HomeMy WebLinkAboutWATERGLEN SELF-STORAGE - REPLAT TRACT ''W'' - 71-93D - CORRESPONDENCE -Department: Zoning Issue Contact: Jenny Nuckols
Topic: General
Number: 8 Created: 1 /15/2009
[1/15/09] No Issues
Be sure and return all of your redlined plans when you re -submit.
If you have any questions regarding these issues or any other issues related to this project,
please feel free to call me at (970) 221-6750.
Yours Truly,
Steve Olt
City Planner
Page 2
,
STAFF PROJECT REVIEW �R
City of Fort Collins
JR ENGINEERING Date: 1/28/2009
DAVE ROBERTS
2620 E. PROSPECT RD
FT. COLLINS, CO 80525
Staff has reviewed your submittal for WATERGLEN SELF STORAGE-REPLAT #71-93D,
and we offer the following comments:
ISSUES:
Department: Engineering Issue Contact: Dave Stringer
Topic: General
Number: 3 Created: 12/23/2002
Need to add note regarding existing easements to be vacated and new easements
dedicated with this plat
Department: Light & Power Issue Contact: Doug Martine
Topic: Electric
Number: 1 Created: 12/12/2002
Developer will need to coordinate power requriements and transformer location with Light &
Power Engineering. Normal Electrical Development Charges will apply.
Department: Natural Resources
Topic: General
Number: 7
No Issues
Issue Contact: Doug Moore
Created: 1 /6/2003
Department: PFA Issue Contact: Michael Chavez
Topic: General
Number: 4 Created: 12/30/2002
Required Access: A fire lane is required. The fire lane shall be visible by painting and
signage, and maintained unobstructed. 97 UFC 901.2.2.1;901.3; 901.4.2;902.2.1
Number: 5 Created: 12/30/2002
Address Numerals: Address numerals shall be visible from the street fronting the property,
and posted with a minimum of 8 inch numerals on a contrasting background. ( Bronze
numerals on brown brick are not acceptable). 97 UFC 901.4.4
Number: 6 Created: 12/30/2002
Water Supply: Commercial
No commercial building can be greater then 300 feet from a fire hydrant. Fire hydrants are
required with a maximum spacing of 600 feet along an approved roadway. Each hydrant
must be capable of delivering 1500 gallons of water per minute at a residual pressure of 20
psi. 97 UFC 901.2.2.2
Department: Transportation Planning Issue Contact: Tom Reiff
Topic: General
Number: 2 Created: 12/18/2002
Please identify and label the edge of the right of way for Waterglen Drive on the plat.
Page 1