[9/15/07] The reverse curves used in the northwest corner of the Rbt need to
be revised to eliminate the curve C12 (as shown on pg 2 of the Plat). Vehicles
do not follow a path such as the curb is shown. They will straighten it out. It
becomes excess pavement collecting trash and debris.
While this curve will not be necessary for vehicles entering the
roundabout from the north, it will be necessary for vehicles navigating the
circle from the south or east.
Number: 86 Created: 9/15/2007
[9/15/07] Please provide fastest path info indicating the expected circulating
speed of the Rbt.
We will submit our calculations for the roundabout design separately.
This information probably should not be included on the construction
plans.
Be sure and return all of your redlined plans when you re -submit.
If you have any questions regarding these issues or any other issues related to
this project, please feel free to call me at (970) 221-6750.
Sincerely,
Shelby Sommer
Associate City Planner
Page 16
This information is now on the plans.
Number: 68 Created: 8/31 /2007
[8/31/07] Provide 10 feet of separation between City 24" water main and
proposed 12" water main in Timberline.
The waterline has been moved to the other side of the street.
Number: 69 Created: 8/31 /2007
[8/31/071 Show all utility crossings in profile of 12" water main.
The waterline profile has been updated.
Department: Zoning Issue Contact: Gary Lopez
Topic: Zoning
Number: 6 Created: 8/23/2007
[8/23/07] No comments
ISSUES:
Department: Traffic Operations Issue Contact: Ward Stanford
Topic: Traffic
Number: 80 Created: 9/15/2007
[9/15/07] Per LCUASS Fig 8-1, a southbound left turn lane must be provided
on Timberline.
Understood. Please refer to traffic study memorandum included with
resubmittal.
Number: 81 Created: 9/15/2007
[9/15/07] On sheet 2 of the Plat, Dickerson Rd is stated as 57' ROW, but drawn
as an 84' ROW. Please correct labeling.
Revised.
Number: 82 Created: 9/15/2007
[9/15/07] What were the growth factors used in the TIS? What other TIS's
were used in the evaluation of this project?
Please refer to traffic study memorandum included with resubmittal.
Number: 83 Created: 9/15/2007
[9/15/07] Why were Lost Time adjustments used? Why was the called PHF
not used in the analysis?
Please refer to traffic study memorandum included with resubmittal.
Number: 84 Created: 9/15/2007
[9/15/07] Need to provide all LCUASS data for mini -roundabouts, plus full
dimensions of interior island, truck apron, inscribed radius, lane widths
(circulating and approach), ped crossing widths, splitter island, landscaping in
and around Rbt, and any other pertinent design data. .
The roundabout is now detailed on the horizontal control plan
Page 15
[8/29/07] ROUNDABOUT VEGETATION/LANDSCAPING: Please use
landscaping that will not exceed 42 inches in height (with the exception of
canopy trees).
Understood. Appropriate changes have been made.
Number: 70 Created: 8/31 /2007
[8/31/07] STREET NAME: The proposed Dickerson cannot be allowed
because it's too close to the existing Didrickson.
Dickerson Road has been renamed to Collamer Road.
Department: Stormwater-Water-Wastewaterlssue Contact: Basil Hamdan.
Topic: Ditch crossing
Number: 53 Created: 8/28/2007
[8/28/07] Ditch crossing agreements need to be obtained from the ditch
company at final.
Verified with Mayer Sommermeyer that this is a common request they
support- there is a standard agreement that is used.
Topic: Grading Plan
Number: 50 Created: 8/28/2007
[8/28/07] Grading Plan is preliminary in nature; more details are needed at
final.
Understood.
Topic: Master Planned Improvements
Number: 52 Created: 8/28/2007
[8/28/07] The site needs to accommodate a 247 cfs flow from the Cooper
Slough basin into the Dry Creek basin. At this point all we are looking for is to
reserve the right of way to pass this flow. The historic spill from the ditch does
not affect this site. The site needs to reserve a minimum of 15 foot easement
for a future drainage channel along the east property line.
A 20' drainage easement was provided on the east property line.
Preliminary design of the overflow channel was included in the drainage
report.
Topic: Off -site storm
Number: 51 Created: 8/28/2007
[8/28/07], Please provide detailed design at final showing location and capacity
of outfall swale.
The off -site storm discharges into a swale provided by WaterFeld P.U.D.
Additional information can be included in the final drainage report.
Department: Stormwater-Water-Wastewaterlssue Contact: Roger Buffington
Topic: WaterMastewater
Number: 67 Created: 8/31 /2007
[8/31/07] Label size and owner of each water main in Timberline.
Page 14
diagonal of the property).. All structures beyond the 660-foot limit shall be fire
sprinklered if a second point of access cannot be provided. FCLUC
3.6.2(B)(C);3.6.6(I); 97UFC 902.2.2.3
Understood. A modification of standards request for the dead end turn
arounds on Collamer Road south of the round about and Cherryhurst
Road east of the round about is included with this resubmittal.
Number: 57 Created: 8/29/2007
[8/29/071 FIRE LANE TO TIMBERLINE: Does this Emergency Access
Eaesment extend all the way to Timberline Road? Also, does the EAE meet our
turning radius requirement?
Per discussion with city staff September 6 and followup, it has been
determined with PFA that the two emergency access roads are not
required on lots 1-3. All EAEs have been verified to meet turning radius
requirements. Horizontal control plans and the plat indicate the
dimensions of these easements.
Number: 58 Created: 8/29/2007
[8/29/07] EAST FIRE LANE: What is the purpose of the east fire lane?
Per discussion with city staff September 6 and followup, it has been
determined with PFA that the two emergency access roads are not
required on lots 1-3.
Number: 59 Created: 8/29/2007
[8/29/07] ADDRESSING: Building 2 should be addressed off Cherryhurst
Road.
Understood.
Number: 60 Created: 8/29/2007
[8/29/07] FIRE DEPARTMENT CONNECTION: Fire department connections
shall be installed remote from the buildings, and located on the street or fire
lane side of buildings, fully visible and recognizable from the street or nearest
point of fire department vehicle access or as otherwise approved by the fire
code official. If possible, a fire hydrant shall be located within 100 feet of the
FDC. 2006 International Fire Code 912.2.1 and PFA Bureau Policy
Acknowledged. Fire lines are currently shown for each building and fire
department connections will be better established at final when floor
plans are developed for each building.
Number: 61 Created: 8/29/2007
[8/29/07] FIRE HYDRANT RELOCATION: Please move the fire hydrant shown
at Timberline on the north side of Cherryhurst, directly south so it's on the south
side of Cherryhurst.
The fire hydrant has been moved.
Number: 62
Created: 8/29/2007
Page 13
Topic: Landscape Plan
Number: 1 Created: 8/15/2007
[8/15/07] A landscape plan showing locations of planned street lights has been
sent to Vignette Studios showing planned streetlights. These lights will need to
be shown on the landscape plan, and street tree locations adjusted to provide a
minimum of 40 feet of clearance between the lights and the trees (15 feet if the
tree is an ornamental type).
The planned street lights have been added to the plans, with appropriate
modifications to the landscape plan made to accommodate spacing.
Department: PFA Issue Contact: Carie Dann
Topic: Fire
Number: 54 Created: 8/29/2007
[8/29/07] WATER SUPPLY: Fire hydrants, where required, must be the type
approved by the water district having jurisdiction and the Fire Department.
Hydrant spacing and water flow must meet minimum requirements based on
type of occupancy. Minimum flow and spacing requirements include:
Commercial, 1,500 gpm at 20 psi residual pressure, spaced not further than
300 feet to the building, on 600-foot centers thereafter; residential within Urban
Growth Area, 1,000 gpm at 20 psi residual pressure, spaced not further than
400 feet to the building, on 800-foot centers thereafter; residential outside
Urban Growth Area, 500 gpm at 20 psi residual pressure, spaced not further
than 400 feet to the building, on 800-foot centers thereafter.
These requirements may be modified if buildings are equipped with automatic
fire sprinkler systems. 97UFC 901.2.2.2
Acknowledges. The buildings will be equipped with automatic fire
sprinkler systems given their size. Fire hydrants have been provided to
meet the -spacing requirements listed.
Number: 55 Created: 8/29/2007
[8/29/07] CUL-DE-SAC: The cul-de-sacs are required to have a turnaround
with a minimum diameter of 100 feet.
There are no cul-de-sacs included in this site design. A modification of
standards request for the dead end turn arounds on Collamer Road south
of the round about and Cherryhurst Road east of the round about is
included with this resubmittal.
Number: 56 Created: 8/29/2007
[8/29/07] CUL-DE-SAC: A dead-end street cannot exceed six -hundred -sixty
(660) feet in length. The turn -around at the end of the street must have an
outside turning radius of fifty (50) feet or more, and an inside turning radius of
twenty-five (25) feet. Short fire lanes are permitted to facilitate a second point of
access when the street is longer than 660 feet. Separation of the access points
at the minimum must meet the Rule of Remoteness (one-half the length of the
Page 12
Topic: Technical services
Number: 73 Created: 8/31/2007
[8/31/07] Show property ownership to the north - Weld, Larimer Canal ?
The owner of the ditch is now shown on the plat.
Number: 74 Created: 8/31/2007
(8/31/07] Conflict with Dickerson Rd. - please discuss with JR Wilson.
Dickerson Road has been renamed to Collamer Road.
Number: 75 Created: 8/31/2007
[8/31/07] Add street names to the vicinity map.
The vicinity map has been revised.
Number: 76 Created: 8/31/2007
(8/31/07] What are the two Book & Page areas near the NW corner? In the
ROW.
These are easements and are now more clearly shown on the plat.
Number: 77 Created: 8/31/2007
[8/31/07] Who is the access easement dedicated to (85060800) ? Can it be
vacated by this Plat? Please verify.
This easement is being vacated by this plat.
Number: 78 Created: 8/31/2007
[8/31/071 See redlines for additional minor comments.
Acknowledged.
Department: Light & Power Issue Contact: Doug Martine
Topic: Electric Utility
Number: 2 Created: 8/15/2007
[8/15/071 The developer will need to coordinate the power needs for each
building and a location for the electrical transformers with Light & Power
Engineering. Note that transformers must have a minimum of 3 feet of
clearance on 3 sides to any wall, structure or fence, and 8 feet of clearance in
front. Also, transformers must be located within 10 feet of an all-weather
surface accessible to electric utility line trucks.
This detail will be provided as part of initial final submittal.
Number: 3 Created: 8/15/2007
[8/15/07] The source of power to this site will be the existing electric vault on
the west side of Timberline, south of this site. The developer may be required
to provide off -site easements and/or permits as necessary to bring power to this
site.
The existing transformer is within the existing right of way on the west
side of Timberline. 70.5 feet of right of way was dedicated with the
Waterfield P.U.D.
Page 11
Number:41 . Created: 8/28/2007
[8/28/07] Please provide a standard City signature approval block in the lower
right hand corner of all sheets.
Because of the scale and shape of the development it was not possible to
provide the signature block in this location on every sheet. / understand
this request, but cannot find that this is a hard requirement.
Number: 42 Created: 8/28/2007
[8/28/07] How will the future canal crossing be constructed ? The prelim. Off -
site design just shows the road going over the canal at grade.
More detail for the crossing has been provided on the revised utility plans.
Number: 43 Created: 8/28/2007
[8/28/07] Provide intersection details on sheet 23 for T-intersection with
Timberline and mini roundabout per LCUASS 7-27,8-13,8-14 and 8-15.
More detailed information is now on the intersection details.
Number: 44 Created: 8/28/2007
[8/28/07] Complete construction details will be required at the final compliance
stage.
Acknowledged.
Number: 45 Created: 8/28/2007
[8/28/07] See redlines for additional minor comments. Return redlines with
your next submittal. All changes to the Utility drawings must also be reflected
on the Site and Landscape plans.
Acknowledged.
Number: 71 Created: 8/31 /2007
[8/31/07] As discussed at the staff review meeting, some street stubs may be
shortened and money escrowed for future construction to avoid building turn-
arounds. Detailed engineered cost estimates will be required for review.of
those portions of streets not constructed. Full design is still required and off -site
preliminary design as well.
Full street design is being provided, but the revised plans are proposing
paving dead ends at a later date. Type 3 barricades are provided just after
the drive entrances. Since the tracts provide access easements for the
lots, they will allow the public to utilize the parking areas as turn around
areas.
Number: 72 Created: 8/31 /2007
[8/31/07] Please consult with JR in Technical services regarding street naming
conflicts.
Dickerson Road has been renamed to Collamer Road.
Page 10
[8/27/07) Offsite Sewer - Show, label and dimension the off -site easement for
the proposed sewer on Timberline. Clearly show the R.O.W. limits on the plan
view. A letter of intent or signed deed of dedication must be received for the
easement prior to scheduling a public hearing.
The offsite sewer is located within the right of way of Timberline road, no
easement is necessary.
Number: 35 Created: 8/27/2007
[8/27/07] No profile information was provided for the sewer, storm drains and
water mains proposed. Will be reviewed with the next submittal.
Profiles are now provided for all of the necessary utilities.
Number: 36 Created: 8/27/2007
[8/27/07] Sheets 15 & 16 were not included in the plan set for the Timberline
design. Need to provide any interim and ultimate design information with cross
sections every 50 feet and a preliminary off -site design for 1000 feet in both
directions.
These sheets are provided in the current set.
Number: 37 Created: 8/27/2007
[8/27/07] Please provide an intersection detail for the intersection of
Cherryhurst and Timberline. Show all dimensions and elevations per LCUASS
7-27.
An intersection detail sheet has been provided with this information
Number: 38 Created: 8/28/2007
[8/28/07] Call out all standard driveways, sidewalks, pedestrian ramps and curb
& gutter on the street design plans (Typ.)
Acknowledged
Number: 39 Created: 8/28/2007
[8/28/07] LCUASS standards do not allow single point grade breaks to exceed
0.4% algebraic grade difference. Please provide vertical curves or additional
grade breaks at these locations. See redlines - street design profiles for
clarification. Add slope and elevation information where needed per the
redlines. All proposed street grades must tie back into existing grades. Please
show locations of proposed inlets at low points on the profile.
Profiles have been revised.
Number: 40 Created: 8/28/2007
[8/28/07] Arterial cross sections - please provide the following information on at
least one cross section (labeled typ.): Dimensions, ROW limits, pavement cross
slopes, max side slopes 4:1 max. All proposed grades must be shown tying
back into existing grades in the cross sections. Any grading outside the ROW
limits may require an easement for road construction (i.e. slope easement).
Additional information has been provided.
Page 9
street name must be selected from an approved list of street names. Please
contact JR Wilson in Technical Services for approved street names.
Acknowledged.
Number: 28 Created: 8/27/2007
[8/27/07] Plat - Please hatch fill the new ROW dedication area. The separation
distance from the centerline of Timberline to the centerline of the private drive
access on Cherryhurst must be no less than 460 feet. The Plat shows a
separation of only 400 feet. Please revise or submit a variance request with
justification. Will the private drives be named? Please consult with PFA for
naming and addressing on private drives.
Per September 6 staff review, given the site constraints staff agreed to
allow an engineering variance to the private drive spacing on Cherryhurst.
In addition, it was agreed that all buildings can be addressed off either
Cherryhurst Road or Collamer Road. As a result the private drives will not
be named.
Number: 29 Created: 8/27/2007
[8/27/07] Please fix line over text and labeling throughout the plan set to
comply with the LCUASS Appendix E scannability requirements. See redlines
for clarification.
Done.
Number: 30 Created: 8/27/2007
[8/27/07] Please show all proposed limits of street cuts needed for utility work
and add the standard street cut note provided where applicable. See redlines
for clarification.
Additional street cuts are shown with the applicable notes
Number: 31 Created: 8/27/2007
[8/27/071 Grading - Please provide adequate spot elevations on the grading
plans to check drainage with arrows showing surface drainage patterns.
Additional information has been added to the plans.
Number: 32 Created: 8/27/2007
[8/27/07] Grading - Some drainage is being directed to low spots where water
will pond. Please see redlines for clarification.
Additional information has been added to the plans.
Number: 33 Created: 8/27/2007
[8/27/07] Grading - Label topo lines with elevations and call out all
inflow/outflow gutters and curb openings. Details must be provided at the final
compliance stage.
Additional information has been added to the plans.
Number: 34
Created: 8/27/2007
Page 8
Aknowledged. The plans have been revised and updated to include
additional information.
Number: 23 Created: 8/27/2007
[8/27/07] Please provide review comments from Boxelder Sanitation and Elco
Water District with your next submittal.
It was understood that the City forwarded plans to the appropriate
agencies. Since this was not the case, these agencies are reviewing the
revised plans and we will submit review comments when they are
received from them.
Number: 24 Created: 8/27/2007
[8/27/07] Plat Cover Sheet - Please provide a different vicinity map that shows
one -line named streets and project location without shading and topography.
The vicinity map will not scan well and does not comply with LCUASS Appendix
E.
The vicinity map has been revised.
Number: 25 Created: 8/27/2007
[8/27/07] The proposed street layout does not comply with section 3.6.3.f for
street stub connections at no more than 660 feet measured along the project
boundary to developable parcels. Please provide a street stub connection
every 660 feet or request for modification based on justification.
Per September 6 staff review, two pedestrian connections are provided
from the developments pedestrian network to the property to the south.
Given the Larimer and Weld Canal on the north, it was agreed that no
additional connections are required on the north other than provisions for
extension of Collamer Road when the adjacent north property is
developed.
Number: 26 Created: 8/27/2007
[8/27/07] The proposed street stub connections do not comply with City Land
Use Code Section 3.6.6.D.4.f.2 for dead ends. No dead end may exceed 660.
feet without standard cul-de-sac turn arounds provided. Please also see
comments from PFA for access and dead end lengths.
Decision has been made that we are not required to build extension/turn
around for Collamer beyond the north edge of round about, given the
length of the dead end is less than 150' A modification of standards is
included with this resubmittal to address the dead-end created for
Cherryhurst Road east of the round about and Collamer Road south of the
round about.
Number: 27 Created: 8/27/2007
[8/27/07] Plat - Dickerson at the canal crossing is mislabeled as 57 feet of
ROW. Should be changed to 84 feet. Dickerson will be an arterial and the
Page 7
Number:14 . Created:8/27/2007
[8/27/07] Is there any fencing proposed? What about trash enclosures?
Please identify on site plan and provide elevations.
Location of and detail for fencing and trash enclosures has been
provided.
Number: 46 Created: 8/28/2007
[8/28/07] Per Section 3.5.3 Variation in Massing of buildings is required.
Horizontal masses shall not exceed a height:width ratio of 1:3 without
substantial variation in massing that includes a change in height and a
projecting or recessed elements. The Rectangular and V Shaped Building
types are especially problematic and need more variation in the large horizontal
massing, but all of the elevations could use some work.
Additional detail has been provided for the elevations.
Department: Current Planning Issue Contact: Dana Leavitt
Topic: Site Plan
Number: 63 Created: 8/29/2007
[8/29/07] Natural Area buffer,for the canal is not being met. During a site visit
in June, it was agreed that an average 50' buffer would be appropriate. With
the inclusion of two emergency access drives located within the buffer, this
approach will need to be re-evaluated.
Per the September 6 review with city staff, several changes have been
made. The emergency access roads have been removed from the plan
per agreement with PFA. Further, the parking area on the northwest
portion of site has been modified to maintain at least a 25' minimum
buffer, with an average buffer exceeding 50'.
Department: Current Planning Issue Contact: Shelby Sommer
Topic: Technical services
Number: 79 Created: 9/4/2007
[9/4/07] Although the street names were selected from the approved street
name list for Arterial/Collector streets, Dickerson is too similar to other street
names in use. Please select another name from the approved street name list
and then we will cross-reference it with the existing names to make sure there
isn't another conflict. Thanks.
Dickerson Road has been renamed to Collamer Road.
Department: Engineering Issue Contact: Randy Maizland
Topic: Engineering
Number: 22 Created: 8/27/2007
[8/27/07] The Utility Plan set is incomplete. Review comments are only as
complete as the information provided. No street design plans were included for
Timberline Road. Several plan and profile sheets do not have a profile design
provided.
Page 6
this is a step in the right direction, it appears that patios have been proposed on
each building that does not meet the requirement as a means to avoid the
standard. In order for this alternative to be considered you'll need to provide
information as to how these patios add pedestrian interest, comfort and visual
continuity along the sidewalk. At this stage I don't see how these patios are an
acceptable alternative to the build -to standard.
Per discussion with city staff September 6, the buildings on the south
portion of the development have been reconfigured to face Collamer
Road, in response to this concern.
Number: 12 Created: 8/27/2007
[8/27/07] The majority of the proposed buildings have footprints greater than
10,000 square feet. Per Division 4.5(E)(2)(1) for any building with a footprint in
excess of 10,000 sq. ft., walls that are greater than 75 feet in length shall
incorporate recesses or projections created by wall plane returns of at least 30
feet; any such building shall be differentiated into multiple sections of mass in
order to achieve proportions that are compatible in scale with adjacent
residential neighborhoods. Please revise plans so that walls over 75 feet in
length are recessed/projected as specified in this section. The building
elevations appear to do this, but it is not clear on the site plan if you are actually
satisfying this standard.
Additional detail has been provided for the building elevations and the
site plan building footprints to meet the building standards.
Number: 48 Created: 8/28/2007
[8/28/07] Please clearly define the small neighborhood park area on the site
plan. The location of the park should be a highly visible area formed by the
street layout and pattern of lots and easily observed from streets. As proposed,
the park does not accomplish this standard as it is not visible from any street,
with the exception of Timberline. Please see Division 4.5(D)(6) for Small
Neighborhood Park standards.
The site design has been modified to make the park more visible from
Cherryhurst Road. These changes include re -orientation of the Lot 8
building and modification of the parking and pedestrian paths on the
north side of the park.
Topic: Building Elevations
Number: 13 Created: 8/27/2007
[8/27/07] The base treatments on the buildings need to be a little more
recognizable and defined. For "L" and Building Type 1 it appears to be cultured
stone, but for the "Rectangular" and ' V" shaped building, there is no defined
base treatment - the cultured stone actually extends all the way up to the
second floor in some areas. Also, please label the maximum building height
on the elevations.
Additional detail has been provided for the elevations.
Page 5
Landscape material size and species will be specified in final plans.
Department: Current Planning Issue Contact: Shelby Sommer
Topic: Lighting Plan
Number: 15 Created: 8/27/2007
[8/27/07] FYI - "Tracts" is misspelled on the lighting plan statistics table.
Otherwise, lighting plan looks fine.
This has been corrected. The plan was updated to the new site plan.
Department: Current Planning Issue Contact: Dana Leavitt
Topic: Plat
Number: 65 Created: 8/29/2007
[8/29/07] A note will be required on the plat explaining the allowable uses
within the natural area buffer zone.
The following note has been added to the plat. "Allowable uses within the
natural area buffer zone Latimer and Weld Canal are defined by Fort
Collins Land Use Code 3.4.1(e)."
Department: Current Planning Issue Contact: Shelby Sommer
Topic: Site Plan
Number: 8 Created: 8/27/2007
[8/27/07] Please clearly identify which buildings/units will be used for
Independent Living facilities. Per the definition of Independent Living in the
Land Use Code, such facilities must occupy no more than 25 percent of the
total GROSS AREA of a long-term care development. Please include
calculations confirming the total gross area of the independent living facility with
respect to the total gross site area of the whole development.
Per discussions with Shelby Sommer and Peter Barnes, it was determined
the 25% calculation can be based either on total gross area or total floor
space. Given the mix of uses and difficulty in specifying the specific
gross area attributable to the independent living uses, it was decided to
use floor space as the basis for this determination.
Number: 9 Created: 8/27/2007
[8/27/07] Please include lot sizes on the site plan in addition to the floor area
estimates.
Done.
Number: 10 Created: 8/27/2007
[8/27/07] Please show adjacent property uses on the site plan.
Adjacent property uses and zoning provided.
Number: 11 Created: 8/27/2007
[8/27/07] As stated in the Conceptual Review letter, this proposal does not
satisfy the "build -to" line requirements in Section 3.5.3(B)(2). The response
says that patios have been provided as a means to meet this standard. While
Page 4
Department: Current Planning, Issue Contact: Shelby Sommer
Topic: Landscape Plan
Number: 16 Created: 8/27/2007
[8/27/07] Please include size and species of each landscape item.
Landscape material size and species will be specified in final plans.
Number: 17 Created: 8/27/2007
[8/27/071 Please show proposed landscape treatment for all areas not covered
by buildings, parking, etc. including the park area (turf?), setback areas....
Hatching has been added to identify turf and shrub areas. Detailed
specification will be provided in final plans.
Number: 18 Created: 8/27/2007
[8/27/07] Foundation plantings are required along high visibility/use areas of
buildings.
Hatching has been added to identify turf and shrub areas. Detailed
specification will be provided in final plans.
Number: 19 Created: 8/27/2007
[8/27/07] The parking lot west of Tract C does not appear to feature any interior
landscaping - 6% interior landscaping is required.
Per discussion with city staff September 6, it was determined this parking
lot does meet the intent of interior landscaping. Measuring the parking lot
as being 63 feet wide (as measured between back of head -in parking
curbs) and 131 feet in length (measured from back of curb on north side
to back of street walk on south side) total parking area. is 8,253 square
feet. The four landscape areas in each corner of lot are 1,192 square feet,
resulting in landscaping in 14.4% of parking lot.
Number: 20 Created: 8/27/2007
[8/27/07] Parking bays shall extend no more than 15 parking spaces without an
intervening landscape island. Please see redlines for problem area(s).
Plan has been modified as requested.
Number: 21 Created: 8/27/2007
[8/27/07] Please clearly identify the locations, species, size and condition of all
significant existing trees, each with your intent to remove, transplant or protect.
Add tree protection specification notes to the landscape plan so that existing
trees will be protected appropriately.
A plan sheet has been added containing this information.
Department: Current Planning
Topic: Landscape Plan
Number: 64
[8/29/07] Provide a plant list.
natural area buffer.
Issue Contact: Dana Leavitt
Created: 8/29/2007
Native plant species will be required within the
Page 3
1. There must be maintained a maintenance and operation road on the south
side of the ditch (the low side) that is at least 25 feet wide from the edge of the
ditch perpendicularly measured out. In scaling off the drawings it appears to
me that along a portion of the northeasterly corner of this subdivision, primarily
along Tract C and a portion of Lot 4 that the access road has not been provided
at a width of 25 feet.
Per phone conversation September 20 with Mayo Sommermeyer, current
plan is acceptable as long as buildings and/or improvements do not
encroach into the 25 feet access road buffer measured from top of ditch.
It is acceptable for lot lines to encroach upon the 25' access road buffer.
The current road will not be improved by the ditch company.
-2. There should be some type of fencing along the northerly boundary.of the
subdivision to keep out or discourage people from the subdivision from
accessing the ditch maintenance road and the irrigation ditch. The ditch at that
point is quite wide and carries a large amount of water. If a person or animal
were to find themselves in the ditch when we are running a full ditch it is likely
they may not survive. A fence also keeps the ditch bank and the ditch shelf
from being a depository for unwanted personal items or yard refuse.
Per review. with Dana Leavitt, a 4 foot high rail fence with wire mesh is
provided along Larimer and Weld Canal border. This requirement was
discussed with Mayo Sommermeyer and received his verbal approval.
By way of caution, the developer should be aware of the fact that there is
probably some degree of "seep" from this ditch when it is running. There are
many areas along the ditch where there is significant seep, which may have an
effect on how foundations, barrier walls, and other construction details are
approached and handles. It will be recommended by me that the developer
confer with our ditch superintendent, Mr. Bill Johnson, at 222-0090 to determine
what seep history there may be in that area.
Acknowledged. .
Number: 47 Created: 8/28/2007
[8/28/07] The following departments/agencies have no concerns with this
proposal: Water Conservation, Park Planning, GIS, Real Estate Services,
Comcast
Thanks!
Department: Current Planning Issue Contact: Dana Leavitt
Topic: Grading Plan
Number: 66 Created: 8/29/2007
[8/29/071 Add Tree Protection notes to the plan.
Tree protection notes have been added.
Page 2
STAFF PROJECT REVIEW
City of Fort Collins
Response to LIBERTY FARMS PDP — TYPE II comments embedded.
DON TILLER Date: 09/04/2007.
VIGNETTE STUDIOS
144 N MASON ST STE 2
FT COLLINS, CO 80524
Staff has reviewed your submittal for LIBERTY FARMS PDP - TYPE II, and we
offer the following comments:
ISSUES:
Department: Advance Planning
Topic: Site Plan
Number: 49
[8/28/07] No comments.
Issue Contact: Pete Wray
Created: 8/28/2007
Department: Current Planning Issue Contact: Shelby Sommer
Topic: General
Number: 4 Created: 8/23/2007
[8/23/07] Please see the attached Building Codes and Standards that will apply
to this proposal. Please schedule the required pre -submittal meeting as noted.
Understood. Pre -submittal meeting will be scheduled prior to building
permit application.
Number: 5 Created: 8/23/2007
[8/23/07] Bonnie Ham (Growth Coordinator - US Postal Service): Developer
must provide mailboxes for residents receiving mail directly. The location,
number and type of mailboxes is negotiable. Please contact Bonnie at 301 E.
Boardwalk, Fort Collins, CO 80525 or bonnie.j.ham@usps.gov for more
information.
Per guidance provided by Bonnie Ham, the mail delivery will be provided
to a central building mail room. This will eliminate the need for change in
address as residents move within the facility as their needs dictate.
Number: 7 Created: 8/27/2007
[8/27/07] Mayo Sommermeyer (Representing Larimer and Weld Canal):
I am general counsel for the Laimer and Weld Irrigation Company.
I have reviewed the submissions of August 8, 2007 with the accompanying
project comments sheet.
Our major supply ditch, the Laimer and Weld Canal, runs on the northern
boundary of this subdivision. We have two major concerns: