HomeMy WebLinkAboutCARE HOUSING AT WINDTRAIL PARK APTS., AMEND. P.U.D - P & F - 66-93G - CORRESPONDENCE - (5)28. It is recommend that Buildings K and L be pulled apart to increase their
separation. As shown, there is only 26 feet of separation and there appears to be room to
shift Building K, and its parking lot, slightly to the east.
This concludes Staff comments at this time. Please call before re -submitting for the
proper number of plan sets. As always, please call if you have any questions or concerns
regarding these comments.
Sincerely:
Ted Shepard
Chief Planner
Enc.
18. All plant material must meet minimum sizes. Please upgrade the deciduous shade
trees to 2 inches minimum caliper, ornamentals to 1.5 inches minimum caliper,
and shrubs to five gallon minimum size.
19. On the Landscape Plan, please modify note number 11 to include "labor" in the
amount of the financial instrument necessary to escrow the installation for the
purpose of obtaining Certificates of Occupancy. Also, at the time of recording, it
is a good idea to provide a Phasing Plan for the landscaping so that C.O.'s can be
granted without bonding for the entire P.U.D.
20. Please add a detail on the fence. This should include height, materials, and other
features.
21. The Site Plan should include a legend. It would be helpful to use B for bike rack,
R for sidewalk ramps, T, for trash enclosure, and reference the symbol used to
indicated entry arbor.
22. Please contact Light and Power as early as possible for likely locations of the
electrical transformer(s). These should be shown on the plans and referenced in
the legend with an "E." Transformers must be within 10 feet of hard surface for
emergency change -out. They should not be within the enclosed areas and should
be screened with plant material or fenced.
23. I am assuming that the "fronts" of Buildings A,B,C,D,E,F,G,H and J all face the
internal fenced play areas and that the rear of the buildings face the parking lots.
Perhaps there is a clear and easy way of graphically depicting the front and back
sides of the dwelling units.
24. The architectural sheets cal for 30-year high profile shingle. It would be helpful
to also specify the roof by the pounds per square. Would these shingles be in the
300 to 350 pounds per square range? Please specify.
25. It is suggested that the community building feature a more predominant porch,
with no dimension less than six feet, to carry forward the theme of attractive,
quality common areas that are so well demonstrated throughout the project.
26. Has any thought been given to color of the lap siding? Will there be one color or
a variety? Will the color be distinctive or match the color of the Windtrail
Condos or Sundering Townhomes?
27. Please label the Site, Landscape and Architectural plans sequentially so that the
Site Plan is sheet 1 of 6, 2 of 6, etc.
7. The Water and Wastewater requests that all water and sewer mains and service
lines be shown on the Landscape Plan. See also redline plans and the comment
sheet.
8. The Light and Power Department is concerned about proper separation of utilities
and requests a utility coordination meeting at the appropriate time. This will
include making sure that street trees are kept a minimum of 40 feet from a public
street light and ornamentals kept a minimum of 15 feet from street lights.
9. The neck -down on Rolland Moore should be specified to feature an "enhanced
crosswalk."
10. The Street Oversizing Program will participate in the construction of Rolland
Moore Drive. Reimbursement will be from the local street to collector street
standard.
11. The vacation of old Bridgefield Drive will require two readings by City Council.
Please provide necessary documentation to the Engineering Department.
12. Poudre Fire Authority cautions that Buildings G, C and N are out of access and
must be equipped with an automatic fire extinguishing system. Also, the fire lane
must feature a red curb and posted with signs stating "No Parking — Fire Lane."
13. Poudre Fire Authority also requests that each individual building shall have its
own distinct street address. One address for the complex will not be acceptable.
14. PFA will require additional fire hydrants throughout the complex.
15. There is a discrepancy between the Site Plan and Plat regarding the distances of
the building envelopes to the reference points. For example, the distance from
Building J to Rolland Moore Drive right-of-way on the plat is 17.71 feet while the
Site Plan shows 22.3 feet. Please resolve this and other discrepancies.
16. The trash enclosures must be designed to accommodate bins and containers for all
the recyclable materials that are picked up the local -trash haulers. Please refer to
the attached sketch for ideas. Also, please provide a detail of the enclosure and
indicate that the enclosure will use the predominant building material as on the
units.
17. TCI of Fort Collins will need a broadband utility easement, also called a service
agreement, before any plans to service this project. This may be obtained from
our Commercial Accounts Executive. The sooner this is obtained, the greater the
chance of sharing a joint trench with another utility. Please contact Reneta
Santro, 493-7400.
., A
Coma ity Planning and Environmenta- �rvices
Current Planning
City of Fort Collins
December 18, 1998
Mr. Brad Saucerman
Jim Sell Design
153 West Mountain Avenue
Fort Collins, CO 80524
Dear Brad:
Staff has reviewed the request for Windtrail Townhomes, Amended Preliminary and
Final P.U.D. and offers the following comments:
The Engineering Department is asking that six parking spaces on the south side
and four parking spaces on the north side of Rolland Moore Drive be eliminated
due to being less than 50 feet setback from the flowline (see redlines). Similarly,
there are five spaces that less than 40 feet from the flowline of Bridgefield and,
therefore, are to be eliminated. This will impact the parking statistics and the
Landscape Plan.
2. Please refer to other Engineering comments on the redlines and the comment
sheets.
3. The P.U.D. Site Plan should include a note addressing the Shire Court closure at
Shields Street. Has it been determined who will close this intersection? What is
the timeframe for closure? If this obligation falls to Care Housing, then these
details will need to be documented in the Development Agreement. If the closure
falls to another party, please reference this in the note.
4. Please refer to the Engineering and Transportation Planning comments regarding
the new street standards. The plans should reflect the proper right-of-way,
pavement width, parking lanes, bike lanes, parkway, etc. to reflect the new
standards.
5. The external sidewalk on Bridgefield should continue north to Shire Court.
6. Please refer to the redlines and comment sheet from Stormwater.