HomeMy WebLinkAboutMASON ST. NORTH, MAJOR AMEND. - FDP - 4-97C - CORRESPONDENCE - (18)ATTACHMENT TO REVISION COMMENT SHEET
PROJECT: #4-97C MASON STREET NORTH
MAJOR AMENDMENT - TYPE I (L UC)
TO: STEVE OLT FROM: CRAIG FOREMAN
THE FOLLOWING ITEMS TO BE NOTED ON PLANS
• NEW SWALE GRADING TO BE COORDINATED WITH PARKS
MAINTENANCE STAFF.
• DEVELOPMENT WORK SHALL INCLUDE RESTORING DISTURBED
AREAS IN PARK TO THE SATISFACTION OF PARKS STAFF
INCLUDING SPRINKLER SYSTEM, EARTHWORK, SOIL
PREPARATION AND APPROVED SOD.
• INCLUDE THE "ORIGINAL GRASS MOWING LINE" IN LEGEND.
• RIP RAP AT THE 48" RCP NEEDS TO BE BURIED
GENERAL COMMENTS
• VERIFY WATER QUALITY POND IS AT APPROPRIATE CAPACITY
FOR THIS DEVELOPMENT'S USE ONLY, AND IS NOT IN EXCESS OF
REQUIRED CAPACITY.
• WHO IS TO TAKE OVER LONG TERM MAINTENANCE OF THE
EXPANDED WATER QUALITY POND?
REVISION
COMMENT SHEET
DATE: June 14, 2004 TO: Craig Foreman -Park Ping.
PROJECT: #4-97C Mason Street North Major Amendment
— Type I (LUC)
All comments must be received by Steve Olt no later than the staff
review meeting:
June 23, 2004
No Comment
RECE,VED
JUN 2 2 p0g4
CURRENT PLANN/NG
Problems or Concerns (see b=inw 06ttached)
**PLEASE IDENTIFY YOUR REDLINES FOR FUTURE
REFERENCE**
ry� rnw
Name (please print)
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
X_Plat x site _Drainage Report _Other
C Utility Redline Utility _Landscape
d '(
E n 333
;3
` 3 A
JQ
I
E
i
I
DATE: 6.14.04 DEPT: TECHNICAL SERVICES
PROJECT: Mason Street North
PLANNER: Steve Olt
ENGINEER: Katie Moore
All comments must be received by: 6.23.04 �pj\
❑ No Problems /
❑ Problems or Concerns (see below or attached)
Comments:
/. ,Pozi.✓f%"1e:5 # 6e45E
2. Q H6 61vg rt raj- dF 7-H(F Rc,A-i A./aeos 7b 5/461w 71-14
THC" / /?A,T /r 130c-0 4C6, vc, Y!%r /`J02r14 /Odr GF
%lam C'X/ST//v( /L/ZT/AJ("2 P �J. /S A Id,9-itr aF
79tUc,& 3V OF
30
Date: June 16, 2004 Signature:
PLEASE SEND COPIES OF MARKED REVISIONS
0 Plat 0 Site 0 Utility 0 Landscape 0 Drainage Report 0 NO COMMENTS -SUBMIT MYLARS
M
plans. Provide 10 feet of utility easement on both sides of
the proposed water main in the railroad crossing location.
See site, landscape and utility plans for other comments.
Topic: Landscape Plan
Number: 18 Created: 9/4/2001
[6/25/041
[4/27/041 Repeat comment
Previous Comment: Show all water and sewer lines on the
landscape plans and provide the required landscape/utility
separation distances.
Be sure and return all of the red -lined plans when you re-
submit.
If you have any questions regarding these issues or any other
issues related to this project, please feel free to call me at
(970)221-6341.
Yours Truly,
Steve Olt
City Planner
cc: Katie Moore
Shear Engineering
Current Planning file #4-97C
Page 6
r
Department: Stormwater Utility Issue Contact: Wes
Lamarque
Topic: Drainage
Number: 184 Created: 4/30/2004
[6/23/041. Please add a note on sheet 15 that the existing
storm sewer that is to be put back in service needs to be
inspected along with the new proposed storm sewer.
The previously abandoned 48-inch storm sewer will need to be
certified as if it were a new storm drain. This will be done
with the rest of the drainage certification for the site. An
inspection of the pipe before plan approval is recommended to
be sure that the pipe is still in good condition. City camera
crews may be able to assist you in accomplishing this.
Number: 185 Created: 4/30/2004
[6/23/041 Repeat Comment
The drainage report needs to reference the current Old Town
Drainage Master Plan. Any updates within the new master plan
need to be incorporated into the current design for the site.
Number: 209 Created: 6/24/2004
[6/24/041 See other minor comments on the redlined plans.
Department: Water Wastewater Issue Contact: Jeff Hill
Topic: General
Number: 210 Created: 6/25/2004
[6/25/041 As previously indicated, the proposed irrigation
tap locations must be shown and labeled on the overall utility
plans. They may not be.coordinated with the landscaper in the
future.
Number: 211 Created: 6/25/2004
[6/25/041 As previously indicated, the sanitary sewer manhole
located on the southwest corner of this project must be
adjusted lower by removing an existing barrel section and
replacing that with a NEW barrel section.
Number: 212 Created: 6/25/2004
[6/25/041 As previously indicated, the 6-inch water main that
extends to the north between Buildings C and B must be
restrained. Clearly define the restraining information on
these plans.
Number: 213 Created: 6/25/2004
[6/25/041 Coordinate the utility easement location shown on
the plat for building B's water services with the utility
Page 5
A fire lane is required. The fire lane shall be visible by
painting and signage, and maintained unobstructed. 1997 UFC
901.2.2.1; 901.3; 901.4.2; 902.2.1; FCLUC
Buildings three stories or more in height must have access to
a 30 foot unobstructed access roadway on at least (1) one side
for aerial operations. PFA Policy 85-5 (B)
Number: 194 Created: 5/5/2004
[6/25/041
[5/5/04] PREMISES IDENTIFICATION: Approved numerals or
addresses shall be provided for all new and existing building
in such a position as to be plainly visible and legible from
the street or road fronting the property. 1997 UFC 901.4.4
A. In Multi -story buildings the following requirements shall
pertain.
1. The first floor units shall be designated with 100's.
2. The second floor units with 200's
3. The third floor units with 300's, and so forth.
B. All brass letters and numerals shall be posted on a black
background. _
C. Some multi -family layouts may require address postings from
the back side as well as the front of the buildings.
D. A counter clockwise addressing pattern shall be maintained
when ever possible.
E. An addressing scheme shall be submitted to the fire
department for approval prior to being posted on the building.
Number: 195 Created: 5/5/2004
[6/25/041
[5/5/04] WATER SUPPLY: Commercial
No commercial.building can be greater then 300 feet from a
fire hydrant.
Fire hydrants are required with a maximum spacing of 600 feet
along an approved roadway. Each hydrant must be capable of
delivering 1500 gallons of water per minute at a residual
pressure of 20 psi. 1997 UFC 901.2.2.2
Number: 196 Created: 5/5/2004
[6/25/041
[5/5/04] BUILDING AREA:
This proposed building exceeds 5000 square feet for type V
construction and must be fire contained or fire sprinklered.
1997 UBC Table 9B
Page 4
Number: 201 Created: 6/22/2004
[6/22/041 Due to the shifting water main in the proposed
utility easement crossing the RR tracks, that easement will
need to be widened to a minimum of 10' each side of the main.
Number: 208 Created: 6/23/2004
[6/23/041
Comment from Technical Services:
The subtitle of the plat needs to show that the tract added
along the north side of the existing Martinez PUD is a part of
Block 34 of the Original City Plat.
Topic: Sheet 3
Number: 135 Created: 11/23/2001
[6/22/041 More information is still needed regarding striping
on Cherry for the length of the block.
[4/26/041 The north bike lane stripe is missing, and more
information regarding striping should be shown to address the
addition of the median and changes to the left turn lane west
of the median.
Original comment:
Please show striping on Cherry Street. (repeat)
Topic: Utility plans
Number: 202 Created: 6/22/2004
[6/22/041 The storm water box shown extending past the Mason
St. N. property line to the west of the project is shown on RR
property. Please either bring this box to a location within
Mason St. N. property or obtain an easement from the RR.
Number: 205 Created: 6/22/2004
[6/22/041,
It appears that ADA grades for the sidewalks crossing the
driveway onto Cherry and the sidewalk aligning with the ped
island are not being met. The maximum cross -slopes on these
sidewalks (north -south) are 1:24 and 1:25, respectively, and
these slopes are currently shown at as much as 12%. Please
revise to match the standard drawings.
Department: PFA
Chavez
Topic: Traffic
Number: 193
[6/25/041
[5/5/04] REQUIRED ACCESS:
Issue Contact: Michael
Created: 5/5/2004
Page 3
Number: 203 Created: 6/22/2004
(6/22/041 General reminder: building footings are not
allowed within easements. Buildings will have to be
constructed exactly where they are shown.
Number: 206 Created: 6/22/2004
[6/22/041 Please see plans for any additional comments.
Number: 207 Created: 6/23/2004
[6/23/04] A completed Development Agreement information sheet
has yet to be received by the City.
Topic: Landscape Plan
Number: 37 Created: 9/4/2001
[6/22/04] Repeat: In particular, the parking lot/back up
area west of the garages south of the RR tracks doesn't match
from the site/landscape plans to the utility plans. Please
coordinate.
[4/26/041 Repeat: Please match with other plans/plat.
Topic: Median
Number: 204 Created: 6/22/2004
[6/22/041 The radii and arc lengths shown for the small
curves on the median curb and gutter do not pass the straight -
face test for the curve requirements. A 1.6" long curve?
Please use min. 100' radii on these curves.
Topic: Plat
Number: 171 Created: 4/26/2004
[6/22/041 I've just heard that the maintenance of Tract A is
still under negotiation. Please come to a final answer on
this topic so that it is known if anything needs to be added
to the plans or DA regarding the maintenance of Tract A.
[4/26/043 Additional language is needed regarding Tract A's
maintenance and ownership. I thought this had been worked out
years ago, but cannot find a copy of what had been agreed
upon. Please contact Parks/Real Estate/City Attorney (Carrie
Daggett) regarding this topic.
Number: 198 Created: 6/22/2004
[6/22/041
All existing easements should be labeled with their reception
number or book and page information, and the new triangle of
land added to the plat should have a note indicating its
reception number as well.
Page 2
i'
STAFF PROJECT REVIEW
City of Fort Collins
Wolff -Lyon Architects Date: 06/28/2004
777 Pearl Street, Suite 210
Boulder, CO. 80302
Staff has reviewed your submittal for MASON STREET NORTH
(MAJOR AMENDMENT TO MARTINEZ PUD), FINAL PLAN, and we offer
the following comments:
ISSUES:
Department: Engineering Issue Contact: Katie Moore
Topic: General
Number: 56 Created: 9/5/2001
[6/22/041 Repeat:
[4/26/04] There are still existing items being shown with
dark line weights, making them look to be proposed instead of
existing (i.e., the sidewalk on Cherry Street). Please
revise.
Original comment:
Please use phantom lines for existing features/buildings
adjacent to site.
Number: 74 Created: 9/5/2001
[6/22/04] Repeat:
[4/26/041 Please provide copies of completed RR agreements to
the City prior to Mylars.
Original comment:
Any work done within the RR ROW/easement requires approval by
the railroad. Please provide a letter of intent from the
Railroad regarding these improvements (grading, landscaping,
pedestrian crossing, etc.).
Number: 197 Created: 6/22/2004
(6/22/04] The plat is the only plan that clearly shows the
property boundaries for this project, but the property
boundaries for the project should be clearly shown on all
plans. Please revise.
Number: 200 Created: 6/22/2004
[6/22/04] Regarding the sight distance easements: only the
easements need to be shown on the plans. The remaining
lengths of line should be deleted.
Page ]