HomeMy WebLinkAboutFOSSIL LAKE FOURTH FILING, FIRST REPLAT - PDP - 33-01Q - CORRESPONDENCE - (5)w
Steve Olt
Planning Department, City of Ft. Collins July 29 2007
P.O. Box 580
Ft. Collins, Co. 80522
Below is the U.S. Postal Service's referral response for project: #33-01Q Fossil Lake
Fourth Filing 1 s` Replat Type I
Referral Response
Mail Service: Centralized delivery using of a minimum of 6 centralized box units
( industry type III ) is required. Revise plan to show the required CBU locations as
approved by the U.S. Postal Service. In all cases the CBUs must be located in the
public right of way or a designated easement. Be advised the responsibility of
purchase and maintaining the CBUs with the concrete pads is that of the
owner/developer/builder/HOA. Prior to occupancy within the development approved
mail receptacles will be in place. Delivery Agreement will be in place prior to any
delivery of mail.
Contact Bonnie Ham Growth Coordinator, U.S. Postal Service
301 E. Boardwalk, Ft. Collins, Co.,
phone # 970-225-4130,
cell # 970-214-3668,
fax # 970-225-4139.
Thank you,
Bonnie Ham
USPS Ft. Collins
The District will require another review due to the nature and number of the above comments. Please do
not hesitate to contact me at 226-3104, ext. 104, if you have any questions or require additional
information.
Respectfully,
�
Mr. T�"
W. Farrill, P.E.
District Engineer
xc: Mr. Michael D. DiTullio, District Manager
North Star Design Inc.
Fossil Lake Condominiums, LLC
• 1 FORT COLLINS•LOVELAND WATER DISTRICT \ SOUTH FORT COLLINS SANITATION DISTRICT
V
August 1, 2007
Mr. Steve Olt
City of Fort Collins
P.O. Box 580
Fort Collins, CO.80525
RE: #33-01Q Fossil Lake PDP
Fourth Filing — 1st Replat Type I
Fossil Lake 7`s Filing
Dear Mr. Olt,
The Fort Collins - Loveland Water District and the South Fort Collins Sanitation District have reviewed
the above mentioned project and submits the following comment.
The sanitary sewer manholes and sewer lines need to be at least five feet from the face of the
curb.
The proposed buildings need an identification for reference and the number of dwelling units for
each building needs to be shown.
The existing 24 inch water line in Ziegler Road needs to be shown.
The meter pits and vaults need to be located within the utility easement.
The District requires fire hydrants at the end of all dead-end water lines.
The landscaping plan needs to be submitted for review.
The beginning, end, length of water line to be deflected and maximum depth needs to be shown
on the proposed deflection.
The maximum depth of the water line lowerings needs to be shown.
The dead-end, 6 inch water lines need to be eliminated.
The phasing sequence needs to be identified.
An irrigation tap was not shown, how will the open areas/landscape be irrigated?
vE CEIVEI)
AUG 0 2 2007
5150 Snead Drive, Fort Collins, CO 80525 Phone (970) 226-3104 Fax (970) 226-0186
This item may be scheduled for an administrative public hearing. I will
assist you with the scheduling of the date, time, and place for the hearing.
Be sure and return all red -lined plans if/when you re -submit prior to the
public hearing. Please check with me for a Final Plan Routing Sheet before
submitting Final Compliance Plan documentation.
If you have any questions regarding these issues or any other issues related
to this project, please feel free to call me at 221-6341.
Yours ,Truly,
I �,{/v � "-
Steve Olt
City Planner
cc: Sheri Langenberger
Fossil Lake Condominiums LLC
North Star Design, Inc.
King Surveyors
Planning & Zoning file #33-01Q
Page 5
Department: Light & Power Issue Contact: Janet McTague
Topic: General
Number: 1 Created: 7 / 30 / 2007
[7/30/07] Light and Power will provide streetlighting along dedicated
roadways. Private drive streetlighting will be provided by the
developer/ builder.
Number: 2 Created: 7 / 30 / 2007
[7/30/07] We'll need to coordinate transformer locations that are within 10'
of a paved surface. A preliminary design has been done and we'd be happy
to work with the developer to see if the proposed locations will work. Please
contact Janet McTague at 224-6154.
Number: 3 Created: 7 / 30 / 2007
[7/30/07] Electric meters will be banked on one wall. Please provide
separation from electric meters and gas meters.
Number: 4 Created: 7 / 30 / 2007
[7/30/071 If necessary, any relocation of the existing electric facilities in the
area will be an additional developer expense.
Department: PFA Issue Contact: Carie Dann
Topic: Fire
Number: 5 Created: 7 / 31 / 2007
[7/31/071 FIRE DEPARTMENT CONNECTIONS: The FDC for the sprinkler
systems shall be easily accessible from the public street or, in the instances
of Buildings E and F, from the private drive. The fire line supplying the
sprinklers is required to be a minimum diameter of 6 inches, unless
hydraulic calculations can show a smaller line can supply the sprinklers.
Number: 6 Created: 7 / 31 / 2007
[7/31/071 KNOX BOX REQUIRED: Poudre Fire Authority requires a "Knox
Box" to be mounted on the front of every new building equipped with a
required fire sprinkler system or fire alarm system. 97UFC 902.4; PFA
BUREAU POLICY 88-20
Number: 7 Created: 7 / 31 / 2007
[7/31/07] EMERGENCY ACCESS: Because buildings E and F, and possibly
Building D, are considered out of access for emergency vehicles, if the
buildings are not equipped with automatic fire sprinklers, the private drive
providing access to these buildings shall be dedicated on the plat as an
Emergency Access Easement and shall meet minimum requirements for the
fire lane.
Page 4
Number: 21 Created: 8 / 2 / 2007
[8/2/07] We will need to do a new development agreement since the legal
will change. I have included an informational sheet for the Development
Agreement that I need filled out and returned.
Number: 22 Created: 8 / 2 / 2007
[8/2/07] Please label the buildings on the utility plans (A, B, C...)
Number: 23 Created: 8 / 2 / 2007
[8/2/07] Need to show the ramp on the west side of Ziegler Road at Fossil
Lake Place. This ramp will need to be built with this project if it doesn't
exist. Make sure it is labeled as being installed.
Number: 24 Created: 8 / 2 / 2007
[8/2/07] The plans need some work to meet the City scanning
requirements. Have places where text are over lines and can not read the
text.
Number: 25 Created: 8 / 2 / 2007
[8/2/07] See redlines for additional comments.
Topic: Plat
Number: 9 Created: 8 / 2 / 2007
[8/2/07] Missing the Public Service easements that were previously on the
plat.
Number: 10 Created: 8 / 2 / 2007
[8/2/07] Need to place a note on the plat indicating what prior easements
are being vacated. Currently the plat states that this plat is subject to all
prior and existing easements. This means that you will have probably have
some easements that will be under your new building envelopes. If you
make a statement that all prior easements are to be vacated and rededicated
with this plat you will need to have Public Service and the Irrigation
company sign the plat to reaccept the new easements being dedicated to
them.
Number: 11 Created: 8 / 2 / 2007
[8/2/07] Technical Services Comments:
1. Boundaries close.
2. The plat should be named Fossil Lake Fourth Filing, 1st Replat
3. Minor text line problem, see redlines.
4. Identify on the plat how the streets were dedicated.
Page 3
Department: Engineering Issue Contact: Sheri
Langenberger
Topic: General
Number: 12 Created: 8 / 2 / 2007
[8/2/07] Need to better identify the phasing that is proposed. Label them
at Phase 1 and Phase 2. The phase line needs to be behind the row line as
both sides of the sidewalk will need to be built when the road is
constructed.
Number: 13 Created: 8 / 2 / 2007
[8/2/07] Is the grading to be phased?
Number: 14 Created: 8 / 2 / 2007
[8/2/07] Show the utilities as they exist now. Part of the waterline and the
northern fire hydrant is already installed.
Number: 15 Created: 8 / 2 / 2007
[8/2/07] If it is okay with the district it would be in your best interest if you
can move the northern sewer manhole south onto this property. That way
you would not have to repave the roadway to the north.
Number: 16 Created: 8 / 2 / 2007
[8/2/07] The Plank plans indicate that the curb return and pan for Fossil
Lake Place exists. If this is true please show this as existing on the plans.
If it is existing will it need to be reconstructed due to the extension of the
waterline into the site?
Number: 17 Created: 8 / 2 / 2007
[8/2/07] Need to show the emergency access road that exists on the plans.
The developer will need to work with Poudre Fire Authority during
construction to make sure that adequate access is maintained to the
northern property during construction.
Number: 18 Created: 8 / 2 / 2007
[8/2/07] Revise the plans to show that you will be connecting into the
street to the north rather than ending the road with barricades. Identify
that the roadway and sidewalks are to be tied into existing improvements
and show the actual off -site grades of the roadway to the north (50 ft is all
that is needed since it ties to existing).
Number: 19 Created: 8/ 2 / 2007
[8/2/07] Need to provide current sidewalk ramp details.
Number: 20 Created: 8 / 2 / 2007
[8/2/07] All plans (utility, site landscape and plat) need to have the same
title.
Page 2
STAFF PROJECT REVIEW
City of Fort Collins
Aller - Lingle Architects PC Date: 08/07/2007
c/o Brad Massey
712 Whalers Way, B-100
Fort Collins, CO 80525
Staff has reviewed your submittal for FOSSIL LAKE PDP, FOURTH FILING
- 1ST REPLAT (TYPE 1), and we offer the following comments:
ISSUES:
Department: Advance Planning
Topic: Fire
Number: 8
[7/31/07] No comment.
Issue Contact: Pete Wray
Created: 7/31 /2007
Department: Current Planning Issue Contact: Steve Olt
Topic: General
Number: 26 Created: 8 / 6 / 2007
[8/6/07] Rick Lee of the City's Building Department indicated that they
have no building code concerns associated with this replatting of the
property.
Number: 27 Created: 8 / 6 / 2007
[8/6/07] A copy of a response received from Bonnie Ham of the U.S. Postal
Service is attached to this comment letter.
Number: 28 Created: 8 / 6/ 2007
[8/6/07] A copy of comments received from Terry Farrill of the Fort
Collins -Loveland Water District and the South Fort Collins Sanitation
District is attached to this comment letter.
Number: 29 Created: 8 / 6 / 2007
[8/6/07] Glen Schlueter of the Stormwater Utility indicated that they
have no comments associated with the replat. However, there appears to be
a change in the amount of flow in the storm water basin and the swale has
been eliminated. The developer may have to put the swale back in.