HomeMy WebLinkAboutRIGDEN FARM, 14TH FILING - FDP - 56-98AS - CORRESPONDENCE - (3)Department: Stormwater-Water-Wastewater Issue
Contact: Roger Buffington
Topic: Water/Wastewater
Number: 81 Created: 4/ 10/2007
[4/ 10/07] Correct sizes of valves on fire lines as noted in red -lined plans.
Number: 82 Created: 4/ 10/2007
[4/ 10/07] There is are electric and cable conflicts with the fire hydrant near
Lot 3.
Number: 83 Created: 4/ 10/ 2007
[4/ 10/07] Add the City details for water main lowerings.
Number: 84 Created: 4 / 11 / 2007
[4/ 11/07] Clarify phasing. If it does not apply to utilities, make that very
clear.
The development plans are in a very good condition. The comments
expressed in this letter could be addressed with direct contact with
appropriate City staff, if needed, and then mylars could be prepared and
submitted. Be sure and return all red -lined plans when you re -submit paper
copies (see Revision Routing Sheet, attached) or submit mylars.
• A copy of a letter received from Lisa Thieme of the Larimer County
Assessor's office is attached to this comment letter.
If you have any questions regarding these issues or any other issues related
to this project, please feel free to call me at 221-6341.
Yours Truly,
Aftsw_
Steve Olt
City Planner
cc: Susan Joy
Interwest Consulting Group
Current Planning file #56-98AS
Page 5
drive aisles, it shall be protected by approved bollards. Please run turning
templates (semi -tractor trailer trucks) to ensure clearance. The four -foot
distance from the curb that was mentioned at Staff Review today is not the
standard PFA uses. Finally, fire hydrants are required to have 42 inches of
clearance (circumference) around the hydrant, which applies to light poles,
vegetation (other than ground cover), etc.
[ 1 / 10/ 07] FIRE HYDRANTS: Due to the proximity of the two fire hydrants
in the parking lot to vehicle traffic, the hydrants shall be protected by a
suitable number and location of protective bollards.
Number: 85 Created: 4 / 11 / 2007
[4/ 11/07] KNOX BOX REQUIRED: Poudre Fire Authority requires a "Knox
Box" to be mounted on the front of every new building equipped with a
required fire sprinkler system or fire alarm system. 97UFC 902.4; PFA
BUREAU POLICY 88-20
Department: Stormwater-Water-Wastewater Issue
Contact: Basil Hamdan
Topic: Plat
Number: 87 Created: 4/ 13/2007
[4/ 13/07] The plat vacates the existing 80-foot drainage easement across
the site. There is a note on the plat showing a new -foot easement to be
dedicated on Lot 9. Please clarify that this new 5-foot easement will be
rededicated by this plat.
Topic: Utility Plans
Number: 80 Created: 4/ 10/2007
[4/ 10/07]
Will the existing storm drainage junction box need to be adjusted at the rim
in order to meet the new grading? The existing rim elevation is 27.13 while
the new rim elevation is 29.40. Please provide an adjustment detail.
How will the inlet within the future development phase be protected in the
interim phase. Protection needs to be mainly vegetative. Please extend the
mulching/ seeding time line for Phase 2 on erosion control construction
sequence table.
Please add a detail for the proposed sidewalk chases.
Silt fence delineation is hard to find since it is overlapping other labels.
Please clarify.
Page 4
Number: 77 Created: 4 / 9 / 2007
[4/9/07] Detail Sheets - Please label all on -site details as "on site".
Thanks.
Number: 78 Created: 4 / 9 / 2007
[4/9/07] Detail Sheet - I will e-mail you the most current pedestrian ramp
detail so that you can replace details 1606 and 1607 with it.
Department: Light & Power Issue Contact: Monica Moore
Topic: Utility Plans
Number: 79 Created: 4 / 9 / 2007
[4/9/07] Transformer location for Lot 7 must be within 10-feet of a paved
surface accessible by an electric line truck.
Department: PFA Issue Contact: Carte Dann
Topic: Fire
Number: 30 Created: 1 / 10/ 2007
[4/ 11/07] Per our discussion, the FDCs will be building -mounted and
located on the street side of the structures (externally, not internally, on the
parking lot side).
[1/10/07] FDC LOCATION: Please call me so we can discuss locations of
the automatic sprinkler fire department connections.
Number: 31 Created: 1 / 10/2007
[4/ 11 / 07] Because all the buildings have fire sprinklers; every point of the
first -floor exterior walls are within 150 of a public street; and the FDCs will
be located on the public -street sides of the buildings, PFA will not require an
Emergency Access Easement.
[1/ 10/07] EMERGENCY ACCESS EASEMENT: Willa blanket EAE be
workable, or should it be revised to specific drive aisles? The fire lane shall
be visible by painting and signage, and maintained unobstructed at all
times. The fire lane must meet the following general requirements:
❑ Be designed as a flat, hard, all-weather driving surface (asphalt or
concrete) capable of supporting fire apparatus weights. Compacted road
base shall be used only for temporary fire lanes or at construction sites.
❑ Have appropriate maintenance agreements that are legally
❑ Maintain the required minimum width of 20 feet throughout the length
of the fire lane. 97UFC 901.2.2.1; 901.3; 901.4.2; 902.2.1
Number: 32 Created: 1 / 10/2007
[4/11/07] External to the site, there are 7 fire hydrants on Iowa, Illinois,
Limon and Custer, so no fire hydrants will be required to be added on the
public -street side of the buildings. Internally, in the parking lot, we will
require only one fire hydrant. This fire hydrant needs to be located on a
suitable traffic island where it will not be exposed to damage from vehicular
traffic. If the hydrant is located within a 25-foot inside turning radius of the
Page 3
Number: 76 Created: 4 / 9 / 2007
[4/9/07] Please provide a barricade after Phase I construction is complete
that would block off the driveway access to Phase II. This way people won't
be trying to cut across the site (and they will).
Topic: Landscape plan
Number: 69
[4/9/07] Please show phasing.
Topic: Plat
Number: 86
[4/ 12/07] From Technical Services:
Created: 4/9/2007
Created: 4 / 12 / 2007
1. Boundary and legal close. One bearing does not match in C 1 curve.
2. Basis of bearings monument descriptions of N 1 /4 corner do not match
the plat.
Topic: Site
Number: 70 Created: 4 / 9 / 2007
[4/9/07] Please show phasing.
Topic: Utility Plans
Number: 71 Created: 4 / 9 / 2007
[4/9/07] Remove all reference to Preliminary Plan, not for construction
prior to mylar.
Number: 72 Created: 4 / 9 / 2007
[4/9/07] Sheet 3 - Please add a few more notes or labels clarifying the
installation/phasing of the sidewalks and onsite utilities. I just want to
make sure there won't be any confusion later as we write the DA, DCP and
then eventually go to construction. Thanks so much, Bob!
Number: 73 Created: 4 / 9 / 2007
[4/9/07] Sheet 4 - See red -lines regarding Note 2. Good note ... would you
mind duplicating it under line 48, too? Thanks!!
Number: 74 Created: 4 / 9 / 2007
[4/9/07] Sheet 9 and typical - the little @ signs will turn into blobs when
scanned. Could you reduce the pen width perhaps? It should scan fine
then.
Number: 75 Created: 4 / 9 / 2007
[4/9/07] Sheet 11 - Will need to phase this sheet too if the storm inlet isn't
getting installed with Phase 1.
Page 2
STAFF PROJECT REVIEW
City of Fort Collins
Don Tiller Date: 04/ 18/2007
LADCO PROPERTIES, LLC
1201 Chickadee Court
Fort Collins, CO 80525
Staff has reviewed your submittal for RIGDEN FARM, 14TH FILING, THE
CENTER AT RIGDEN FARM - FINAL PLANS, and we offer the following
comments:
ISSUES:
Department: Current Planning Issue Contact: Steve Olt
Topic: Site
Number: 88 Created: 4/ 18/2007
[4/ 18/07] There was a bike rack previously shown just to the west of the
building on Lot 2, along Illinois Drive. This rack has apparently been
eliminated. It really should remain to provide accessible bike parking for the
buildings on Lots 1 & 2. Nothing (landscaping, utilities) would appear to
preclude this bike rack.
Number: 89 Created: 4/ 18/2007
[4/ 18/07] The 2 crosswalks in the northerly 8' wide walk (just south of Lots
2 & 10) should be constructed of concrete. This is the public walkway
between developments in Rigden Farm.
Number: 90 Created: 4/ 18/2007
[4/ 18/07] It would be beneficial to show better line (weight) differentiation
between the lot lines, the buildings, and sidewalks on the Site & Landscape
Plans.
Department: Engineering Issue Contact: Susan Joy
Topic: General
Number: 68 Created: 4 / 9 / 2007
[4/9/07] Please add a note to all of the plan sets stating that the City and
Utility companies approved the location of the trash enclosures within the
blanket utility easement. A good place for this note on the utility plan set
would be under line 48 of the General Notes. You can word this note any
way you wish, just want to make sure that you won't have trouble later at
the time of building permit. Chad - do you think it would be appropriate to
put this note on the plat as well?
Page 1