HomeMy WebLinkAboutRIGDEN FARM, 12TH FILING - PDP - 56-98AN - CORRESPONDENCE - (11)Steve Olt -Brooklyn Pa rkRowhouses,Phase2, Prelim inaryDesignReview-082306.Comm entLetter2.doc Page 9
"final" decisions provided by City staff at the Preliminary Design Review meeting on
August 23Td. I will be coordinating a meeting with you, your clients, and City
staff (Engineering, Stormwater, Water/Wastewater, Poudre Fire Authority, and
Transportation Planning) to further discuss issues associated with this
proposed development and provide further direction before you invest
additional time and expense to prepare Project Development Plans for
submittal to the City.
If you have any questions regarding these issues or any other issues related to
this project, please feel free to call me at 221-6341.
Yours Truly,
Steve Olt
City Planner
cc: Cameron Gloss
Susan Joy
Glen Schlueter
Roger Buffmgton
David Averill
Carie Dann
Ron Gonzales
Hearne Construction/Scott Hearne
Current Planning File
Page 9
Steve Olt - Brooklyn Park Rowhouses,Phase2, Pre[ iminaryDesignReview-082306.Comm entLetter2.doc Page 8
[8/27/06] Provide a fire hydrant connecting to the existing 8-inch water stub
off Kansas. It appears that there is space for a hydrant to the north or south of
the drive. The arrangement of curb stops and meter pits for the three services
connecting to this line makes maintenance/replacement of the services
difficult. We would like to work with you on revising this during utility plan
review.
Number: 24 Created: 8/ 27 / 2006
[8/27/06] Provide sizing calculations for the water services. The larger
buildings may need 2-inch services. (Plant investment fees and water rights for
residential are based on number of units and lot area NOT size of service.)
Number: 25 Created: 8 / 27 / 2006
[8/27/06] Are any irrigation taps planned?
Number: 26 Created: 8 / 27 / 2006
[8/27/06] City Code (Section 26-94 and 26-256) requires that each building
has separate water/sewer services. On the revise plan sheet that was received
on 8/25/06, it appears that units 48-51 are separate from units 52-62 and will
need separate services. In addition, the sewer service for units 16-24 must be
a separate service line to the MH east of Iowa.
Department: Zoning Issue Contact: Peter Barnes
Topic: Zoning
Number: 9 Created: 8 / 23 / 2006
[8/23/061 The property is located in the MMN zone and is subject to a Type 1
review. The number of off-street parking spaces required is based on the
number of bedrooms per unit. 1.5 spaces for every 1 bedroom unit, 1.75
spaces for every 2 bedroom unit, and 2 spaces for every 3 bedroom unit.
The following comment was received from Ron Gonzales of the Poudre Fire
Authority on August 28, 2006:
"I recently had a brief meeting with the Hearne Brothers regarding a fire
dept. access issue. We were successful resolving the issue so that we're
able to gain access from two directions for dwelling units facing the
interior court.
They were going to speak with you (Steve Olt, Current Planning) and
perhaps R. Buffington (Water/Wastewater) to check how this safety
measure might impact the balance of the project."
There has been concern expressed about the apparent lack of information or
Page 8
Steve Olt 'Brooklyn Park Rowhouses,Phase2,PreliminaryDesignReview-082306.Comm entLetter2.doc Page 7
be the back wall of the guest parking area since the pipe runs through
there anyway. The stairs may have to be on one side or the other to make
the inlet easier to build. (Referring to the updated site plan with pipe
in center of 12 ft. guest parking area)
Another suggestion is to build in some redundancy by adding
additional area inlets in the private drive. The only down side to
that is additional grates could also plug easier than an open throat
inlet.
2. Another concern is running the pipe through the wall which is essentially
part of the foundation wall of the building.
A suggestion is to sleeve the pipe which would have to be a water
tight pipe like ductile iron or PVC water pipe since it is so close to
the building foundations. Just for future maintenance the sleeve
should run from driveway to driveway and completely under the
building.
In addition to the maintenance concern is the possibility of a beam
break as the pipe goes through the wall. Maybe with the open
throat inlet there would be a box that could serve as protection of
the pipe as it went through the wall.
Number: 30 Created: 8 / 29 / 2006
[8/29/061 Rigden Farm Overall Drainage Plan basin delineation: At the PDR
there was discussion on the drainage sub -basins that were given to the
applicant when the property was purchased. The original Filing One report
shows a basin 582 that has a basin line on the south side of pond 212. In the
latest update for Filing Six some basins were combined differently but on this
site the basin line for basin 58 still has a line on the south side of pond 212.
In fact it shows a future street on the south side of pond 212, most of which is
to drain into the pond. So for this particular site pond 212 is designed to take
a small portion of it at the high imperviousness of a street. As far as what the
applicant was given by the seller I do not know the source of that information.
Other than that I can only speculate that the information may have been
misinterpreted. I will make a "pdf' file showing the basins from both reports
and send them electronically to the applicant's engineer. If there is a basin
transfer of drainage the modeling will be required to document system capacity
or needed revisions.
Department: Water -Wastewater
Topic: Water/Wastewater
Number: 23
Page 7
Issue Contact: Roger Buffington
Created: 8 / 27 / 2006
Steve Olt-' Brooklyn ParkRowhouses,Phase2,PreliminaryDesignReview-082306.Comm entLetter2.doc Page 6
existing pond one will be needed as part of the final plan approval if there isn't already
one. The maintenance of the channel is the responsibility of the property owner unless
there are other agreements with the Rigden Farm developer.
Number: 4 Created: 8 / 22 / 2006
[8/22/06] The applicant asked if units 16 - 18 can drain to the streets in front
of the unit. It appears that is the intent of the overall design so that is fine.
Number: 28 Created: 8/28/2006
[8/28/06] During the PDR the applicant asked for documentation on why the
garages cannot be flooded. Sec. 26-492 "Declaration of Purpose" of the City
code includes protection of property. Sec. 26-541 "Property Owners to provide
stormwater facilities" and Sec. 26-544 "Stormwater facilities required for
subdivisions" also speak to the issue. In addition the Storm Drainage Design
Criteria and Construction Standards give more detailed design information
such as the clogging factors.
Number: 29 Created: 8 / 28 / 2006
[8/28/06] Emergency overflow for the sump inlet in the private: The following
are a couple concerns and suggestions to address each one:
The primary concern is to have an outfall in addition to the area inlet to
divert the flow and prevent it from entering any buildings if the inlet is
plugged. It is not the possible plugging of the pipe that is the main
concern. It is mainly plugging of the area inlet. If this can be addressed
the concept shown on the site plan could be approved.
- I think the first thing that needs to be considered is what is the
volume of runoff draining to the inlet if it were plugged from the
beginning of a 100 year storm? It may be possible to grade the
private drive such that the water will pond only in the drive
especially if the contributing area can be minimized.
In conjunction with that a way to minimize the drainage area
contributing to the sump inlets is to possibly drain the center of
the project (Units 38-64) to Kansas Dr. Or if need be have a
separate pipe along Kansas to drain the center of the project.
A possible way to address plugging of the grate on the sump inlet
would be to have a second inlet into the pipe that has more of a
vertical open throat like a type R inlet so it isn't as likely to get
plugged by debris like a grate. A possible location for this would
Page 6
Steve Olt-' Brooklyn ParkRowhouses,Phase2, Prelim inaryDesignReview-082306.CommentLetter2.doc Page 5
the fire lane.
If a fire lane cannot be provided, the buildings shall be fire sprinklered.
Number: 7 Created: 8 / 23 / 2006
[8/23/06] ADDRESSING: Address numerals shall be visible from the street
fronting the property, and posted with a minimum of six-inch (6) numerals on
a contrasting background. (Bronze numerals on brown brick are not
acceptable.) For this project, PFA also requires the address to be mounted at
the rear (garage side) of each individual unit. Addressing shall be consistent
with the system for Brooklyn Park - Phase 1.
Number: 8 Created: 8/23/2006
[8/23/061 TURNING RADII: Minimum inside turning radius is 25 feet,
minimum outside turning radius is 50 feet.
Number: 22
[8/25/06).
Created: 8/25/2006
Topic: Zoning
Number: 10 Created: 8 / 23 / 2006
[8/23/06] MONUMENT SIGN: A monument sign shall be erected at the drive
cuts on Kansas Drive, displaying the units addressed off Kansas.
Department: Stormwater Issue Contact: Glen Schlueter
Topic: Stormwater
Number: 1 Created: 8 / 22 / 2006
[8/22/06] This site is in the Foothills drainage basin. The city wide new
development fee is $3,070.00/acre which it is subject to the runoff coefficient
reduction. This fee is to be paid at the time the building permit is issued.
Number: 2 Created: 8/ 22 / 2006
[8/22/06]A drainage and erosion control report and construction plans are
required and they must be prepared by a Professional Engineer registered in
Colorado. The design engineer will need to verify that the imperviousness is
the same or less than the imperviousness used in the overall drainage report
for Rigden Farm. The report indicates 90% imperviousness. The pond along
the north side of the site is to have a volume of 0.8 ac-ft. in case there is any
grading in the pond area. Water quality treatment was included in the overall
drainage plan.
Number: 3 Created: 8/ 22 / 2006
[8/22/06) If the pond to the north is partially on this site an easement for the
Page 5
Steve Olt - Brooklyn Park Rowhouses,Phase2, Prelim inaryDesignReview-082306.CommentLetter2.doc Page 4
Comment 14.
Number: 19 Created: 8/25/2006
[8/25/061 A utility coordination is suggested prior to first submittal. Please
contact me so that I can set one up for you when you're ready with the new
layout.
Number: 20 Created: 8/25/2006
(8/25/06] Grading must be flat to nearly flat for a minimum of 2' behind the
sidewalk. All grading affecting public row can not exceed 4:1 slopes.
Number: 21 Created: 8/25/2006
[8/25/06] Please see LCUASS and Appendix E4 for other submittal
requirements. I can email the checklist to you to make it easier if you like. We
have the items required prior to hearing highlighted so you know what must be
shown on the plans with the first submittal. The check list must be completed
and submitted with the first round of review as well. Email me at
sjoy@fcgov.com and I'll send it back.
Department: PFA Issue Contact: Carte Dann
Topic: FIRE
Number: 5 Created: 8 / 23 / 2006
[8/23/06] WATER SUPPLY: Fire hydrants, where required, must be the type
approved by the water district having jurisdiction and the Fire Department.
Hydrant spacing and water flow must meet minimum requirements based on
type of occupancy. Spacing and flow requirements include 1,500 gpm at 20 psi
residual pressure, spaced not further than 300 feet to the building, on 600-foot
centers thereafter.
Number: 6 Created: 8 / 23 / 2006
[8/23/06] ACCESS: A fire lane is required. This fire lane shall be visible by
painting and signage, and maintained unobstructed at all times. A fire lane
plan shall be submitted for approval prior to installation. In addition to the
design criteria already contained in relevant standards and policies, any new
fire lane must meet the following general requirements:
0 Be designed as a flat, hard, all-weather driving surface (asphalt or
concrete) capable of supporting fire apparatus weights. Compacted road
base shall be used only for temporary fire lanes or at construction sites.
0 Have appropriate maintenance agreements that are legally binding and
enforceable.
0 Be designated on the plat as an Emergency Access Easement.
0 Maintain the required minimum width of 30 feet throughout the length of
Page 4
Steve Olt -'Brooklyn Park Rowhouses,Phase2, Prelim inaryDesignReview-082306.CommentLetter2.doc Page 3
[8/25/06] Diagonal Parking off Kansas: This will not be permitted and no
variance will be granted. Please design the street section in accordance with 7-
9F.
Number: 13 Created: 8 / 25 / 2006
[8/25/06] Skewed Driveway off Kansas: A 75 degree skew has been proposed
and does not meet our minimum requirement of 90 degrees, plus or minus 10
degrees for a minimum of 25'. A variance request will not be considered to this
standard as it appears the site will easily accommodate that requirement. In
other words, there are no site constraints that would prevent a safer, straighter
driveway from being constructed to standard for the first 25'.
Number: 14 Created: 8 / 25 / 2006
[8/25/061 Attached Sidewalks: A variance will not be granted as there are no
site constraints preventing this project from designing the typical street section
to standard. Please design all street frontage in accordance with 7-9F and 7-
5F. Please keep in mind as you are adjusting your layout that no structures of
any kind, including stairs, retaining walls (versi-lock or other), footings and
foundations, are allowed within the utility easement. See Figure 16-1 for other
requirements regarding minimum setbacks for other objects and materials.
Number: 15 Created: 8 / 25 / 2006
[8/25/06] Please design driveways in accordance with 706 or if the TIS shows
more than 350 trips a day, then design the driveway in accordance with 707
per 9.3.2.A. Since the driveways will become part of emergency access drive,
PFA may require 25' curb returns to meet their minimum inside turning radii
requirements instead of our 20' requirement'. PFA's safety minimums would
take precedence. The maximum grade from the row (back of walk) is 8% for a
minimum of 20' per 9.3.3.B.
Number: 16 Created: 8 / 25 / 2006
(8/25/061 Until existing conditions (including unbuilt approved driveway
locations) are shown for a minimum of 150' from the property boundaries, the
driveway locations cannot be approved. Proposed driveways must line up with
those proposed across the street.
Number: 17 Created: 8 / 25/ 2006
[8/25/061 See Figure 19-6 for parking setback requirements. The traffic
volumes discussed in the TIS will be necessary to use the table and determine
the required setback to the first garage door from the street. It will probably be
either 40' or 50'
Number: 18 Created: 8 / 25 / 2006
[8/25/06] No structures of any kind are allowed within easements. See
Page 3
Steve Olt - BrooklynParkRowhouses,Phase2,PreliminaryDesignReview-082306.CommentLetter2.doc Page 2
beginning on Page 5.
Transportation Planning
a. Transportation Planning will not support the proposed attached
sidewalks on Iowa and Kansas Drives. Should these sidewalks be allowed
to be attached then the sidewalks must be a minimum of 6.5' wide.
b. If the proposed diagonal parking on Kansas Drive is allowed then the
sidewalk in front of those spaces must be a minimum of 6' wide.
Poudre Fire Authority (PFA)
a. PFA needs exterior accesses (man doors) to the living areas from the
garage sides of the buildings. These doors need to be separate from the
garage doors.
Planning
a. With the layout as proposed at Preliminary Design Review, the sidewalks
along the north side of the property and the interior courtyard between
buildings must be designed and constructed to satisfy the "major
walkway spine" definition and requirements as set forth in the Land Use
Code.
b. All buildings must be set back from the surrounding street rights -of -way
a minimum of 15'.
C. This property, being in the MMN - Medium Density Mixed -Use
Neighborhood Zoning District, must maintain a minimum average
density of 12 dwelling units per net acre of residential land. There is no
maximum allowable residential density in this district. The proposed 64
dwelling units on the 2.6 acres results in a density of 24.6 dwelling units
per acre.
Department: Engineering Issue Contact: Susan Joy
Topic: General
Number: 11 Created: 8/25/2006
[8/25/06] The first driveway off Kansas is much too close to Custer and
presents a safety issue. Our minimum driveway setback is 175' from CL to CL
and it appears that you have provided for only 100'. No variance will be
granted due to safety and traffic concerns.
Number: 12
Page 2
Created: 8/ 25 / 2006
t,Steve Olt - BrooklynParkRowhouses,Phase2, Prelim inaryDesignReview-082306.CommentLetter2.doc Page 1
�� STAFF PROJECT REVIEW
City of Fort Collins
MTA Date: 08 / 29 / 2006
c/o Troy Jones
204 Walnut Street, Suite D
Fort Collins, CO 80524
Staff has reviewed your submittal for BROOKLYN PARK ROWHOUSES,
PHASE 2 - PRELIMINARY DESIGN REVIEW, and we offer the following
comments:
ISSUES:
Department: Current Planning Issue Contact: Steve Olt
Topic: General
Number: 27 Created: 8 / 28 / 2006
[8/28/06] The following comments were expressed at staff review on
August 23, 2006:
Engineering
a. Regarding the proposed sidewalk along the north side of the property,
adjacent to the existing detention pond, there must be a minimum 2'
wide flat area from the north edge of the walk to the top of the pond
slope.
b. The private driveways to this facility from Kansas Drive must maintain a
minimum 12' separation, edge to edge.
Water/ Wastewater
a. There are existing utilities all around this site.
b. The more services to this site the more utility coordination issues there
are.
Stormwater
a. The drainage facility to the north is an existing detention pond, not a
drainage channel; therefore, it cannot be piped.
b. There are some grading issues associated with this site.
C. Please see additional Stormwater comments in this letter, below,
Page 1
Steve Olt - Re: revised comments - Brooklyn Park Rowhouses Page 1
From: Susan Joy
To: Steve Olt; swh0101 @aol.com; Troy Jones
Date: 08/29/2006 2:16:27 PM
Subject: Re: revised comments - Brooklyn Park Rowhouses
Just noticed that the comment under Steve's Transportation Planning department paragraph should have
been updated to reflect the city's decision to NOT allow any diagonal parking along the site. It currently
reads is as if there is an opportunity for a variance and I want to make sure that there is no
misunderstanding - Traffic has looked at it and made their determination. There will be no diagonal
parking.
>>> Steve Olt 8/29/2006 1:57:53 PM >>>
Troy and Scott,
Attached is a revised comment letter for your Preliminary Design Review meeting on August 23, 2006,
about the Brooklyn Park Rowhouses, Phase 2 project. This letter contains additional, "final" Stormwater
comments and a comment received from Ron Gonzales of the Poudre Fire Authority since I sent the
previous letter yesterday.
Steve
CC: Cameron Gloss; Carie Dann; David Averill; Eric Bracke; Glen Schlueter; Marc Virata;
Roger Buffington; Ron Gonzales