City of Fort Collins COMMENT SHEET
Current Planning
DATE: March 141 2007 TO: Technical Services
PROJECT PLANNER: Steve Olt
#42-05A TALON ESTATES PDP — TYPE I
Please return all comments to the project planner no later than the staff
review meeting:
March 28, 2007
Note -.Please identify Your redlines for future reference
I . e'-U P V'A4_' r � LE6 AL C 10SE,
❑ No Problems
❑ Problems or Concerns (see below, attached, or DMS)
01 TYE /Z co /J ff (106,41)
"C m / 31
Name (ple print)
CHECK HERE IF YOU WISH TO RECEIVE COPIES OF REVISIONS
_Plat _Site _Drainage Report _Other
_Utility _Redline Utility _Landscape
6a
City of Fort Collins
FORT COLLINS-LOVELAND WATER DISTRICT \ SOUTH FORT COLLINS SANITATION DISTRICT
V
March 26, 2007
Mr. Steve Olt
City of Fort Collins
P.O. Box 580
Fort Collins, CO 80525
RE: Talon Estate PDP
Dear Mr. Olt,
RECEIVED
fM2P
CURRENT PLANNING
The Fort Collins - Loveland Water District has reviewed the above mentioned project and submits the
following comments.
The existing District water services are to be connected to the new Fort Collins water line after
the water line has been put into service. The District's existing water line must remain in service
until all water services have been relocated.
The District will require a signature block on the construction sheets that affect District facilities.
All work on or around District facilities are to be coordinated with the District.
The property needs to be excluded from the District boundaries. The Petition for Exclusion
packet can be obtained at the District's office
Please do not hesitate to contact me at 226-3104, ext. 104, if you have any questions or require additional
information.
Respectfully,
�—
Mr. Try W. Farrill, P.E.
District Engineer
xc: Mr. Michael D. DiTullio, District Manager
Mr. Kevin Forbes, P.E., Stewart & Associates
5150 Snead Drive, Fort Collins, CO 80525 Phone (970) 226-3104 Fax (970) 226-0186
Yours Truly, mftobk�
Steve Olt
City Planner
cc: Susan Joy
George & Nadine Holter
Current Planning file #42-05A
Page 7
J
Number: 128 Created: 3/ 29 / 2007
[3/29/071 Stormwater is ready for a hearing. Additional comments may
follow at Final Compliance.
Department: Stormwater-Water-Wastewater Issue
Contact: Roger Buffington
Topic: Water/Wastewater
Number: 85 Created: 2/ 12/2007
[3/27/07] There are discrepancies on service line locations within the
utility plans between the overall utility plan and the sanitary sewer plan and
profile sheets. It still appears that some of the sewer services are shown on
the high side of the lots which may eliminate basements
[2/ 12/07] Coordinate locations of water/sewer services between utility
plans and landscape plans. Some of the sewer services on the landscape
plan are toward the high side of the lots.
Number: 87 Created: 2/ 12/2007
[3/27/07] How much clear distance between water main and storm sewer
at the point of crossing? 12" required.
[2/ 12/07] Show 16" water main on storm sewer plan and profile sheet.
Also include the FCLWD water main. (Has set of utility plans been provided
to the district for review?)
Number: 88 Created: 2/ 12/2007
[3/27/071
[2/ 12/07] Add FCLWD signature block.
Number: 119 Created: 3 / 27 / 2007
[3/27/07] Revise grading to minimizes cuts on Falcon Drive over 16-inch
water main and thereby, eliminate the need for insulation.
Number: 129 Created: 3 / 29 / 2007
[3/ 29 / 07] See redlined plans for other comments.
This development proposal may now be scheduled for an
Administrative Public Hearing. Contact me to work with you in scheduling
the date, time, and place for this hearing.
Be sure and return all red -lined plans when you formally submit Final
Compliance Plans.
If you have any questions regarding these issues or any other issues related
to this project, please feel free to call me at 221-6341.
Page 6
..
Number: 112 Created: 3 / 23 / 2007
[3/23/071 Streetlights will be installed with this development.
Department: PFA Issue Contact: Carte Dann
Topic: Fire
Number: 14 Created: 1 / 3 / 2007
[3/28/07] Both Longwing Drive and Broadwing Road are acceptable street
names.
[1/3/07] STREET NAME: Talon Drive cannot be used, because it is too
similar to an existing street name. Also, because this street makes a 90-
degree turn, it is required to become a second, new street with a separate
name. Contact me with prospective street names and I can confirm whether
they're acceptable.
Department: Stormwater-Water-Wastewater Issue
Contact: Wes Lamarque
Topic: Erosion/Sediment Control
Number: 117 Created: 3/ 27/ 2007
[3/27/071 Please add the City's standard erosion control notes dated
September 2003 to the plan set and delete any other notes related to erosion
control.
Topic: Stormwater
Number: 18 Created: 1 / 4 / 2007
[3/27/07] The City requires a detailed grading plan for residential lots to
include all the detailed information that is needed for the lot to be
constructed per plan. This includes the building envelope, building FF
elevations, lot corner spot elevations, high points or break point spot
elevations within the lot that show a minimum of 2% grade to the lot
corners, and actual final grading contours that show grading around the
structures. A variance would be required to do anything less. The City
recommends a meeting to discuss alternatives for a variance. This can be
done now or after hearing. Also, why are the FF elevations so high above
the sidewalk elevations? Is the plan to have garden level back yards,
walkouts? Driveways may be extremely steep with these FF elevations.
[2/ 15/07]
[ 1 / 4 / 07] At final compliance, a detailed grading plan will be required
showing final grades and building F.F. elevations.
Number: 118 Created: 3 / 27 / 2007
[3/27/07] Since the FCLWD line is being abandoned, can the storm sewer
be moved south to 10 feet north of the proposed sanitary sewer.
Page 5
Number: 120 Created: 3 / 28 / 2007
[3/28/07] Hi Justin! Great submittal! I didn't have enough time this week
to review the plans for Final Compliance items, sorry!! I will look at the
plans in greater detail with your first round of Final Compliance review but
everything looks good for hearing. Great job! : )
Topic: Utility Plans - Plan & Profiles
Number: 40 Created: 1 / 6/ 2007
[3/23/07]
[2/7/07] Repeat. Until this information is shown, the street grades may
need to be adjusted to meet the minimum cover requirements.
[1/6/07] Plan and Profile sheets - Please show the water line (keep in mind
minimum cover requirements set forth in section 12.2.2. Show and station
all proposed driveways, provide missing slope info & missing VC info, and
for both street widenings - show, label and dimension in accordance with 7-
24. You can provide a detail off to the side if scannability becomes an issue.
(Per Mike Herzig, R1 = 20'-36')
Number: 72 Created: 2 / 8 / 2007
[3/23/07] (FC) You are doing this, just the notation is wrong on a couple of
sheets. No biggie. See red -lines.
[2 / 8/ 07] Final Compliance - mid -block cross -pans must be 12' minimum.
Number: 130 Created: 3 / 30 / 2007
[3/30/07] If the District's water line is to be abandoned, it must be
abandoned in accordance with LCUASS 22.1.2.A.2.c keeping in mind that
you still have to meet minimum cover requirements required by 12.2.2. If
you can't get the minimum cover over the abandoned pipe, then you'll need
to remove the old pipe and backfill in accordance with 22.2.3.
Department: Light & Power Issue Contact: Alan Rutz
Topic: Light & Power
Number: 109 Created: 3 / 23 / 2007
[3/23/07] The main electric system will be installed on the north side of
Falcon Drive between the curb and sidewalk. A proposed storm drain
shown in this area will need to be moved.
Number: 110 Created: 3 / 23 / 2007
[3/23/07] The overhead electric line along Falcon Drive belongs to the City
of Ft Collins. This line will be removed and undergrounded when this
project is developed.
Number: 111 Created: 3 / 23 / 2007
[3/23/07] Show location of the existing gas line and the proposed extension
of the gas line along Falcon Drive.
Page 4
Number: 116 Created: 3 / 23 / 2007
[3/23/071 (FC) New plantings are shown on the south side of Falcon Drive
at the Broadwing Road intersection. This development is not required to
plant or maintain them in any way. Just wanted to make sure that you
knew that.
Topic: Plat
Number: 101
[3/23/071
Created: 2/ 14/2007
[2/ 14/07] From Technical Services - Add note about wildlife buffer, see
redlines.
Topic: Site
Number: 64 Created: 2 / 8 / 2007
[3/23/07]
[2/8/07] Dimension all sidewalks and parkways.
Number: 71 Created: 2 / 8 / 2007
[3/23/071 (FC)
[2/8/07] Tract A easements do not match the plat.
Number: 113 Created: 3 / 23 / 2007
[3/23/07] (FC) Use a radius instead of angle points where the sidewalk
meanders around. Also, suggest increasing the width of the sidewalk by 2'
and just doing concrete to the existing fence because you can't use gravel or
mulch in that area (see 16-1 in Chapter 16 of LCUASS). Landscaping this
area is tough ... very hard to maintain BUT whatever you come up with that
doesn't contradict 16-1 is ok by me : )
Number: 114 Created: 3 / 23 / 2007
[3/23/07] (FC) Missing a driveway at Falcon Drive bend.
Topic: Utility Plans - General
Number: 34 Created: 1 / 5/ 2007
[3/23/071 (FC) Just carrying the comment forward to final compliance.
[2/7/07] Repeat. Driveways need to be shown on the plans designed in
accordance with 706. Per LCUASS 9.4.2, driveways must be perpendicular
to the CL of the road, plus or minus 10 degrees, for a minimum of 25' from
the curb.
[ 1 / 5/ 07] All existing driveways along Falcon Drive must be built in
accordance with detail 706.
Page 3
ti
•
Number: 126 Created: 3 / 29 / 2007
[3/29/071 The Property Boundary lines along the north and east sides of
the property, although labeled as asked for, seems inconsistent (line weight)
from the Property Boundary lines along the west and south sides of the
property.
Number: 127 Created: 3 / 29 / 2007
[3/29/07] Under PROPERTY DESCRIPTION on the Site Plan, the reference
to Replat of Tract 'A' is incorrect. This property has not been platted and
there is no Tract 'A' to replat; therefore, this should be changed to Talon
Estates, situated in ...
Topic: Stormwater
Number: 122 Created: 3 / 29 / 2007
[3/29/07] Ed Wendel of the Pleasant Valley & Lake Canal Company has
indicated that it appears that his concerns with storm drainage have been
met with the storm drain connection to Taft Hill Road.
Topic: Utility Plans
Number: 95 Created: 2/ 13/2007
[3/29/07] Carried over only as a reminder.
[2/ 13/07] Len Hilderbrand of Xcel Energy offers the following comments:
a. An existing gas main ends at 448' west of the west right-of-way line of
South Taft Hill Road. The main is a 3/4" MW steel pipe.
b. To serve the proposed new lots in this development, the existing 3/4"
main will need to be re -enforced to a new 1-1/4" main.
Please contact Len directly if you need additional information regarding his
comments.
Topic: Utility Plans -General
Number: 121 Created: 3 / 29 / 2007
[3/29/071 A copy of the comment letter (dated 3/26/07) received from
Terry Farrill, Fort Collins -Loveland Water District, is attached to this City
Staff comment letter.
Department: Engineering Issue Contact: Susan Joy
Topic: Landscape Plans
Number: 115 Created: 3/ 23/ 2007
[3/23/071 (FC) Driveways need to match the utility plans.
Page 2
r
STAFF PROJECT REVIEW
City of Fort Collins
Stewart & Associates, Inc. Date: 04/02/2007
c/o Kevin Forbes, P.E.
103 South Meldrum Street
Fort Collins, CO 80521
Staff has reviewed your submittal for TALON ESTATES, PDP - TYPE 1, and
we offer the following comments:
ISSUES:
Department: Current Planning Issue Contact: Steve Olt
Topic: General
Number: 125 Created: 3 / 29 / 2007
[3/29/07] City staff has determined that the latest set of revised plans as
submitted are in a condition to enable staff to schedule an Administrative
Public Hearing. Comments expressed in this letter may be addressed with
the Applicant's formal Final Compliance Plan submittal for review, after the
public hearing.
Topic: Landscape Plans
Number: 123 Created: 3 / 29 / 2007
[3/29/07] The Landscape Plan specifies 1.25" caliper street trees, which are
permitted by the table in Section 3.2.1(D)(4) Tree Species and Minimum
Sizes of the Land Use Code, for street trees on a Residential Local Street.
However, a neighbor has expressed a request for this development to
provide as much landscaping as possible to help mitigate the visual impact
of a number of new homes across Falcon Drive from the existing homes. The
standard minimum street tree size is 2.0" caliper. Although not required by
the City, it would be a significant and more considerate gesture if this
developer would initially plant at least 2.0" caliper street trees along the
Falcon Drive frontages. If the developer is willing, please make this change
in the Plant List on the Landscape Plan.
Number: 124 Created: 3 / 29 / 2007
[3/29/071 On the Landscape Plan, please label, or indicate "Typical"
somewhere, the Property Boundary.
Topic: Site
Number: 49 Created: 2 / 2 / 2007
[3/29/071 However, the Property Boundary must be labeled on the Site &
Landscape Plans so that it can be distinguished from the lot lines.
[2/2/07] Please label the Property Boundary on the Site Plan. Falcon Drive
should not be shown to be included in the Property Boundary as it appears
to be on the Site Plan. The Landscape Plan and Subdivision Plat are correct.
Page I