com
Topic: General
Comment Number: 1 Comment Originated: 07/17/2012
07/17/2012: More detail is needed for the Rain Garden. The outlet sturcture needs to be
shown with the spill elevation. The grading from the pond to the sidewalk is too steep. This
should be a 4 to 1 slope.
Comment Number: 2 Comment Originated: 07/17/2012
07/17/2012: The rain garden needs to be in a drain gqqasement. OK
Comment Number: 3 Comment Originated: 07/17/2012
07/17/2012: Please include the soil media se 6citicaNbons on the Detail Sheet 11.
,
Department: Technical Services
Contact: Jeff County, 970.221-6588, jcountv(@fcg 'V.com
Topic: Building Elevations "I VIIIII
Comment Number: 3 Comment Originated: 07/13/2012
07/13/2012: No comments.
Topic: Construction Drawings
Comment Number: 4
07/13/2012: There are text over text issues on sheet 5.
Topic: Landscape Plans
Comment Number: 2
07/13/2012: No comments.
Topic: Site Plan
Comment Number: 1
07/13/2012: No comments.
Department: Water -Wastewater Engineering
Contact: Roger Buffington, 970-221.6854, rbuffington(D.fcaov.com
Comment Originated: 07/13/2012
Comment Originated: 07/13/2012
Comment Originated: 07/13/2012
i
Department: Engineering Development Review
Contact: Andrew Gingerich, 970.221.6603, aginaerich(afc-gov.com
Topic: Construction Drawings
Comment Number: 3 Comment Originated: 07/17/2012
07/17/2012: Sheet 3 - Repeat Comment from PDP "The curb head along Elizabeth and near
the existing handicap ramps at the corner of City Park and Elizabeth in in need of repair. These
sections of curb head will need to be removed and replaced as necessary".. Please add a
note to the demolition plan in place of the current "protect in place" or add reference to note .
Comment Number: 4 Comment Originated: 07/17/2012
07/17/2012: Sheet 4 - Please include additional dimensioning and callouts for sidewalks,
parking stall depth, access width, etc.
Comment Number: 5 Comment Originated: 07/17/2012
07/17/2012: Sheet 5 - Please correct the couple of text over text occurences on this sheet.
Comment Number: 6 Comment Originated: 07/17/2012
07/17/2012: Sheet 6 - Label curb and gutter type and locations within the parking lot and
provide corresponding curb and gutter details on detail sheets.
Comment Number: 7 Comment Originated: 07/17/2012
07/17/2012: Sheet 9 - Please label on the Horiz. control,plan and/or grading plan the different
curb and gutter types being proposed and show the`corrre ondmg details.
Comment Number: 8 L Comment Originated: 07/17/2012
07/17/2012: Sheet 9 - Please provide the detail, or°t edri way being proposed (707).
Comment Number: 9
07/17/2012: Sheet 10 - Is
please provide a detail.
Comment Number: 10
07/17/2012: Sheet 10 - It i
proposed.
Comment Number: 11
Comment Originated: 07/17/2012
being proposed on the project? If so,
Comment Originated: 07/17/2012
site plan the concrete channel detail is being
Comment Originated: 07/17/2012
07/17/2012: Sheet 11 - The design sheets callout a "rain garden" but the detail for the porous
landscape detention area does not mention rain garden. Please ensure detail and callout are
consistent in callouts.
Comment Number: 12 Comment Originated: 07/17/2012
07/17/2012: Please provide some grade arrows with slope callouts on the grading plan.
Specifically in the area of the handicap parking stall and driveway approaches.
Topic: Site Plan
Comment Number: 1 Comment Originated: 07/17/2012
07/17/2012: Please correct "bot" with "not" in the note 12 of the site plan.
Department: Light And Power
Contact: Doug Martine, 970.224.6152, dmartine(&fcaov.com
Topic: General
Community Development and
City of
Neighborhood services
Fort Collins
261 North College Avenue
Box 580
Fort
Fort Collins, CO 80622
970.221.6750
970.224.6134 - fax
fcgov. com/developmentreview
July 18, 2012
Cathy Mathis
The Birdsall Group
444 Mountain Ave
Fort Collins, CO 80521
RE: Elizabeth & City Park Corner Redevelopment, FDP120003, Round Number 1
Please see the following summary of comments from City staff and outside reviewing agencies for your
submittal of the above referenced project. If you have questions about any comments, you may contact the
individual commenter or direct your questions through the Project Planner, Courtney Levingston, at
970-416-2283 or clevingston@fcgov.com.
Comment Summary:
Department: Current Planning
Contact: Courtney Levingston, 970.416.2283, clevAcis on fe' ov.com
Topic: Building Elevations
Comment Number: 1 Comment Originated: 07/1712012
07117/2012: Please add a note tonewe building elevations (in two places) indicating the
gas electrical meters will be painted brown to match CMU block veneer.
Comment Number: 2
07/17/2012: Remove "PDP" from the title of Drawing At of 3 (Elevations)
Topic: Lighting Plan
Comment Number: 1
07/17/2012: Please provide final lighting plan.
Department: Engineering Development Review.
Contact: Andrew Gingerich, 970.221.6603, agingerich(rilfcgov.com
Topic: Construction Drawings
Comment Originated: 07117/2012
Comment Originated: 07/17/2012
Comment Number: 2 Comment Originated: 07/17/2012
07/17/2012: Sheet 1 - PDP can be removed from title as it does not need to be a part of the
project title.