HomeMy WebLinkAboutCARIBOU APARTMENTS (RESUBMITTED) - FDP - 18-02D - CORRESPONDENCE - (5)a
Department: Stormwater-Water-Wastewater Issue
Contact: Roger Buffington
Topic: Water/WW
Number: 19 Created: 7 / 5 / 2006
[1/2/07] Please provide more detail so an accurate determination of service
size can be checked.
[7/5/06] Provide water service sizing calculations for the 32 and 44 unit
buildings.
Number: 51 Created: 1 / 2 / 2007
[1/2/07] Revise sanitary sewer between ex. MH and MH 2 as shown on
plans. (The elevation of the 8-inch sewer is well above the invert of the 27-
inch sewer; therefore, the very slight amount less than the 90-degree
connection is not significant.)
At staff review on January 3, 2007, David Averill of the Transportation
Planning Department stated that a "temporary" off -site asphalt trail
(sidewalk) is needed from this property to the south along the west side of
Timberline Road.
City staff is ready to accept mylars of the development plans to move
to recording of the plans. Be sure and return all red -lined plans if/when
you re -submit.
If you have any questions regarding these issues or any other issues related
to this project, please feel free to call me at (970)221-6341.
Yours Truly,
Steve Olt
City Planner
cc: Randy Maizland
Roger Buffington
Marc Hendricks
Current Planning file # 18-02D
Page 3
•
Department: PFA Issue Contact: Carie Dann
Topic: Fire
Number: 35 Created: 7 / 6 / 2006
[1/3/07]
[7/6/06] KNOX BOX: A Knox Box is required to be mounted at the main
entrance of any building equipped with an automatic fire sprinkler system.
Number: 38 Created: 7 / 6 / 2006
[ 1 / 3 / 07] Thank you for specifying 10-inch building numerals and 6-inch
individual unit numerals. Because the private streets are going to be
named, each building should be given a separate, individual numeric
address and street name. Also regarding addressing, something we've begun
doing with multi -building complexes addressed off multiple streets, is put
the building address numerals AND street name on the front of the building.
So for example, the front of Building 3 would show 3601 VERDENA WAY.
[7/6/06] ADDRESSING: Address numerals shall be posted on each
building, with numerals a minimum 6 inches high. Building numbers and
unit numbers shall be approved by PFA in advance. Contact Carie Dann for
specific information.
Topic: Landscape
Number: 54 Created: 1 / 3/ 2007
[ 1 / 3/ 07] HAZARDOUS MATERIALS: Pertaining to the clubhouse/ swimming
pool, any toxic, corrosive, or reactive materials, or flammable/combustible
liquids (as defined in the Uniform Fire Code) if used, stored, or handled on
site, must have a Hazardous Materials Impact Analysis (HMIA) completed
and supplied to the Planning Department and the Fire Department.
Department: Transportation Planning Issue Contact: David Averill
Topic: General
Number: 52 Created: 1 / 2 / 2007
[ 1 / 2 / 07] No comments or concerns.
Department: Stormwater-Water-Wastewater Issue
Contact: Roger Buffington
Topic: Landscape
Number: 53 Created: 1 / 2 / 2007
[1/2/071 Adjust tree to meet minimum separation from Building 3 sanitary
sewer service.
Department: Stormwater-Water-Wastewater Issue
Contact: Wes Lamarque
Topic: Stormwater
Number: 32 Created: 7/ 6/ 2006
[ 1 / 5/ 07] No Comments.
[7/6/06] No Comments.
Page 2
w
STAFF PROJECT REVIEW
City of Fort Collins
VF Ripley Associates Date: 01 / 31 / 2007
c/o Cathy Mathis for Marc Hendricks
401 West Mountain Avenue, Suite 201
Fort Collins, CO. 80521
Staff has reviewed your submittal for CARIBOU APARTMENTS
(RESUBMITTED), FINAL PLANS, and we offer the following comments:
ISSUES:
Department: Current Planning Issue Contact: Dana Leavitt
Topic: Landscape
Number: 55 Created: 1 / 3 / 2007
[1/3/07] No issues.
Department: Engineering Issue Contact: Randy Maizland
Topic: Engineering
Number: 56 Created: 1 / 3 / 2007
[1/3/07] Please provide a City signature approval block on sheet 8A in the
lower right hand corner.
Number: 57 Created: 1 / 3 / 2007
[1/3/07] Refer to sheet 13 of the Utility Plans. The 90 degree elbow
intersection shall meet the design requirements of LCUASS 7-24. Minimum
distance between PC and PRC is 45 feet. Please check design requirements
and revise if necessary. Remove the access easement label from the typical
private street cross section.
Number: 58 Created: 1 / 3 / 2007
[1/3/07] Please add a typical detail for interim asphalt sidewalk
construction to sheet 25. Asphalt should be at least 3 inches rolled and
compacted with proper drainage.
Number: 59 Created: 1 / 3 / 2007
[1/3/07] Utility Plans are basically ready for mylars. Submit revised mylar
originals, with red -lines, for final check and routing for signatures.
Topic: General
Number: 44 Created: 7 / 6 / 2006
[1/3/07] No Development Agreement Info sheet has been provided. Per the
staff meeting request, a DA info sheet will be emailed to Tricia with North
Star.
Page 1