HomeMy WebLinkAboutCITY OF FORT COLLINS POLICE SERVICES FACILITY - FDP - 29-05A - CORRESPONDENCE -Another formal round of review is not necessary. Prior to submitting mylars for recording,
please check in with Engineering and Stormwater to address the comments provided in this
letter. Please call if you have any questions.
Sincerely:
Ted Shepard
Chief Planner
Page 3
0
The silt fencing shown on the plan is inside the streets which are also being constructed.
Why? What protects surrounding areas from the street construction?
Your calculations don't seem to include the same BMP's shown on the plan.
Your report should contain a narrative indicating the BMP's to be used and the sequencing
of the BMP's installation during construction.
[1 /11 /06]
The plan sheet needs a legend for BMP's being utilized.
2. The silt fencing shown on the plan is inside the streets which are also being
constructed. Why?
3. How does the southeast detention pond outlet, and is the construction of any pipeline
there protected?
4.• There must be a note on the plan that disturbed areas are to be seeded/mulched (per
your report and calculations).
5. Your calculations don't seem to include the same BMP's shown on the plan.
Topic: Plat
Number: 63 Created: 9/13/2005
[2/14/06] Plat needs to be signed prior to mylars signature for these plans.
[1/5/06] Need to see a copy of the revised plat by Stantec.
[9/13/05] Please modify the plat so that the drainage easement does not extend beyond the
limits of the proposed detention pond.
Topic: Storm Line 2 Alignment
Number: 82 Created: 2/14/2006
[2/14/06] Why is the storm line on the north side of the building located so close to the
building? If possible maintain 10 feet of separation form the building. If this was done to
avoid landscaping conflicts, then it is OK to leave line in current location as long as you note
that line is to be privately owned and maintained.
Topic: Utility Plans
Number: 84 Created: 2/16/2006
[2/16/06] Please label the existing irrigation line per construction Stantec's plans as an
irrigation line rather than a drainage line as shown.
Department: Stormwater-Water-Wastewater Issue Contact: Roger Buffington
Topic: Water/WW
Number: 75 Created: 1 /13/2006
[2/15/06]
[1/13/06] No comments.
Page 2
STAFF PROJECT REVIEW
City of Fort Collins
VIGNETTE STUDIOS Date: 02/23/2006
TERENCE HOAGLUND
144 N MASON ST., SUITE 2
FORT COLLINS, CO 80524
Staff has reviewed your submittal for FORT COLLINS POLICE FACILITY PDP AND FINAL
PLANS - TYPE I, and we offer the following comments:
ISSUES:
Department: Engineering Issue Contact: Dan DeLaughter
Topic: General
Number: 79 Created: 2/14/2006
[2/14/06] 18' Sewer easement shown on the site and landscape plan is not shown on the
utility plans. Please coordinate.
Number: 80 Created: 2/14/2006
[2/14/06] Add dashed linetype to legend on the demo plan- not sure what it is.
Number: 81 Created: 2/14/2006
[2/14/06] We cannot sign the mylars for this project until the plat for Spring Creek Farms
North is filed.
Topic: Landscape Plan
Number: 83 Created: 2/16/2006
[2/16/06] Please box the text where indicated and remove contours.
Department: PFA Issue Contact: Carie Dann
Topic: fire
Number: 76 Created: 2/3/2006
[2/3/06] The atrium shall include an approved smoke -removal system. Plans shall be
submitted to Poudre Fire Authority prior to approval.
Number: 77 Created: 2/3/2006
[2/3/06] Address numerals shall be visible from the street fronting the property, and posted
with minimum six-inch numerals on a contrasting background. (Bronze numerals on brown
brick are not acceptable.) 97UFC901.4.4
Number: 78 Created: 2/3/2006
[2/3/06] The fire lane shall be visible by painting and signage, and maintained unobstructed.
A fire lane plan shall be submitted prior to approval.
Department: Stormwater-Water-Wastewater Issue Contact: Basil Harridan
Topic: Erosion/Sediment Control
Number: 74 Created: 1 /11/2006
(2/13/06]
Second Review
February 13, 2006
Page 1